Overview

The “Voltage unbalance protection of shunt capacitor bank” function uses the neutral voltage measurement of an ungrounded single or double WYE configuration of SCB. The protection arrangements are based on the terminal voltage limit and the current limit of the capacitor units.

For more detailed information on “Voltage unbalance protection of shunt capacitor bank” function, refer to ABB, Relion 670 Series manuals.

To see other supported functions, click here.


Function Identification

Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Voltage unbalance protection of the shunt capacitor bank SCUVPTOV Uub > 60V

Signals & Setting Parameters


SCUVPTOV function block

SCUVPTOV function block

SCUVPTOV Input signals

SCUVPTOV Input signals
Name Type Default Description
U3P GROUP SIGNAL Group signal for three phase bus voltage
U3NEUT GROUP SIGNAL Group signal for capacitor bank neutral voltage
BLOCK BOOLEAN 0 Block of function
BLKTR BOOLEAN 0 Block of trip
BLKALM BOOLEAN 0 Block of alarm
BLKWRN BOOLEAN 0 Block of warning
INHIBIT BOOLEAN 0 Inhibit the function
TRIGCOMP BOOLEAN 0 Trigger input to store the calculated compensation factors into the IED memory. The stored values will be used for future compensation in the function.
RESETCOMP BOOLEAN 0 Force the stored compensation factors to zero.

SCUVPTOV Output signals

SCUVPTOV Output signals
Name Type Description
TRIP BOOLEAN Trip signal
START BOOLEAN Start signal
ALARM BOOLEAN Alarm signal
WARNING BOOLEAN Warning signal
BLKD BOOLEAN Block due to bus voltage in any phase is lower than the set UMin> value or SCB disconnection is detected
COMPEXED BOOLEAN Indicates that a trigger was made for compensation
PUNUNBAL REAL Capacitor bank neutral unbalance voltage in % of UBase

SCUVPTOV Non group settings (basic)

SCUVPTOV Non group settings (basic)
Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 – 12 1 1 Selection of one of the Global Base Value groups

SCUVPTOV Group settings (basic)

SCUVPTOV Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off
On
Off Operation Off / On
UMin> 5.0 – 100.0 %UB 0.1 75.0 Minimum bus voltage for operation in
% of UBase
CompEnable Disable
Enable
Enable Selection of neutral voltage unbalance compensation
UNUnbalWrn> 1.0 – 95.0 %UB 0.1 1.0 Neutral voltage unbalance warning level in % of UBase
tDefWrn 0.00 – 60.00 s 0.01 5.00 Definite time delay to warning
UNUnbalAlm> 1.0 – 95.0 %UB 0.1 2.5 Neutral voltage unbalance alarm level in % of UBase
tDefAlm 0.00 – 60.00 s 0.01 5.00 Definite time delay to alarm
UNUnbal> 1.0 – 95.0 %UB 0.1 5.5 Neutral voltage unbalance trip level in
% of UBase
CurveType Definite time
Programmable
Definite time Selection of time delay curve type for trip
tDefTrip 0.00 – 60.00 s 0.01 5.00 Definite time delay for trip
k 0.05 – 15.00 0.01 0.05 Time multiplier for programmable curve for trip
tMin 0.00 – 60.00 s 0.01 0.10 Minimum operate time for programmable curve for trip
tReset 0.00 – 60.00 s 0.01 0.02 Reset time delay for warning, alarm and trip
tPCrv 0.000 – 3.000 0.001 1.000 Parameter P for programmable curve for trip
tACrv 0.005 – 200.000 0.001 1.000 Parameter A for programmable curve for trip
tBCrv 0.50 – 100.00 0.01 1.00 Parameter B for programmable curve for trip
tCCrv 0.0 – 1.0 0.1 0.0 Parameter C for programmable curve for trip
tDCrv 0.000 – 60.000 0.001 0.000 Parameter D for programmable curve for trip
CrvSat 0 – 100 1 0 Tuning parameter for programmable curve

SCUVPTOV Non group settings (advanced)

SCUVPTOV Non group settings (advanced)
Name Values (Range) Unit Step Default Description
BlockTrip Trip disabled
Trip enabled
Trip enabled Trip blocked / enabled

SCUVPTOV Monitored data

SCUVPTOV Monitored data
Name Type Values (Range) Unit Description
LASTCOMP GROUP SIGNAL Indicates date and time when the last trigger was made for compensation
UNUNBAL REAL kV Instantaneous magnitude of capacitor bank neutral unbalance voltage
PUNUNBAL REAL % Capacitor bank neutral unbalance voltage in % of UBase
UL1 REAL kV Bus voltage of phase L1
UL2 REAL kV Bus voltage of phase L2
UL3 REAL kV Bus voltage of phase L3
UNSCB REAL kV Capacitor bank neutral voltage
K1USED REAL Used compensation factor of K1 for unbalance neutral voltage calculation
K2USED REAL Used compensation factor of K2 for unbalance neutral voltage calculation
K1MON REAL Monitored compensation factor of K1 for unbalance neutral voltage calculation
K2MON REAL Monitored compensation factor of K2 for unbalance neutral voltage calculation

Technical data


Technical data

Logics & highlights


Protection scheme for ungrounded double WYE capacitor bank

Protection scheme for ungrounded double WYE capacitor bank

Single line diagram for an ungrounded double WYE capacitor bank

Single line diagram for an ungrounded double WYE capacitor bank

Units arrangement in an ungrounded double WYE connected capacitor bank

Units arrangement in an ungrounded double WYE connected capacitor bank

Single line diagram for an ungrounded single WYE capacitor bank

Single line diagram for an ungrounded single WYE capacitor bank

Units arrangement in an ungrounded single WYE connected capacitor bank

Units arrangement in an ungrounded single WYE connected capacitor bank

Ungrounded single WYE SCB connected to function block

Ungrounded single WYE SCB connected to function block

Programmable curve

Programmable curve

SCUVPTOV block diagram

SCUVPTOV block diagram

Simplified Warning, Alarm, and Trip logic

Simplified Warning, Alarm, and Trip logic

Reporting over IEC 61850

Reporting over IEC 61850