Siemens / “Voltage current 1 phase” function group _ Setting & highlights _ SI5202

Table of Contents

Overview

In the “Voltage current 1 phase” function group, all functions can be used for protecting and for monitoring a protection object or equipment that allow a 1-phase current and voltage measurement or a zero-sequence voltage measurement via the 3-phase voltage measuring point.

For more detailed information on “Voltage current 1 phase” function group, refer to SIPROTEC 5 devices, V8.30 & higher manuals.

To see other supported function groups, click here.


Structure of the Voltage-Current 1-Phase Function Group

Structure of the Voltage-Current 1-Phase Function Group

Setting Parameters


Write-Protected Settings

Addr. Parameter C Setting Options Default Setting
Rated values
_:9421:103 General:Rated apparent power   -1.00 MVA to -1.00 MVA 0.00 MVA
Power-system data
_:9421:214 General:M I-1ph uses MeasP with ID   0 to 100 0
_:9421:223 General:CT mismatch M I-1ph   0.00 to 100.00 0.00

Setting parameters for Voltage-Current 1-Phase Function Group

Addr. Parameter C Setting Options Default Setting
Rated values
_:9421:101 General:Rated current   1 A to 100 000 A 1000 A
_:9421:102 General:Rated voltage   0.20 kV to 1200.00 kV 400.00 kV
Measurements
_:9421:150 General:P, Q sign   not reversed
reversed
not reversed

Logic Diagrams & highlights


Voltage input Properties

Voltage input Properties

Fundamental Components of the Voltage-Current 1-Phase Function Group

Fundamental Components of the Voltage-Current 1-Phase Function Group

Operational Measured Values of the Voltage-Current 1-Phase Function Group

Operational Measured Values of the Voltage-Current 1-Phase Function Group