Overview

In the “Voltage current 3 phase” function group, you can use all the functions for protection and supervision of a protected object or equipment that allows 3-phase current and voltage measurement. The function group also contains the operational measurement for the protected object or equipment.

For more detailed information on “Voltage current 3 phase” function group, refer to SIPROTEC 5 devices, V8.30 & higher manuals.

To see other supported function groups, click here.


Structure of the Voltage-Current 3-Phase Function Group

Structure of the Voltage-Current 3-Phase Function Group

Structure/Embedding of the Process Monitor Function

Structure/Embedding of the Process Monitor Function

Setting Parameters


Write-Protected Settings for Voltage-Current 3-Phase Function Group

Addr. Parameters C Range of Values Default Setting
Network data
_:103 General:rated apparent power   0.20 MVA to 5 000.00 MVA 692.82 MVA

Setting parameters for Voltage-Current 3-Phase Function Group

Addr. Parameter C Setting Options Default Setting
Rated values
_:9451:101 General:Rated current   1.00 A to 100000.00 A 1000.00 A
_:9451:102 General:Rated voltage   0.20 kV to 1200.00 kV 400.00 kV
Power-system data
_:9451:149 General:Power-sys. neutral point   grounded
suppress. coil grounded
isolated
grounded
Measurements
_:9451:158 General:P, Q sign   not reversed
reversed
not reversed

Setting parameters for Process Monitor: Cold-Load Pickup Detection (Optional)

Addr. Parameter C Setting Options Default Setting
Cold-load PU
_:1 Cold-load PU:Mode   off
on
test
off
_:101 Cold-load PU:Operating mode   I open
CB and I open
I open
_:102 Cold-load PU:Dropout threshold current 1 A @ 100 Irated 0.030 A to 10.000 A 1.000 A
5 A @ 100 Irated 0.15 A to 50.00 A 5.00 A
1 A @ 50 Irated 0.030 A to 10.000 A 1.000 A
5 A @ 50 Irated 0.15 A to 50.00 A 5.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.000 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 5.000 A
_:103 Cold-load PU:Dropout delay curr.crit.   1 s to 600 s 600 s
_:104 Cold-load PU:Dropout delay CB closed   1 s to 21600 s 3600 s
_:105 Cold-load PU:Min. CB- open time   0 s to 21600 s 3600 s

Logic Diagrams & highlights


Operational Measured Values of the Voltage-Current 3-Phase Function Group

Operational Measured Values of the Voltage-Current 3-Phase Function Group

Creation of the Pickup Indication of the Voltage-Current 3-Phase Function Group

Creation of the Pickup Indication of the Voltage-Current 3-Phase Function Group

Creation of the Operate Indication of the Voltage-Current 3-Phase Function Group

Creation of the Operate Indication of the Voltage-Current 3-Phase Function Group

Logic Diagram of the Overall Function Process Monitor

Logic Diagram of the Overall Function Process Monitor

Logic Diagram of the Current-Flow Criterion Function Block

Logic Diagram of the Current-Flow Criterion Function Block

Logic Diagram of the Circuit-Breaker Condition for the Protected-Object Function Block

Logic Diagram of the Circuit-Breaker Condition for the Protected-Object Function Block

Logic Diagram of Closure Detection

Logic Diagram of Closure Detection

Logic Diagram of the Cold-Load Pickup Detection Function Block

Logic Diagram of the Cold-Load Pickup Detection Function Block