Siemens / SIPROTEC 7SJ61 V4.9 setting parameters & highlights (SI4018)

Table of Contents

Overview

The SIPROTEC 7SJ61 relays can be used for line protection of high and medium voltage networks with earthed (grounded), low-resistance earthed, isolated or compensated neutral point. When protecting motors, the SIPROTEC 7SJ61 is suitable for asynchronous machines of all sizes.

For more detailed information on “SIPROTEC 7SJ61” relays, refer to SIPROTEC 4 devices manuals.

To see other supported devices, click here.


Functional Scope

Addr. Parameter C Setting Options Default Setting Comments
103 Grp Chge OPTION   Disabled
Enabled
Disabled Setting Group Change Option
104 OSC. FAULT REC.   Disabled
Enabled
Enabled Oscillographic Fault Records
112 Charac. Phase   Disabled
Definite Time
TOC IEC
TOC ANSI
User Defined PU
User def. Reset
Definite Time 50/51
113 Charac. Ground   Disabled
Definite Time
TOC IEC
TOC ANSI
User Defined PU
User def. Reset
Definite Time 50N/51N
117 Coldload Pickup   Disabled
Enabled
Disabled Cold Load Pickup
122 InrushRestraint   Disabled
Enabled
Disabled 2nd Harmonic Inrush Restraint
127 50 1Ph   Disabled
Enabled
Disabled 50 1Ph
131 Sens. Gnd Fault   Disabled
Definite Time
TOC IEC
TOC ANSI
User Defined PU
Log. inverse A
Log. Inverse B
Disabled (sensitive) Ground fault
133 INTERM.EF   Disabled
with Ignd
with 3I0
with Ignd,sens.
Disabled Intermittent earth fault protection
140 46   Disabled
TOC ANSI
TOC IEC
Definite Time
Disabled 46 Negative Sequence Protection
141 48   Disabled Enabled Disabled 48 Startup Time Supervision for Motors
142 49   Disabled
No ambient temp
With amb. temp.
Disabled 49 Thermal Overload Protection
143 66 #of Starts   Disabled
Enabled
Disabled 66 Startup Counter for Motors
144 LOAD JAM PROT.   Disabled
Enabled
Disabled Load Jam Protection
170 50BF   Disabled
Enabled
enabled w/ 3I0>
Disabled 50BF Breaker Failure Protection
171 79 Auto Recl.   Disabled
Enabled
Disabled 79 Auto-Reclose Function
172 52 B.WEAR MONIT   Disabled
Ix-Method
2P-Method
I2t-Method
Disabled 52 Breaker Wear Monitoring
182 74 Trip Ct Supv   Disabled
2 Binary Inputs
1 Binary Input
Disabled 74TC Trip Circuit Supervision
190 RTD-BOX INPUT   Disabled
Port C
Disabled External Temperature Input
191 RTD CONNECTION   6 RTD simplex
6 RTD HDX
12 RTD HDX
6 RTD simplex Ext. Temperature Input Connec- tion Type
FLEXIBLE FCT. 1…20   Flexible Function 01
Flexible Function 02
Flexible Function 03
Flexible Function 04
Flexible Function 05
Flexible Function 06
Flexible Function 07
Flexible Function 08
Flexible Function 09
Flexible Function 10
Flexible Function 11
Flexible Function 12
Flexible Function 13
Flexible Function 14
Flexible Function 15
Flexible Function 16
Flexible Function 17
Flexible Function 18
Flexible Function 19
Flexible Function 20
Please select Flexible Functions 1…20

Device, General Settings

Addr. Parameter C Setting Options Default Setting Comments
610 FltDisp.LED/LCD   Target on PU
Target on TRIP
Target on PU Fault Display on LED / LCD
617A T103 with 16 MV   YES
NO
OFF
NO T103-transfer limeted to 16 meas. values
625A T MIN LED HOLD   0 .. 60 min; ∞ 0 min Minimum hold time of latched LEDs
640 Start image DD   image 1
image 2
image 7
image 8
image 9
image 10
image 1 Start image Default Display
700 GOOSE-Stop   YES
NO
NO GOOSE-Stop

Power System Data 1

Addr. Parameter C Setting Options Default Setting Comments
201 CT Starpoint   towards Line
towards Busbar
towards Line CT Starpoint
204 CT PRIMARY   10 .. 50000 A 100 A CT Rated Primary Current
205 CT SECONDARY   1A
5A
1A CT Rated Secondary Current
207 Vnom-PRI VT V4   0.10 .. 800.00 kV 12.00 kV VT Rated Primary Voltage V4
208 Vnom-SEC VT V4   100 .. 225 V 100 V VT Rated Secondary Voltage V4
209 PHASE SEQ.   A B C
A C B
A B C Phase Sequence
210A TMin TRIP CMD   0.01 .. 32.00 sec 0.15 sec Minimum TRIP Command Duration
211A TMax CLOSE CMD   0.01 .. 32.00 sec 1.00 sec Maximum Close Command Duration
212 BkrClosed I MIN 1A 0.04 .. 1.00 A 0.04 A Closed Breaker Min. Current Threshold
5A 0.20 .. 5.00 A 0.20 A
214 Rated Frequency   50 Hz
60 Hz
50 Hz Rated Frequency
217 Ignd-CT PRIM   1 .. 50000 A 60 A Ignd-CT rated primary current
218 Ignd-CT SEC   1A
5A
1A Ignd-CT rated secondary current
235A ATEX100   NO
YES
NO Storage of th. Replicas w/o Power Supply
238 Ignd2-CT PRIM   1 .. 50000 A 60 A Ignd2-CT rated primary c. (conn. to I2)
250A 50/51 2-ph prot   ON
OFF
OFF 50, 51 Time Overcurrent with 2ph. prot.
251A CT Connect.   A, B, C, (Gnd)
A,G2,C,G; G->B
A,G2,C,G; G2->B
A, B, C, (Gnd) CT Connection
260 Ir-52   10 .. 50000 A 125 A Rated Normal Current (52 Breaker)
261 OP.CYCLES AT Ir   100 .. 1000000 10000 Switching Cycles at Rated Normal Current
262 Isc-52   10 .. 100000 A 25000 A Rated Short-Circuit Breaking Current
263 OP.CYCLES Isc   1 .. 1000 50 Switch. Cycles at Rated Short-Cir. Curr.
264 Ix EXPONENT   1.0 .. 3.0 2.0 Exponent for the Ix- Method
265 Cmd.via control   (Einstellmoglichkeiten anwendungsabhangig) none 52 B.Wear: Open Cmd. via Control Device
266 T 52 BREAKTIME   1 .. 600 ms 80 ms Breaktime (52 Breaker)
267 T 52 OPENING   1 .. 500 ms 65 ms Opening Time (52 Breaker)
276 TEMP. UNIT   Celsius
Fahrenheit
Celsius Unit of temperature meas- urement
280 Holmgr. for Σi   NO
YES
NO Holmgreen-conn. (for fast sum-i-monit.)
281A Swi.auth.via BI   NO
YES
OFF
NO Change switch.authority via binary input
282A Interl.on/offBI   NO
YES
OFF
NO Interlocking on or off via binary input
613A 50N/51N/67N w.   Ignd (measured)
3I0 (calcul.)
Ignd (measured) 50N/51N/67N Ground Overcurrent with

Oscillographic Fault Records

Addr. Parameter C Setting Options Default Setting Comments
401 WAVEFORMTRIGGER   Save w. Pickup
Save w. TRIP
Start w. TRIP
Save w. Pickup Waveform Capture
402 WAVEFORM DATA   Fault event
Pow.Sys.Flt.
Fault event Scope of Waveform Data
403 MAX. LENGTH   0.30 .. 5.00 sec 2.00 sec Max. length of a Waveform Capture Record
404 PRE. TRIG. TIME   0.05 .. 0.50 sec 0.25 sec Captured Waveform Prior to Trigger
405 POST REC. TIME   0.05 .. 0.50 sec 0.10 sec Captured Waveform after Event
406 BinIn CAPT.TIME   0.10 .. 5.00 sec; ∞ 0.50 sec Capture Time via Binary Input

Settings Groups

Addr. Parameter C Setting Options Default Setting Comments
302 CHANGE   Group A
Group B
Group C
Group D
Binary Input
Protocol
Group A Change to Another Setting Group

Power System Data 2

Addr. Parameter C Setting Options Default Setting Comments
1102 FullScaleCurr.   10 .. 50000 A 100 A Measurem: FullScaleCurrent(Equipm.rating)
1107 I MOTOR START 1A 0.40 .. 10.00 A 2.50 A Motor Start Current (Block 49, Start 48)
5A 2.00 .. 50.00 A 12.50 A
1114A Op.I meas.<1%   NO
YES
NO Operational current measurement < 1%

Overcurrent Protection 50, 51, 50N, 51N

Addr. Parameter C Setting Options Default Setting Comments
1201 FCT 50/51   ON
OFF
ON 50, 51 Phase Time Overcurrent
1202 50-2 PICKUP 1A 0.10 .. 35.00 A; ∞ 2.00 A 50-2 Pickup
5A 0.50 .. 175.00 A; ∞ 10.00 A  
1203 50-2 DELAY   0.00 .. 60.00 sec; ∞ 0.00 sec 50-2 Time Delay
1204 50-1 PICKUP 1A 0.10 .. 35.00 A; ∞ 1.00 A 50-1 Pickup
5A 0.50 .. 175.00 A; ∞ 5.00 A  
1205 50-1 DELAY   0.00 .. 60.00 sec; ∞ 0.50 sec 50-1 Time Delay
1207 51 PICKUP 1A 0.10 .. 4.00 A 1.00 A 51 Pickup
5A 0.50 .. 20.00 A 5.00 A  
1208 51 TIME DIAL   0.05 .. 3.20 sec; ∞ 0.50 sec 51 Time Dial
1209 51 TIME DIAL   0.50 .. 15.00 ; ∞ 5.00 51 Time Dial
1210 51 Drop-out   Instantaneous
Disk Emulation
Disk Emulation Drop-out characteristic
1211 51 IEC CURVE   Normal Inverse
Very Inverse
Extremely Inv.
Long Inverse
Normal Inverse IEC Curve
1212 51 ANSI CURVE   Very Inverse
Inverse
Short Inverse
Long Inverse
Moderately Inv.
Extremely Inv.
Definite Inv.
Very Inverse ANSI Curve
1213A MANUAL CLOSE   50-3 instant.
50-2 instant.
50 -1 instant.
51 instant.
Inactive
50-2 instant. Manual Close Mode
1214A 50-2 active   Always
with 79 active
Always 50-2 active
1215A 50 T DROP-OUT   0.00 .. 60.00 sec 0.00 sec 50 Drop-Out Time Delay
1216A 50-3 active   Always
with 79 active
Always 50-3 active
1217 50-3 PICKUP 1A 1.00 .. 35.00 A; ∞ ∞ A 50-3 Pickup
5A 5.00 .. 175.00 A; ∞ ∞ A  
1218 50-3 DELAY   0.00 .. 60.00 sec; ∞ 0.00 sec 50-3 Time Delay
1219A 50-3 measurem.   Fundamental
True RMS
Instantaneous
Fundamental 50-3 measurement of
1220A 50-2 measurem.   Fundamental
True RMS
Fundamental 50-2 measurement of
1221A 50-1 measurem.   Fundamental
True RMS
Fundamental 50-1 measurement of
1222A 51 measurem.   Fundamental
True RMS
Fundamental 51 measurement of
1230 51/51N   1.00 .. 20.00 I/Ip; ∞
0.01 .. 999.00 TD
  51/51N
1231 MofPU Res T/Tp   0.05 .. 0.95 I/Ip; ∞
0.01 .. 999.00 TD
  Multiple of Pickup <-> T/Tp
1301 FCT 50N/51N   ON
OFF
ON 50N, 51N Ground Time Overcurrent
1302 50N-2 PICKUP 1A 0.05 .. 35.00 A; ∞ 0.50 A 50N-2 Pickup
5A 0.25 .. 175.00 A; ∞ 2.50 A
1303 50N-2 DELAY   0.00 .. 60.00 sec; ∞ 0.10 sec 50N-2 Time Delay
1304 50N-1 PICKUP 1A 0.05 .. 35.00 A; ∞ 0.20 A 50N-1 Pickup
5A 0.25 .. 175.00 A; ∞ 1.00 A
1305 50N-1 DELAY   0.00 .. 60.00 sec; ∞ 0.50 sec 50N-1 Time Delay
1307 51N PICKUP 1A 0.05 .. 4.00 A 0.20 A 51N Pickup
5A 0.25 .. 20.00 A 1.00 A
1308 51N TIME DIAL   0.05 .. 3.20 sec; ∞ 0.20 sec 51N Time Dial
1309 51N TIME DIAL   0.50 .. 15.00 ; ∞ 5.00 51N Time Dial
1310 51N Drop-out   Instantaneous
Disk Emulation
Disk Emulation Drop-Out Characteristic
1311 51N IEC CURVE   Normal Inverse
Very Inverse
Extremely Inv.
Long Inverse
Normal Inverse IEC Curve
1312 51N ANSI CURVE   Very Inverse
Inverse
Short Inverse
Long Inverse
Moderately Inv.
Extremely Inv.
Definite Inv.
Very Inverse ANSI Curve
1313A MANUAL CLOSE   50N-3 instant.
50N-2 instant.
50N-1 instant.
51N instant.
Inactive
50N-2 instant. Manual Close Mode
1314A 50N-2 active   Always
With 79 Active
Always 50N-2 active
1315A 50N T DROP-OUT   0.00 .. 60.00 sec 0.00 sec 50N Drop-Out Time Delay
1316A 50N-3 active   Always
with 79 active
Always 50N-3 active
1317 50N-3 PICKUP   0.25 .. 35.00 A; ∞ ∞ A 50N-3 Pickup
1318 50N-3 DELAY   0.00 .. 60.00 sec; ∞ 0.00 sec 50N-3 Time Delay
1319A 50N-3 measurem.   Fundamental
True RMS
Instantaneous
Fundamental 50N-3 measurement of
1320A 50N-2 measurem.   Fundamental
True RMS
Fundamental 50N-2 measurement of
1321A 50N-1 measurem.   Fundamental
True RMS
Fundamental 50N-1 measurement of
1322A 51N measurem.   Fundamental
True RMS
Fundamental 51N measurement of
1330 50N/51N   1.00 .. 20.00 I/Ip; ∞
0.01 .. 999.00 TD
  50N/51N
1331 MofPU Res T/TEp   0.05 .. 0.95 I/Ip; ∞
0.01 .. 999.00 TD
  Multiple of Pickup <-> T/TEp
2201 INRUSH REST.   OFF
ON
OFF Inrush Restraint
2202 2nd HARMONIC   10 .. 45 % 15 % 2nd. harmonic in % of fundamental
2203 CROSS BLOCK   NO
YES
NO Cross Block
2204 CROSS BLK TIMER   0.00 .. 180.00 sec 0.00 sec Cross Block Time
2205 I Max 1A 0.30 .. 25.00 A 7.50 A Maximum Current for Inrush Restraint
5A 1.50 .. 125.00 A 37.50 A

Dynamic Cold Load Pickup

Addr. Parameter C Setting Options Default Setting Comments
1701 COLDLOAD PICKUP   OFF
ON
OFF Cold-Load-Pickup Function
1702 Start Condition   No Current
Breaker Contact
79 ready
No Current Start Condition
1703 CB Open Time   0 .. 21600 sec 3600 sec Circuit Breaker OPEN Time
1704 Active Time   1 .. 21600 sec 3600 sec Active Time
1705 Stop Time   1 .. 600 sec; ∞ 600 sec Stop Time
1801 50c-2 PICKUP 1A 0.10 .. 35.00 A; ∞ 10.00 A 50c-2 Pickup
5A 0.50 .. 175.00 A; ∞ 50.00 A
1802 50c-2 DELAY   0.00 .. 60.00 sec; ∞ 0.00 sec 50c-2 Time Delay
1803 50c-1 PICKUP 1A 0.10 .. 35.00 A; ∞ 2.00 A 50c-1 Pickup
5A 0.50 .. 175.00 A; ∞ 10.00 A
1804 50c-1 DELAY   0.00 .. 60.00 sec; ∞ 0.30 sec 50c-1 Time Delay
1805 51c PICKUP 1A 0.10 .. 4.00 A 1.50 A 51c Pickup
5A 0.50 .. 20.00 A 7.50 A
1806 51c TIME DIAL   0.05 .. 3.20 sec; ∞ 0.50 sec 51c Time dial
1807 51c TIME DIAL   0.50 .. 15.00 ; ∞ 5.00 51c Time dial
1808 50c-3 PICKUP 1A 1.00 .. 35.00 A; ∞ ∞ A 50c-3 Pickup
5A 5.00 .. 175.00 A; ∞ ∞ A
1809 50c-3 DELAY   0.00 .. 60.00 sec; ∞ 0.00 sec 50c-3 Time Delay
1901 50Nc-2 PICKUP 1A 0.05 .. 35.00 A; ∞ 7.00 A 50Nc-2 Pickup
5A 0.25 .. 175.00 A; ∞ 35.00 A
1902 50Nc-2 DELAY   0.00 .. 60.00 sec; ∞ 0.00 sec 50Nc-2 Time Delay
1903 50Nc-1 PICKUP 1A 0.05 .. 35.00 A; ∞ 1.50 A 50Nc-1 Pickup
5A 0.25 .. 175.00 A; ∞ 7.50 A
1904 50Nc-1 DELAY   0.00 .. 60.00 sec; ∞ 0.30 sec 50Nc-1 Time Delay
1905 51Nc PICKUP 1A 0.05 .. 4.00 A 1.00 A 51Nc Pickup
5A 0.25 .. 20.00 A 5.00 A
1906 51Nc T-DIAL   0.05 .. 3.20 sec; ∞ 0.50 sec 51Nc Time Dial
1907 51Nc T-DIAL   0.50 .. 15.00 ; ∞ 5.00 51Nc Time Dial
1908 50Nc-3 PICKUP   0.25 .. 35.00 A; ∞ ∞ A 50Nc-3 Pickup
1909 50Nc-3 DELAY   0.00 .. 60.00 sec; ∞ 0.00 sec 50Nc-3 Time Delay

Single-Phase Overcurrent Protection

Addr. Parameter C Setting Options Default Setting Comments
2701 50 1Ph   OFF
ON
OFF 50 1Ph
2702 50 1Ph-2 PICKUP 1A 0.05 .. 35.00 A; ∞ 0.50 A 50 1Ph-2 Pickup
5A 0.25 .. 175.00 A; ∞ 2.50 A
2703 50 1Ph-2 PICKUP   0.003 .. 1.500 A; ∞ 0.300 A 50 1Ph-2 Pickup
2704 50 1Ph-2 DELAY   0.00 .. 60.00 sec; ∞ 0.10 sec 50 1Ph-2 Time Delay
2705 50 1Ph-1 PICKUP 1A 0.05 .. 35.00 A; ∞ 0.20 A 50 1Ph-1 Pickup
5A 0.25 .. 175.00 A; ∞ 1.00 A
2706 50 1Ph-1 PICKUP   0.003 .. 1.500 A; ∞ 0.100 A 50 1Ph-1 Pickup
2707 50 1Ph-1 DELAY   0.00 .. 60.00 sec; ∞ 0.50 sec 50 1Ph-1 Time Delay

Negative Sequence Protection 46

Addr. Parameter C Setting Options Default Setting Comments
4001 FCT 46   OFF
ON
OFF 46 Negative Sequence Protection
4002 46-1 PICKUP 1A 0.05 .. 3.00 A 0.10 A 46-1 Pickup
5A 0.25 .. 15.00 A 0.50 A
4003 46-1 DELAY   0.00 .. 60.00 sec; ∞ 1.50 sec 46-1 Time Delay
4004 46-2 PICKUP 1A 0.05 .. 3.00 A 0.50 A 46-2 Pickup
5A 0.25 .. 15.00 A 2.50 A
4005 46-2 DELAY   0.00 .. 60.00 sec; ∞ 1.50 sec 46-2 Time Delay
4006 46 IEC CURVE   Normal Inverse
Very Inverse
Extremely Inv.
Extremely Inv. 46 IEC Curve
4007 46 ANSI CURVE   Extremely Inv.
Inverse
Moderately Inv.
Very Inverse
Extremely Inv. 46 ANSI Curve
4008 46-TOC PICKUP 1A 0.05 .. 2.00 A 0.90 A 46-TOC Pickup
5A 0.25 .. 10.00 A 4.50 A
4009 46-TOC TIMEDIAL   0.50 .. 15.00 ; ∞ 5.00 46-TOC Time Dial
4010 46-TOC TIMEDIAL   0.05 .. 3.20 sec; ∞ 0.50 sec 46-TOC Time Dial
4011 46-TOC RESET   Instantaneous
Disk Emulation
Instantaneous 46-TOC Drop Out
4012A 46 T DROP-OUT   0.00 .. 60.00 sec 0.00 sec 46 Drop-Out Time Delay

Motorprotection (Motor Starting Protection 48, Motor Restart Inhibit 66, LoadJam)

Addr. Parameter C Setting Options Default Setting Comments
4101 FCT 48   OFF
ON
OFF 48 Startup Time Supervision for Motors
4102 STARTUP CURRENT 1A 0.50 .. 16.00 A 5.00 A Startup Current
5A 2.50 .. 80.00 A 25.00 A
4103 STARTUP TIME   1.0 .. 180.0 sec 10.0 sec Startup Time
4104 LOCK ROTOR TIME   0.5 .. 180.0 sec; ∞ 2.0 sec Permissible Locked Rotor Time
4105 STARTUP T WARM   0.5 .. 180.0 sec; ∞ 10.0 sec Startup Time for warm motor
4106 TEMP.COLD MOTOR   0 .. 80 %; ∞ 25 % Temperature limit for cold motor
4301 FCT 66   OFF
ON
OFF 66 Startup Counter for Motors
4302 IStart/IMOTnom   1.10 .. 10.00 4.90 I Start / I Motor nominal
4303 T START MAX   1 .. 320 sec 10 sec Maximum Permissible Starting Time
4304 T Equal   0.0 .. 320.0 min 1.0 min Temperature Equalizaton Time
4305 I MOTOR NOMINAL 1A 0.20 .. 1.20 A 1.00 A Rated Motor Current
5A 1.00 .. 6.00 A 5.00 A
4306 MAX.WARM STARTS   1 .. 4 2 Maximum Number of Warm Starts
4307 #COLD-#WARM   1 .. 2 1 Number of Cold Starts – Warm Starts
4308 Kτ at STOP   0.2 .. 100.0 5.0 Extension of Time Constant at Stop
4309 Kτ at RUNNING   0.2 .. 100.0 2.0 Extension of Time Constant at Running
4310 T MIN. INHIBIT   0.2 .. 120.0 min 6.0 min Minimum Restart Inhibit Time
4311 ROTOR OVERLOAD   ON
OFF
Alarm Only
ON Rotor Overload Protection
4401 Load Jam Prot.   ON
OFF
Alarm Only
OFF Load Jam Protection
4402 Load Jam I> 1A 0.50 .. 12.00 A 2.00 A Load Jam Tripping Threshold
5A 2.50 .. 60.00 A 10.00 A
4403 TRIP DELAY   0.00 .. 600.00 sec 1.00 sec Load Jam Trip Delay
4404 I Alarm 1A 0.50 .. 12.00 A 1.80 A Load Jam Alarm Threshold
5A 2.50 .. 60.00 A 9.00 A
4405 ALARM DELAY   0.00 .. 600.00 sec 1.00 sec Load Jam Alarm Delay
4406 T Start Blk.   0.00 .. 600.00 sec 10.00 sec Load Jam Blocking after motor start


Thermal Overload Protection 49

Addr. Parameter C Setting Options Default Setting Comments
4201 FCT 49   ON
OFF
Alarm Only
OFF 49 Thermal overload protection
4202 49 K-FACTOR   0.10 .. 4.00 1.10 49 K-Factor
4203 TIME CONSTANT   1.0 .. 999.9 min 100.0 min Time Constant
4204 49 Θ ALARM   50 .. 100 % 90 % 49 Thermal Alarm Stage
4205 I ALARM 1A 0.10 .. 4.00 A 1.00 A Current Overload Alarm Setpoint
5A 0.50 .. 20.00 A 5.00 A
4207A Kτ-FACTOR   1.0 .. 10.0 1.0 Kt-FACTOR when motor stops
4208A T EMERGENCY   10 .. 15000 sec 100 sec Emergency time
4209 49 TEMP. RISE I   40 .. 200 °C 100 °C 49 Temperature rise at rated sec. curr.
4210 49 TEMP. RISE I   104 .. 392 °F 212 °F 49 Temperature rise at rated sec. curr.
4211 TEMPSENSOR RTD   1 .. 6 1 Temperature sensor connected to RTD
4212 TEMPSENSOR RTD   1 .. 12 1 Temperature sensor connected to RTD


Measurement Supervision

Addr. Parameter C Setting Options Default Setting Comments
5308A FFM Idiff (3ph) 1A 0.05 .. 1.00 A 0.10 A Differential Current Threshold (3phase)
5A 0.25 .. 5.00 A 0.50 A
8101 MEASURE. SUPERV   OFF
ON
ON Measurement Supervision
8104 BALANCE I LIMIT 1A 0.10 .. 1.00 A 0.50 A Current Threshold for Balance Monitoring
5A 0.50 .. 5.00 A 2.50 A
8105 BAL. FACTOR I   0.10 .. 0.90 0.50 Balance Factor for Current Monitor
8106 Σ I THRESHOLD 1A 0.05 .. 2.00 A; ∞ 0.10 A Summated Current Monitoring Threshold
5A 0.25 .. 10.00 A; ∞ 0.50 A
8107 Σ I FACTOR   0.00 .. 0.95 0.10 Summated Current Monitoring Factor
8109 FAST Σ i MONIT   OFF
ON
ON Fast Summated Current Monitoring
8110A T BAL. V LIMIT   0 .. 100 sec 5 sec T Balance Factor for Voltage Monitor
8111A T BAL. I LIMIT   0 .. 100 sec 5 sec T Current Balance Monitor

Trip Circuit Supervision 74TC

Addr. Parameter C Setting Options Default Setting Comments
8201 FCT 74TC   ON
OFF
ON 74TC TRIP Circuit Supervision
8202 Alarm Delay   1 .. 30 sec 2 sec Delay Time for alarm

Ground Fault Protection 64, 67N(s), 50N(s), 51N(s)

Addr. Parameter C Setting Options Default Setting Comments
3101 Sens. Gnd Fault   OFF
ON
OFF (Sensitive) Ground Fault
3113 50Ns-2 PICKUP   0.001 .. 1.500 A 0.300 A 50Ns-2 Pickup
3113 50Ns-2 PICKUP 1A 0.05 .. 35.00 A 10.00 A 50Ns-2 Pickup
5A 0.25 .. 175.00 A 50.00 A
3114 50Ns-2 DELAY   0.00 .. 320.00 sec; ∞ 1.00 sec 50Ns-2 Time Delay
3117 50Ns-1 PICKUP   0.001 .. 1.500 A 0.100 A 50Ns-1 Pickup
3117 50Ns-1 PICKUP 1A 0.05 .. 35.00 A 2.00 A 50Ns-1 Pickup
5A 0.25 .. 175.00 A 10.00 A
3118 50Ns-1 DELAY   0.00 .. 320.00 sec; ∞ 2.00 sec 50Ns-1 Time delay
3119 51Ns PICKUP   0.001 .. 1.400 A 0.100 A 51Ns Pickup
3119 51Ns PICKUP 1A 0.05 .. 4.00 A 1.00 A 51Ns Pickup
5A 0.25 .. 20.00 A 5.00 A
3119 51Ns PICKUP   0.003 .. 0.500 A 0.004 A 51Ns Pickup
3120 51NsTIME DIAL   0.05 .. 4.00 sec; ∞ 1.00 sec 51Ns Time Dial
3120 51c TIME DIAL   0.50 .. 15.00 ; ∞ 5.00 51c Time dial
3121A 50Ns T DROP-OUT   0.00 .. 60.00 sec 0.00 sec 50Ns Drop-Out Time Delay
3127 51Ns I T min   0.003 .. 1.400 A 1.333 A 51Ns Current at const. Time Delay T min
3127 51Ns I T min 1A 0.05 .. 20.00 A 15.00 A 51Ns Current at const. Time Delay T min
5A 0.25 .. 100.00 A 75.00 A
3128 51Ns I T knee   0.003 .. 0.650 A 0.040 A 51Ns Current at Knee Point
3128 51Ns I T knee 1A 0.05 .. 17.00 A 5.00 A 51Ns Current at Knee Point
5A 0.25 .. 85.00 A 25.00 A
3129 51Ns T knee   0.20 .. 100.00 sec 23.60 sec 51Ns Time Delay at Knee Point
3131 M.of PU TD   1.00 .. 20.00 MofPU; ∞
0.01 .. 999.00 TD
  Multiples of PU Time-Dial
3132 51Ns TD   0.05 .. 1.50 0.20 51Ns Time Dial
3140 51Ns Tmin   0.00 .. 30.00 sec 1.20 sec 51Ns Minimum Time Delay
3140 51Ns T min   0.10 .. 30.00 sec 0.80 sec 51Ns Minimum Time Delay
3141 51Ns Tmax   0.00 .. 30.00 sec 5.80 sec 51Ns Maximum Time Delay
3141 51Ns T max   0.50 .. 200.00 sec 93.00 sec 51Ns Maximum Time Delay (at 51Ns PU)
3142 51Ns TIME DIAL   0.05 .. 15.00 sec; ∞ 1.35 sec 51Ns Time Dial
3143 51Ns Startpoint   1.0 .. 4.0 1.1 51Ns Start Point of Inverse Charac.
3144 51Ns IEC CURVE   Normal Inverse
Very Inverse
Extremely Inv.
Long Inverse
Normal Inverse IEC Curve
3145 51Ns ANSI CURVE   Very Inverse
Inverse
Short Inverse
Long Inverse
Moderately Inv.
Extremely Inv.
Definite Inv.
Very Inverse ANSI Curve
3146 51Ns Drop-out   Instantaneous
Disk Emulation
Disk Emulation Drop-out characteristic
3160 α1 red.dir.area   1 .. 15 ° 2 ° Alpha1 (reduction directional area)
3161 α2 red.dir.area   1 .. 15 ° 2 ° Alpha2 (reduction directional area)

Intermittent Ground Fault Protection

Addr. Parameter C Setting Options Default Setting Comments
3301 INTERM.EF   OFF
ON
OFF Intermittent earth fault protection
3302 Iie> 1A 0.05 .. 35.00 A 1.00 A Pick-up value of interm. E/F stage
5A 0.25 .. 175.00 A 5.00 A
3302 Iie> 1A 0.05 .. 35.00 A 1.00 A Pick-up value of interm. E/F stage
5A 0.25 .. 175.00 A 5.00 A
3302 Iie>   0.005 .. 1.500 A 1.000 A Pick-up value of interm. E/F stage
3303 T-det.ext.   0.00 .. 10.00 sec 0.10 sec Detection extension time
3304 T-sum det.   0.00 .. 100.00 sec 20.00 sec Sum of detection times
3305 T-reset   1 .. 600 sec 300 sec Reset time
3306 Nos.det.   2 .. 10 3 No. of det. for start of int. E/F prot

Automatic Reclosing System 79

Addr. Parameter C Setting Options Default Setting Comments
7101 FCT 79   OFF
ON
OFF 79 Auto-Reclose Function
7103 BLOCK MC Dur.   0.50 .. 320.00 sec; 0 1.00 sec AR blocking duration after manual close
7105 TIME RESTRAINT   0.50 .. 320.00 sec 3.00 sec 79 Auto Reclosing reset time
7108 SAFETY 79 ready   0.01 .. 320.00 sec 0.50 sec Safety Time until 79 is ready
7113 CHECK CB?   No check
Chk each cycle
No check Check circuit breaker before AR?
7114 T-Start MONITOR   0.01 .. 320.00 sec; ∞ 0.50 sec AR start-signal monitoring time
7115 CB TIME OUT   0.10 .. 320.00 sec 3.00 sec Circuit Breaker (CB) Supervision Time
7116 Max. DEAD EXT.   0.50 .. 1800.00 sec; ∞ 100.00 sec Maximum dead time extension
7117 T-ACTION   0.01 .. 320.00 sec; ∞ ∞ sec Action time
7118 T DEAD DELAY   0.0 .. 1800.0 sec; ∞ 1.0 sec Maximum Time Delay of Dead- Time Start
7127 DEADTIME 1: PH   0.01 .. 320.00 sec 0.50 sec Dead Time 1: Phase Fault
7128 DEADTIME 1: G   0.01 .. 320.00 sec 0.50 sec Dead Time 1: Ground Fault
7129 DEADTIME 2: PH   0.01 .. 320.00 sec 0.50 sec Dead Time 2: Phase Fault
7130 DEADTIME 2: G   0.01 .. 320.00 sec 0.50 sec Dead Time 2: Ground Fault
7131 DEADTIME 3: PH   0.01 .. 320.00 sec 0.50 sec Dead Time 3: Phase Fault
7132 DEADTIME 3: G   0.01 .. 320.00 sec 0.50 sec Dead Time 3: Ground Fault
7133 DEADTIME 4: PH   0.01 .. 320.00 sec 0.50 sec Dead Time 4: Phase Fault
7134 DEADTIME 4: G   0.01 .. 320.00 sec 0.50 sec Dead Time 4: Ground Fault
7135 # OF RECL. GND   0 .. 9 1 Number of Reclosing Cycles Ground
7136 # OF RECL. PH   0 .. 9 1 Number of Reclosing Cycles Phase
7137 Cmd.via control   (Einstellmoglichkeiten anwendungsabhangig) none Close command via control device
7139 External SYNC   YES
NO
NO External 25 synchronisation
7140 ZONE SEQ.COORD.   OFF
ON
OFF ZSC – Zone sequence coordination
7150 50-1   No influence
Starts 79
Stops 79
No influence 50-1
7151 50N-1   No influence
Starts 79
Stops 79
No influence 50N-1
7152 50-2   No influence
Starts 79
Stops 79
No influence 50-2
7153 50N-2   No influence
Starts 79
Stops 79
No influence 50N-2
7154 51   No influence
Starts 79
Stops 79
No influence 51
7155 51N   No influence
Starts 79
Stops 79
No influence 51N
7163 46   No influence
Starts 79
Stops 79
No influence 46
7164 BINARY INPUT   No influence
Starts 79
Stops 79
No influence Binary Input
7165 3Pol.PICKUP BLK   YES
NO
NO 3 Pole Pickup blocks 79
7166 50-3   No influence
Starts 79
Stops 79
No influence 50-3
7167 50N-3   No influence
Starts 79
Stops 79
No influence 50N-3
7172 67Ns-1   No influence
Starts 79
Stops 79
No influence 67Ns-1
7173 67Ns-2   No influence
Starts 79
Stops 79
No influence 67Ns-2
7174 67Ns TOC   No influence
Starts 79
Stops 79
No influence 67Ns TOC
7175 bef.1.Cy:67Ns-1   Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 1. Cycle: 67Ns-1
7176 bef.1.Cy:67Ns-2   Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 1. Cycle: 67Ns-2
7177 bef.1Cy:67NsTOC   Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 1. Cycle: 67Ns TOC
7178 bef.2.Cy:67Ns-1   Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 2. Cycle: 67Ns-1
7179 bef.2.Cy:67Ns-2   Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 2. Cycle: 67Ns-2
7180 bef.2Cy:67NsTOC   Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 2. Cycle: 67Ns TOC
7181 bef.3.Cy:67Ns-1   Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 3. Cycle: 67Ns-1
7182 bef.3.Cy:67Ns-2   Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 3. Cycle: 67Ns-2
7183 bef.3Cy:67NsTOC   Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 3. Cycle: 67Ns TOC
7184 bef.4.Cy:67Ns-1   Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 4. Cycle: 67Ns-1
7185 bef.4.Cy:67Ns-2   Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 4. Cycle: 67Ns-2
7186 bef.4Cy:67NsTOC   Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 4. Cycle: 67Ns TOC
7200 bef.1.Cy:50-1   Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 1. Cycle: 50-1
7201 bef.1.Cy:50N-1   Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 1. Cycle: 50N-1
7202 bef.1.Cy:50-2   Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 1. Cycle: 50-2
7203 bef.1.Cy:50N-2   Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 1. Cycle: 50N-2
7204 bef.1.Cy:51   Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 1. Cycle: 51
7205 bef.1.Cy:51N   Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 1. Cycle: 51N
7212 bef.2.Cy:50-1   Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 2. Cycle: 50-1
7213 bef.2.Cy:50N-1   Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 2. Cycle: 50N-1
7214 bef.2.Cy:50-2   Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 2. Cycle: 50-2
7215 bef.2.Cy:50N-2   Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 2. Cycle: 50N-2
7216 bef.2.Cy:51   Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 2. Cycle: 51
7217 bef.2.Cy:51N   Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 2. Cycle: 51N
7224 bef.3.Cy:50-1   Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 3. Cycle: 50-1
7225 bef.3.Cy:50N-1   Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 3. Cycle: 50N-1
7226 bef.3.Cy:50-2   Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 3. Cycle: 50-2
7227 bef.3.Cy:50N-2   Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 3. Cycle: 50N-2
7228 bef.3.Cy:51   Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 3. Cycle: 51
7229 bef.3.Cy:51N   Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 3. Cycle: 51N
7236 bef.4.Cy:50-1   Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 4. Cycle: 50-1
7237 bef.4.Cy:50N-1   Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 4. Cycle: 50N-1
7238 bef.4.Cy:50-2   Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 4. Cycle: 50-2
7239 bef.4.Cy:50N-2   Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 4. Cycle: 50N-2
7240 bef.4.Cy:51   Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 4. Cycle: 51
7241 bef.4.Cy:51N   Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 4. Cycle: 51N
7248 bef.1.Cy:50-3   Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 1. Cycle: 50-3
7249 bef.1.Cy:50N-3   Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 1. Cycle: 50N-3
7250 bef.2.Cy:50-3   Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 2. Cycle: 50-3
7251 bef.2.Cy:50N-3   Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 2. Cycle: 50N-3
7252 bef.3.Cy:50-3   Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 3. Cycle: 50-3
7253 bef.3.Cy:50N-3   Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 3. Cycle: 50N-3
7254 bef.4.Cy:50-3   Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 4. Cycle: 50-3
7255 bef.4.Cy:50N-3   Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 4. Cycle: 50N-3

Breaker Failure Protection 50BF

Addr. Parameter C Setting Options Default Setting Comments
7001 FCT 50BF   OFF
ON
OFF 50BF Breaker Failure Protection
7004 Chk BRK CONTACT   OFF
ON
OFF Check Breaker contacts
7005 TRIP-Timer   0.06 .. 60.00 sec; ∞ 0.25 sec TRIP-Timer
7006 50BF PICKUP 1A 0.03 .. 20.00 A 0.10 A 50BF Pickup current threshold
5A 0.15 .. 100.00 A 0.50 A
7007 50BF PICKUP IE>   0.03 .. 20.00 A 0.10 A 50BF Pickup earth current threshold
7008 50BF-2 Delay   0.06 .. 60.00 sec; ∞ 0.50 sec Delay of 2nd stage for busbar trip

Flexible Protection Functions

Addr. Parameter C Setting Options Default Setting Comments
0 FLEXIBLE FUNC.   OFF
ON
Alarm Only
OFF Flexible Function
0 OPERRAT. MODE   3-phase
1-phase
no reference
3-phase Mode of Operation
0 BLK f out of r   YES
NO
YES Block while Freq. is out of range
0 MEAS. QUANTITY   Please select
Current
dV/dt rising
dV/dt falling
Binary Input
Please select Selection of Measured Quantity
0 MEAS. METHOD   Fundamental
True RMS
Positive seq.
Negative seq.
Zero sequence
Ratio I2/I1
Fundamental Selection of Measurement Method
0 PICKUP WITH   Exceeding
Dropping below
Exceeding Pickup with
0 CURRENT   Ia
Ib
Ic
In
In sensitive
In2
Ia Current
0 P.U. THRESHOLD 1A 0.03 .. 40.00 A 2.00 A Pickup Threshold
5A 0.15 .. 200.00 A 10.00 A
0 P.U. THRESHOLD 1A 0.03 .. 40.00 A 2.00 A Pickup Threshold
5A 0.15 .. 200.00 A 10.00 A
0 P.U. THRESHOLD   0.001 .. 1.500 A 0.100 A Pickup Threshold
0 P.U. THRESHOLD   2.0 .. 200.0 V 110.0 V Pickup Threshold
0 P.U. THRESHOLD 1A 0.5 .. 10000.0 VAR 200.0 VAR Pickup Threshold
5A 2.5 .. 50000.0 VAR 1000.0 VAR
0 P.U. THRESHOLD   15 .. 100 % 20 % Pickup Threshold
0 P.U. THRESHOLD   4 .. 100 V/s 60 V/s Pickup Threshold
0 T TRIP DELAY   0.00 .. 3600.00 sec 1.00 sec Trip Time Delay
0A T DROPOUT DELAY   0.00 .. 60.00 sec 0.00 sec Dropout Time Delay
0A DROPOUT RATIO   0.70 .. 0.99 0.95 Dropout Ratio
0A DROPOUT RATIO   1.01 .. 3.00 1.05 Dropout Ratio

Temperature Detection via RTD Boxes

Addr. Parameter C Setting Options Default Setting Comments
9011A RTD 1 TYPE   Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
Pt 100 Ω RTD 1: Type
9012A RTD 1 LOCATION   Oil
Ambient
Winding
Bearing
Other
Oil RTD 1: Location
9013 RTD 1 STAGE 1   -50 .. 250 °C; ∞ 100 °C RTD 1: Temperature Stage 1 Pickup
9014 RTD 1 STAGE 1   -58 .. 482 °F; ∞ 212 °F RTD 1: Temperature Stage 1 Pickup
9015 RTD 1 STAGE 2   -50 .. 250 °C; ∞ 120 °C RTD 1: Temperature Stage 2 Pickup
9016 RTD 1 STAGE 2   -58 .. 482 °F; ∞ 248 °F RTD 1: Temperature Stage 2 Pickup
9021A RTD 2 TYPE   Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
Not connected RTD 2: Type
9022A RTD 2 LOCATION   Oil
Ambient
Winding
Bearing
Other
Other RTD 2: Location
9023 RTD 2 STAGE 1   -50 .. 250 °C; ∞ 100 °C RTD 2: Temperature Stage 1 Pickup
9024 RTD 2 STAGE 1   -58 .. 482 °F; ∞ 212 °F RTD 2: Temperature Stage 1 Pickup
9025 RTD 2 STAGE 2   -50 .. 250 °C; ∞ 120 °C RTD 2: Temperature Stage 2 Pickup
9026 RTD 2 STAGE 2   -58 .. 482 °F; ∞ 248 °F RTD 2: Temperature Stage 2 Pickup
9031A RTD 3 TYPE   Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
Not connected RTD 3: Type
9032A RTD 3 LOCATION   Oil
Ambient
Winding
Bearing
Other
Other RTD 3: Location
9033 RTD 3 STAGE 1   -50 .. 250 °C; ∞ 100 °C RTD 3: Temperature Stage 1 Pickup
9034 RTD 3 STAGE 1   -58 .. 482 °F; ∞ 212 °F RTD 3: Temperature Stage 1 Pickup
9035 RTD 3 STAGE 2   -50 .. 250 °C; ∞ 120 °C RTD 3: Temperature Stage 2 Pickup
9036 RTD 3 STAGE 2   -58 .. 482 °F; ∞ 248 °F RTD 3: Temperature Stage 2 Pickup
9041A RTD 4 TYPE   Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
Not connected RTD 4: Type
9042A RTD 4 LOCATION   Oil
Ambient
Winding
Bearing
Other
Other RTD 4: Location
9043 RTD 4 STAGE 1   -50 .. 250 °C; ∞ 100 °C RTD 4: Temperature Stage 1 Pickup
9044 RTD 4 STAGE 1   -58 .. 482 °F; ∞ 212 °F RTD 4: Temperature Stage 1 Pickup
9045 RTD 4 STAGE 2   -50 .. 250 °C; ∞ 120 °C RTD 4: Temperature Stage 2 Pickup
9046 RTD 4 STAGE 2   -58 .. 482 °F; ∞ 248 °F RTD 4: Temperature Stage 2 Pickup
9051A RTD 5 TYPE   Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
Not connected RTD 5: Type
9052A RTD 5 LOCATION   Oil
Ambient
Winding
Bearing
Other
Other RTD 5: Location
9053 RTD 5 STAGE 1   -50 .. 250 °C; ∞ 100 °C RTD 5: Temperature Stage 1 Pickup
9054 RTD 5 STAGE 1   -58 .. 482 °F; ∞ 212 °F RTD 5: Temperature Stage 1 Pickup
9055 RTD 5 STAGE 2   -50 .. 250 °C; ∞ 120 °C RTD 5: Temperature Stage 2 Pickup
9056 RTD 5 STAGE 2   -58 .. 482 °F; ∞ 248 °F RTD 5: Temperature Stage 2 Pickup
9061A RTD 6 TYPE   Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
Not connected RTD 6: Type
9062A RTD 6 LOCATION   Oil
Ambient
Winding
Bearing
Other
Other RTD 6: Location
9063 RTD 6 STAGE 1   -50 .. 250 °C; ∞ 100 °C RTD 6: Temperature Stage 1 Pickup
9064 RTD 6 STAGE 1   -58 .. 482 °F; ∞ 212 °F RTD 6: Temperature Stage 1 Pickup
9065 RTD 6 STAGE 2   -50 .. 250 °C; ∞ 120 °C RTD 6: Temperature Stage 2 Pickup
9066 RTD 6 STAGE 2   -58 .. 482 °F; ∞ 248 °F RTD 6: Temperature Stage 2 Pickup
9071A RTD 7 TYPE   Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
Not connected RTD 7: Type
9072A RTD 7 LOCATION   Oil
Ambient
Winding
Bearing
Other
Other RTD 7: Location
9073 RTD 7 STAGE 1   -50 .. 250 °C; ∞ 100 °C RTD 7: Temperature Stage 1 Pickup
9074 RTD 7 STAGE 1   -58 .. 482 °F; ∞ 212 °F RTD 7: Temperature Stage 1 Pickup
9075 RTD 7 STAGE 2   -50 .. 250 °C; ∞ 120 °C RTD 7: Temperature Stage 2 Pickup
9076 RTD 7 STAGE 2   -58 .. 482 °F; ∞ 248 °F RTD 7: Temperature Stage 2 Pickup
9081A RTD 8 TYPE   Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
Not connected RTD 8: Type
9082A RTD 8 LOCATION   Oil
Ambient
Winding
Bearing
Other
Other RTD 8: Location
9083 RTD 8 STAGE 1   -50 .. 250 °C; ∞ 100 °C RTD 8: Temperature Stage 1 Pickup
9084 RTD 8 STAGE 1   -58 .. 482 °F; ∞ 212 °F RTD 8: Temperature Stage 1 Pickup
9085 RTD 8 STAGE 2   -50 .. 250 °C; ∞ 120 °C RTD 8: Temperature Stage 2 Pickup
9086 RTD 8 STAGE 2   -58 .. 482 °F; ∞ 248 °F RTD 8: Temperature Stage 2 Pickup
9091A RTD 9 TYPE   Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
Not connected RTD 9: Type
9092A RTD 9 LOCATION   Oil
Ambient
Winding
Bearing
Other
Other RTD 9: Location
9093 RTD 9 STAGE 1   -50 .. 250 °C; ∞ 100 °C RTD 9: Temperature Stage 1 Pickup
9094 RTD 9 STAGE 1   -58 .. 482 °F; ∞ 212 °F RTD 9: Temperature Stage 1 Pickup
9095 RTD 9 STAGE 2   -50 .. 250 °C; ∞ 120 °C RTD 9: Temperature Stage 2 Pickup
9096 RTD 9 STAGE 2   -58 .. 482 °F; ∞ 248 °F RTD 9: Temperature Stage 2 Pickup
9101A RTD10 TYPE   Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
Not connected RTD10: Type
9102A RTD10 LOCATION   Oil
Ambient
Winding
Bearing
Other
Other RTD10: Location
9103 RTD10 STAGE 1   -50 .. 250 °C; ∞ 100 °C RTD10: Temperature Stage 1 Pickup
9104 RTD10 STAGE 1   -58 .. 482 °F; ∞ 212 °F RTD10: Temperature Stage 1 Pickup
9105 RTD10 STAGE 2   -50 .. 250 °C; ∞ 120 °C RTD10: Temperature Stage 2 Pickup
9106 RTD10 STAGE 2   -58 .. 482 °F; ∞ 248 °F RTD10: Temperature Stage 2 Pickup
9111A RTD11 TYPE   Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
Not connected RTD11: Type
9112A RTD11 LOCATION   Oil
Ambient
Winding
Bearing
Other
Other RTD11: Location
9113 RTD11 STAGE 1   -50 .. 250 °C; ∞ 100 °C RTD11: Temperature Stage 1 Pickup
9114 RTD11 STAGE 1   -58 .. 482 °F; ∞ 212 °F RTD11: Temperature Stage 1 Pickup
9115 RTD11 STAGE 2   -50 .. 250 °C; ∞ 120 °C RTD11: Temperature Stage 2 Pickup
9116 RTD11 STAGE 2   -58 .. 482 °F; ∞ 248 °F RTD11: Temperature Stage 2 Pickup
9121A RTD12 TYPE   Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
Not connected RTD12: Type
9122A RTD12 LOCATION   Oil
Ambient
Winding
Bearing
Other
Other RTD12: Location
9123 RTD12 STAGE 1   -50 .. 250 °C; ∞ 100 °C RTD12: Temperature Stage 1 Pickup
9124 RTD12 STAGE 1   -58 .. 482 °F; ∞ 212 °F RTD12: Temperature Stage 1 Pickup
9125 RTD12 STAGE 2   -50 .. 250 °C; ∞ 120 °C RTD12: Temperature Stage 2 Pickup
9126 RTD12 STAGE 2   -58 .. 482 °F; ∞ 248 °F RTD12: Temperature Stage 2 Pickup

Average Measurements

Addr. Parameter C Setting Options Default Setting Comments
8301 DMD Interval   15 Min., 1 Sub
15 Min., 3 Subs
15 Min.,15 Subs
30 Min., 1 Sub
60 Min., 1 Sub
60 Min.,10 Subs
5 Min., 5 Subs
60 Min., 1 Sub Demand Calculation Intervals
8302 DMD Sync.Time   On The Hour
15 After Hour
30 After Hour
45 After Hour
On The Hour Demand Synchronization Time

Min/Max Measurement Setup

Addr. Parameter C Setting Options Default Setting Comments
8311 MinMax cycRESET   NO
YES
YES Automatic Cyclic Reset Function
8312 MiMa RESET TIME   0 .. 1439 min 0 min MinMax Reset Timer
8313 MiMa RESETCYCLE   1 .. 365 Days 7 Days MinMax Reset Cycle Period
8314 MinMaxRES.START   1 .. 365 Days 1 Days MinMax Start Reset Cycle in

error: Content is protected !!