ABB / Zero sequence overcurrent protection (LCZSPTOC) for DTT _ Setting & highlights _ AB2116

Table of Contents

Overview

Zero sequence components are present in all abnormal conditions involving earth. They have a considerably high value during earth faults. The “Zero sequence overcurrent protection” is a definite time stage comparator function.

For more detailed information on “Zero sequence overcurrent protection” function, refer to ABB, Relion 670 Series manuals.

To see other supported functions, click here.


Function Identification

Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Zero sequence overcurrent protection LCZSPTOC 51N

Signals & Setting Parameters


LCZSPTOC Function block

LCZSPTOC Function block

LCZSPTOC Input signals

LCZSPTOC Input signals
Name Type Default Description
I3P GROUP SIGNAL Three phase group signal for current inputs
BLOCK BOOLEAN 0 Block overall function
BLKTR BOOLEAN 0 Block trip output

LCZSPTOC Output signals

LCZSPTOC Output signals
Name Type Description
TRIP BOOLEAN Trip signal for zero sequence over current protection
START BOOLEAN Start signal for zero sequence over current protection

LCZSPTOC Group settings (basic)

LCZSPTOC Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off
On
Off Operation Off/On
3I0> 3 – 2500 %IB 1 100 Zero sequence over current start value in % of IBase
t3I0 0.000 – 60.000 s 0.001 0.000 Time delay to operate

LCZSPTOC Non group settings (basic)

LCZSPTOC Non group settings (basic)
Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 – 12 1 1 Selection of one of the Global Base Value groups

LCZSPTOC Monitored data

LCZSPTOC Monitored data
Name Type Values (Range) Unit Description
3I0 Real A Zero sequence current value

Technical Data


LCZSPTOC technical data

LCZSPTOC technical data