Overview

The mho characteristics can be classified into Offset or Directional. The directional mho characteristics can be set to Offset, Forward or Reverse by the setting parameter DirMode. The offset mho characteristic can be set to Forward or Reverse or Non-Directional.

For more detailed information, refer to ABB, Relion 670 Series manuals.

To see other supported elements click here.


ZMHPDIS Identification

Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Full-scheme distance protection, mho characteristic ZMHPDIS Z< 21

Signals & Setting Parameters


ZMHPDIS function block

ZMHPDIS function block

ZMHPDIS Input signals

ZMHPDIS Input signals
Name Type Default Description
I3P GROUP SIGNAL Connection for current sample signals
U3P GROUP SIGNAL Connection for voltage sample signals
CURR_INP GROUP SIGNAL Connection for current signals
VOLT_INP GROUP SIGNAL Connection for voltage signals
POL_VOLT GROUP SIGNAL Connection for polarizing voltage
BLOCK BOOLEAN 0 Block of function
BLKZ BOOLEAN 0 Block due to fuse failure
BLKZMTD BOOLEAN 0 Block signal for blocking of time domaine function
BLKHSIR BOOLEAN 0 Blocks time domain function at high SIR
BLKTRIP BOOLEAN 0 Blocks all operate output signals
BLKPE BOOLEAN 0 Blocks phase-to-earth operation
BLKPP BOOLEAN 0 Blocks phase-to-phase operation
EXTNST BOOLEAN 0 External start
INTRNST BOOLEAN 0 Internal start
DIRCND INTEGER 0 External directional condition
STCND INTEGER 0 External start condition (loop enabler)
LDCND INTEGER 0 External load condition (loop enabler)

ZMHPDIS Output signals

ZMHPDIS Output signals
Name Type Description
TRIP BOOLEAN Trip General
TRL1 BOOLEAN Trip phase L1
TRL2 BOOLEAN Trip phase L2
TRL3 BOOLEAN Trip phase L3
TRPE BOOLEAN Trip phase-to-earth
TRPP BOOLEAN Trip phase-to-phase
START BOOLEAN Start General
STL1 BOOLEAN Start phase L1
STL2 BOOLEAN Start phase L2
STL3 BOOLEAN Start phase L3
STPE BOOLEAN Start phase-to-earth
STPP BOOLEAN Start phase-to-phase
STTIMER BOOLEAN Start timer

ZMHPDIS Group settings (basic)

ZMHPDIS Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off
On
Off Operation Off/On
DirMode Off
Offset
Forward
Reverse
Forward Direction mode
LoadEncMode Off
On
Off Load encroachment mode Off/On
ReachMode Overreach
Underreach
Overreach Reach mode Over/Underreach
ZnTimerSel Timers seperated
Timers linked
Internal start
Start from PhSel
External start
Timers seperated Zone timer selection
OpModePE Off
On
On Operation mode Off / On of Phase- Earth loops
ZPE 0.005 – 3000.000 Ohm/p 0.001 30.000 Positive sequence impedance setting for Phase-Earth loop
ZAngPE 10 – 90 Deg 1 85 Angle for positive sequence line impedance for Phase-Earth loop
KN 0.00 – 3.00 0.01 0.80 Magnitude of earth return compensation factor KN
KNAng -180 – 180 Deg 1 -15 Angle for earth return compensation factor KN
ZRevPE 0.005 – 3000.000 Ohm/p 0.001 30.000 Reverse reach of the phase to earth loop(magnitude)
tPE 0.000 – 60.000 s 0.001 0.000 Delay time for operation of phase to earth elements
IMinOpPE 10 – 30 %IB 1 20 Minimum operation phase to earth current
OpModePP Off
On
On Operation mode Off / On of Phase- Phase loops
ZPP 0.005 – 3000.000 Ohm/p 0.001 30.000 Impedance setting reach for phase to phase elements
ZAngPP 10 – 90 Deg 1 85 Angle for positive sequence line impedance for Phase-Phase elements
ZRevPP 0.005 – 3000.000 Ohm/p 0.001 30.000 Reverse reach of the phase to phase loop(magnitude)
tPP 0.000 – 60.000 s 0.001 0.000 Delay time for operation of phase to phase
IMinOpPP 10 – 30 %IB 1 20 Minimum operation phase to phase current

ZMHPDIS Group settings (advanced)

ZMHPDIS Group settings (advanced)
Name Values (Range) Unit Step Default Description
OffsetMhoDir Non-directional
Forward
Reverse
Non-directional Direction mode for offset mho
OpModetPE Off
On
On Operation mode Off / On of Zone timer, Ph-E
OpModetPP Off
On
On Operation mode Off / On of Zone timer, Ph-ph

ZMHPDIS Non group settings (basic)

ZMHPDIS Non group settings (basic)
Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 – 12 1 1 Selection of one of the Global Base Value groups

Logics & highlights


Load encroachment influence on the offset mho characteristic

Load encroachment influence on the offset mho characteristic

Mho, offset mho characteristic and the source impedance influence on the mho characteristic

Mho, offset mho characteristic and the source impedance influence on the mho characteristic

Simplified mho characteristic and vector diagram for phase L1-to-L2 fault

Simplified mho characteristic and vector diagram for phase L1-to-L2 fault

Simplified offset mho characteristic and voltage vectors for phase L1-to-L2 fault

Simplified offset mho characteristic and voltage vectors for phase L1-to-L2 fault

Simplified offset mho characteristic in forward direction for phase L1-to-L2 fault

Simplified offset mho characteristic in forward direction for phase L1-to-L2 fault

Operation characteristic for reverse phase L1-to-L2 fault

Operation characteristic for reverse phase L1-to-L2 fault

Simplified mho characteristic and vector diagram for phase L1-to- earth fault

Simplified mho characteristic and vector diagram for phase L1-to- earth fault

Simplified offset mho characteristic and voltage vector for phase L1-to- earth fault

Simplified offset mho characteristic and voltage vector for phase L1-to- earth fault

Simplified characteristic for offset mho in forward direction for L1-to-earth fault

Simplified characteristic for offset mho in forward direction for L1-to-earth fault

Simplified characteristic for offset mho in reverse direction for L1-to-earth fault

Simplified characteristic for offset mho in reverse direction for L1-to-earth fault

Simplified logic for release start signal

Simplified logic for release start signal

Composition of starting signals

Composition of starting signals

Tripping logic for the distance protection zone

Tripping logic for the distance protection zone

Zone timer logic

Zone timer logic