Overview
The “Generator stator overload protection”, is used to protect the stator winding against excessive temperature as a result of overcurrents. The functions operating characteristic is designed in accordance with the American standard IEEE-C50.13.
For more detailed information on “Generator stator overload protection” function, refer to ABB, Relion 670 Series manuals.
To see other supported functions, click here.
Function Identification
Function description | IEC 61850 identification |
IEC 60617 identification |
ANSI/IEEE C37.2 device number |
Generator stator overload protection | GSPTTR | 49S | |
Signals & Setting Parameters
GSPTTR function block
GSPTTR Input signals
GSPTTR Input signals | |||
Name | Type | Default | Description |
I3P | GROUP SIGNAL | – | Current Group Connection |
BLOCK | BOOLEAN | 0 | Block of function |
SETLKOUT | BOOLEAN | 0 | Input for forcing the output LOCKOUT |
RSTLKOUT | BOOLEAN | 0 | Reset of the output LOCKOUT and theta to 0% |
GSPTTR Output signals
GSPTTR Output signals | |||
Name | Type | Description | |
TRIP | BOOLEAN | General trip signal from the function | |
START | BOOLEAN | General start signal from the function | |
LOCKOUT | BOOLEAN | Trip lockout output (latched) | |
BLKRECL | BOOLEAN | Block machine closing command | |
GSPTTR Group settings (basic)
GSPTTR Group settings (basic) | |||||
Name | Values (Range) | Unit | Step | Default | Description |
Operation | Off On |
– | – | Off | Operation Off / On |
I> | 105.0 – 900.0 | % | 0.1 | 110.0 | Current pickup value for overload protection |
ReclsLevTheta | 1.0 – 100.0 | % | 0.1 | 70.0 | Level for theta in percent below which the generator can be reconnected to grid |
k1 | 1.00 – 200.00 | s | 0.01 | 37.50 | Time multiplier for thermal charact. operate time delay |
AutoLockout | Off On |
– | – | Off | Auto lockout enables activation of LOCKOUT when TRIP is set |
tPulse | 0.5 – 10.0 | s | 0.1 | 1.0 | Minimum pulse length of the trip signal |
tMin | 1.0 – 120.0 | s | 0.1 | 10.0 | Minimum time, used in operate characteristic |
tMax | 100.0 – 2000.0 | s | 0.1 | 300.0 | Maximum time, used in operate characteristic |
tCutOff | 10.0 – 2000.0 | s | 0.1 | 120.0 | Cut-off time, used in operate characteristic |
tReset | 10.0 – 2000.0 | s | 0.1 | 120.0 | Time required for Theta to reset from 100% to 0% |
GSPTTR Group settings (advanced)
GSPTTR Group settings (advanced) | |||||
Name | Values (Range) | Unit | Step | Default | Description |
PosSeqFactor | 0.0 – 10.0 | – | 0.1 | 1.0 | Weighting factor for the positive sequence current |
NegSeqFactor | 0.0 – 10.0 | – | 0.1 | 6.0 | Weighting factor for the negative sequence current |
GSPTTR Non group settings (basic)
GSPTTR Non group settings (basic) | |||||
Name | Values (Range) | Unit | Step | Default | Description |
MeasurCurrent | RMS PosSeqNegSeq |
– | – | RMS | Measured current quantity (RMS or weighted sum of positive and negative sequence) |
GlobalBaseSel | 1 – 12 | – | 1 | 1 | Selection of one of the Global Base Value groups |
GSPTTR Monitored data
GSPTTR Monitored data | ||||
Name | Type | Values (Range) | Unit | Description |
IMEAS | REAL | – | A | Measured current, used for calculation of operate time |
THETA | REAL | – | % | Overload in percent of set trip level (i.e. Trip=100%) |