GE / VT fuse failure _ Element settings & highlights _ GU8238

Table of Contents

Overview

The “VT fuse failure” detector is used to raise an alarm and/or block elements that operate incorrectly for a full or partial loss of AC potential caused by one or more blown fuses. Some elements that can be blocked (via the BLOCK input) are distance, voltage restrained overcurrent, and directional current.

For more detailed information on “VT fuse failure” detector, refer to GE, Universal Relay (UR) family of products, Version 8.0x manuals.

To see other supported elements, click here.


Setting Parameters


Modbus memory map for Setting parameters

Products Hex address Register name Range Units Step Format Default
B30, C60, C70, C95, D30, D60, F35, F60, G30, G60, L30, L60, L90, M60, N60, T60 CF1A VT Fuse Failure Function 0 to 1 1 F102 0 (Disabled)
" CF1B VT Fuse Failure Neutral Wire Open Function 0 to 1 1 F102 0 (Disabled)
" CF1C VT Fuse Failure Neutral Wire Open 3rd Harmonic Pickup 0.004 to 3 pu 0.001 F001 100
" CF1D VT Fuse Failure 1 Alarm Delay 0 to 65.535 s 0.001 F001 1000
B30 CF1E VT Fuse Failure 1 CT Source 0 to 30 1 F677 0 (None0
B30, C60, C70, C95, D30, D60, F35, F60, G30, G60, L30, L60, L90, M60, N60, T60 CF1F …Repeated for Source 2          
B30, C60, C70, C95, D60, F35, F60, G30, G60, L60, L90, M60, N60, T60 CF24 …Repeated for Source 3          
" CF29 …Repeated for Source 4          
B30, C70, F35, N60, T60 CF2E …Repeated for Source 5          
" CF33 …Repeated for Source 6          
F102 0 = Disabled, 1 = Enabled
F677 0 = None, 1 = SRC 1, 2 = SRC 2, 3 = SRC 3, 4 = SRC 4, 5 = SRC 5, 6 = SRC 6, 7 = SRC 7

Logics & highlights


VT fuse fail logic

VT fuse fail logic