GE / Wattmetric zero sequence directional (ANSI 32N, IEC PSDE) _ Element settings & highlights _ GU8078

Table of Contents

Overview

The “Wattmetric zero sequence directional” element responds to power derived from zero-sequence voltage and current in a direction specified by the element characteristic angle. The angle can be set within all four quadrants, and the power can be active or reactive. Therefore, the element can be used to sense either forward or reverse ground faults in either inductive, capacitive, or resistive networks. The inverse time characteristic allows time coordination of elements across the network.

For more detailed information on “Wattmetric zero sequence directional” element, refer to GE, Universal Relay (UR) family of products, Version 8.0x manuals.

To see other supported elements, click here.


Setting Parameters


Modbus memory map for Setting parameters

Products Hex address Register name Range Units Step Format Default
D30, D60, F35, F60, L60, L90 7630 Wattmetric Ground Fault 1 Function 0 to 1 1 F102 0 (Disabled)
" 7631 Wattmetric Ground Fault 1 Source 0 to 5 1 F167 0 (SRC 1)
" 7632 Wattmetric Ground Fault 1 Voltage 0 to 1 1 F234 0
(Calculated VN)
" 7633 Wattmetric Ground Fault 1 Overvoltage Pickup 0.02 to 3 pu 0.01 F001 20
" 7634 Wattmetric Ground Fault 1 Current 0 to 1 1 F235 0
(Calculated IN)
" 7635 Wattmetric Ground Fault 1 Overcurrent Pickup 0.002 to 30 pu 0.001 F001 60
" 7636 Wattmetric Ground Fault 1 Overcurrent Pickup Delay 0 to 600 s 0.01 F001 20
" 7637 Wattmetric Ground Fault 1 Power Pickup 0.001 to 1.2 pu 0.001 F001 100
" 7638 Wattmetric Ground Fault 1 ECA 0 to 360 ° Lag 1 F001 0
" 7639 Wattmetric Ground Fault 1 Power Pickup Delay 0 to 600 s 0.01 F001 20
" 763A Wattmetric Ground Fault 1 Curve 0 to 5 1 F236 0 (Definite Time)
" 763B Wattmetric Ground Fault 1 Multiplier 0.01 to 2 s 0.01 F001 100
" 763C Wattmetric Ground Fault 1 Block 0 to 4294967295 1 F300 0
" 763E Wattmetric Ground Fault 1 Target 0 to 2 1 F109 0 (Self-reset)
" 763F Wattmetric Ground Fault 1 Events 0 to 1 1 F102 0 (Disabled)
" 7640 Wattmetric Ground Fault 1 Reference Power 0.001 to 1.2 pu 0.001 F001 500
" 7641 Reserved 0 to 1 1 F001 0
" 7642 …Repeated for Wattmetric Ground Fault 2          
F35 7654 …Repeated for Wattmetric Ground Fault 3          
" 7666 …Repeated for Wattmetric Ground Fault 4          
" 7678 …Repeated for Wattmetric Ground Fault 5          
F102 0 = Disabled, 1 = Enabled
F109 0 = Self-reset, 1 = Latched, 2 = Disabled
F167 0 = SRC 1, 1 = SRC 2, 2 = SRC 3, 3 = SRC 4, 4 = SRC 5, 5 = SRC 6
F234 0 = Calculated VN, 1 = Measured VX
F235 0 = Calculated IN, 1 = Measured IG
F236 0 = Definite Time, 1 = Inverse, 2 = FlexCurve A, 3 = FlexCurve B, 4 = FlexCurve C, 5 = FlexCurve D

Logics & highlights


Definitions

Definitions

Wattmetric characteristic angle response

Wattmetric characteristic angle response