Siemens / Unbalanced load protection _ Setting & highlights _ SI5080

Table of Contents

Overview

The “Unbalanced load protection” function detects unbalanced loads or line interruptions of electrical machines (generators and motors). Unbalanced loads create a counter-rotating magnetic field at double frequency in the rotor, and also overheat the damper winding.

For more detailed information on “Unbalanced load protection” function, refer to SIPROTEC 5 devices, V8.30 & higher manuals.

To see other supported functions, click here.


Structure/Embedding of the Function


Setting Parameters


Setting parameters for Unbalanced Load Protection

Addr. Parameter C Setting Options Default Setting
Therm. Stage 1
_:11011:1 Therm. Stage 1:Mode   off
on
test
off
_:11011:2 Therm. Stage 1:Operate & flt.rec. blocked   no
yes
no
_:11011:101 Therm. Stage 1:Max. continuously perm. I2   3.0 % to 30.0 % 10.0 %
_:11011:102 Therm. Stage 1:Unbalanced load factor K   1.0 s to 100.0 s 15.0 s
_:11011:103 Therm. Stage 1:Cooling time therm.replica   0 s to 50000 s 1500 s
_:11011:104 Therm. Stage 1:Warning delay   0.0 s to 60.0 s;∞ 15.0 s

Logic Diagrams & highlights


Logic Diagram of the Unbalanced-Load Protection Function

Logic Diagram of the Unbalanced-Load Protection Function

Operate Curve of the Unbalanced-Load Protection

Operate Curve of the Unbalanced-Load Protection

Calculation of functional measured value ΘI2/Θop

Calculation of functional measured value ΘI2/Θop

Example of an Unbalanced-Load Characteristic Specified by the Machine Manufacturer

Example of an Unbalanced-Load Characteristic Specified by the Machine Manufacturer