Overview

The “Open pole detector” element detects if any pole of the associated circuit breaker is opened or the conductor is broken on the protected power line and cable.

For more detailed information on “Open pole detector” element, refer to GE, Universal Relay (UR) family of products, Version 8.0x manuals.

To see other supported elements, click here.


Setting Parameters


Modbus memory map for Setting parameters

Products Hex address Register name Range Units Step Format Default
N60 3DBE Open Pole Detect Function 0 to 1 1 F102 0 (Disabled)
" 3DBF Open Pole Detect Block 0 to 4294967295 1 F300 0
" 3DC1 Open Pole Detect A Aux Co 0 to 4294967295 1 F300 0
" 3DC3 Open Pole Detect B Aux Co 0 to 4294967295 1 F300 0
" 3DC5 Open Pole Detect C Aux Co 0 to 4294967295 1 F300 0
" 3DC7 Open Pole Detect Current Source 0 to 5 1 F167 0 (SRC 1)
" 3DC8 Open Pole Detect Current Pickup 0.05 to 20 pu 0.01 F001 20
" 3DC9 Open Pole Detect Voltage Source 0 to 5 1 F167 0 (SRC 1)
" 3DCA Open Pole Detect Voltage Input 0 to 1 1 F102 0 (Disabled)
" 3DCB Open Pole Detect Pickup Delay 0 to 65.535 s 0.001 F001 60
" 3DCC Open Pole Detect Reset Delay 0 to 65.535 s 0.001 F001 100
" 3DCD Open Pole Detect Target 0 to 2 1 F109 0 (Self-reset)
" 3DCE Open Pole Detect Events 0 to 1 1 F102 0 (Disabled)
" 3DCF Open Pole Detect Broken Co 0 to 1 1 F102 0 (Disabled)
F102 0 = Disabled, 1 = Enabled
F109 0 = Self-reset, 1 = Latched, 2 = Disabled
F167 0 = SRC 1, 1 = SRC 2, 2 = SRC 3, 3 = SRC 4, 4 = SRC 5, 5 = SRC 6

Logics & highlights


Open pole detector logic

Open pole detector logic