Siemens / Stator ground fault protection 100 % (20 Hz) _ Setting & highlights _ SI5088

Table of Contents

Overview

The “Stator ground fault protection 100 % (20 Hz)” function works with an injected 20-Hz voltage into the generator neutral point. It detects ground faults in the stator winding of generators connected to the electrical power system via a generator transformer, and also ground faults in the entire winding range (100%) including the machine neutral point.

For more detailed information on “Stator ground fault protection 100 % (20 Hz)” function, refer to SIPROTEC 5 devices, V8.30 & higher manuals.

To see other supported functions, click here.


Structure/Embedding of the Function

Structure/Embedding of the Function

Setting Parameters


General setting parameters

Addr. Parameter C Setting Options Default Setting
General
_:2311:106 General:I20< supervision 1 A @ 1.6 Irated 0.005 A to 0.040 A 0.010 A
5 A @ 1.6 Irated 0.025 A to 0.200 A 0.050 A
_:2311:107 General:V20< supervi- sion   0.300 V to 14.723 V 1.732 V
_:2311:101 General:Correction angle   -60.00 ° to 60.00 ° 0.00 °
_:2311:103 General:Transf. Resis- tance Rps   0.000 Ω to 700.000 Ω 0.000 Ω
_:2311:110 General:Sec./prim. factor R SGF   1.00 to 200.00 37.00
_:2311:1 General:RL-parallel acti- vate   no
yes
no
_:2311:104 General:RL-parallel   20.000 Ω to 700.000 Ω 20.000 Ω
_:2311:15 General:Correction factor RL-par.   -0.100 to 0.100 0.000

Setting parameters for Stage R(20 Hz)

Addr. Parameter C Setting Options Default Setting
R(20Hz)< 1
_:17011:1 R(20Hz)< 1:Mode   off
on
test
off
_:17011:2 R(20Hz)< 1:Operate & flt.rec. blocked   no
yes
yes
_:17011:3 R(20Hz)< 1:Threshold   20.000 Ω to 700.000 Ω 100.000 Ω
_:17011:6 R(20Hz)< 1:Operate delay   0.00 s to 60.00 s 10.00 s
R(20Hz)< 2
_:17012:1 R(20Hz)< 2:Mode   off
on
test
off
_:17012:2 R(20Hz)< 2:Operate & flt.rec. blocked   no
yes
no
_:17012:3 R(20Hz)< 2:Threshold   20.000 Ω to 700.000 Ω 20.000 Ω
_:17012:6 R(20Hz)< 2:Operate delay   0.00 s to 60.00 s 1.00 s

Setting parameters for Stage I(RMS)

Addr. Parameter C Setting Options Default Setting
I(RMS)> 1
_:17041:1 I(RMS)> 1:Mode   off
on
test
off
_:17041:2 I(RMS)> 1:Operate & flt.rec. blocked   no
yes
no
_:17041:3 I(RMS)> 1:Threshold 1 A @ 1.6 Irated 0.020 A to 1.500 A 0.400 A
5 A @ 1.6 Irated 0.100 A to 7.500 A 2.000 A
_:17041:6 I(RMS)> 1:Operate delay   0.00 s to 60.00 s 1.00 s

Logic Diagrams & highlights


Basic Principle of Voltage Injection into the Generator Neutral Point

Basic Principle of Voltage Injection into the Generator Neutral Point

Connection of the Stator Ground-Fault Protection 100 % (20 Hz) with Grounding Transformer or Neutral-Point Transformer

Connection of the Stator Ground-Fault Protection 100 % (20 Hz) with Grounding Transformer or Neutral-Point Transformer

System Configuration with Parallel Load Resistor

System Configuration with Parallel Load Resistor

Logic Diagram of the Functionality Across Stages

Logic Diagram of the Functionality Across Stages

Logic Diagram of an R(20 Hz)< Stage

Logic Diagram of an R(20 Hz)< Stage

Required calculations

Required calculations

Connection of the Stator Ground-Fault Protection 100 % (20 Hz) on a Primary Load Resistor

Connection of the Stator Ground-Fault Protection 100 % (20 Hz) on a Primary Load Resistor

Logic Diagram of an I(RMS)> Stage

Logic Diagram of an I(RMS)> Stage