Overview

The “Undervoltage protection with positive sequence voltage” function monitors the permissible voltage range, protects equipment (for example, plant components and machines) from damages caused by undervoltage. It also protects motors and generators from inadmissible operating states and a possible loss of stability in the event of voltage dips.

For more detailed information on “Undervoltage protection with positive sequence voltage” function, refer to SIPROTEC 5 devices, V8.30 & higher manuals.

To see other supported functions, click here.


Structure/Embedding of the Function

Structure/Embedding of the Undervoltage protection with positive sequence voltage Function

Setting Parameters


Setting parameters for Undervoltage protection with positive sequence voltage

Addr. Parameter C Setting Options Default Setting
General
_:2311:104 General:Current-flow criterion   off
on
on
_:2311:101 General:Threshold I> 1 A @ 100 Irated 0.030 A to 10.000 A 0.050 A
5 A @ 100 Irated 0.15 A to 50.00 A 0.25 A
1 A @ 50 Irated 0.030 A to 10.000 A 0.050 A
5 A @ 50 Irated 0.15 A to 50.00 A 0.25 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 0.050 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 0.250 A
Stage 1
_:481:1 Stage 1:Mode   off
on
test
off
_:481:2 Stage 1:Operate & flt.rec. blocked   no
yes
no
_:481:10 Stage 1:Blk. by meas.- volt. failure   no
yes
yes
_:481:101 Stage 1:Pickup delay   no
yes
no
_:481:3 Stage 1:Threshold   0.300 V to 200.000V 46.000V
_:481:4 Stage 1:Dropout ratio   1.01 to 1.20 1.05
_:481:6 Stage 1:Operate delay   0.00 s to 60.00 s 3.00 s
Stage 2
_:482:1 Stage 2:Mode   off
on
test
off
_:482:2 Stage 2:Operate & flt.rec. blocked   no
yes
no
_:482:10 Stage 2:Blk. by meas.- volt. failure   no
yes
yes
_:482:101 Stage 2:Pickup delay   no
yes
no
_:482:3 Stage 2:Threshold   0.300 V to 200.000 V 40.000V
_:482:4 Stage 2:Dropout ratio   1.01 to 1.20 1.05
_:482:6 Stage 2:Operate delay   0.00 s to 60.00 s 0.50 s

Logic Diagrams & highlights


Logic Diagram of the Stage Undervoltage Protection with Positive-Sequence Voltage

Logic Diagram of the Stage Undervoltage Protection with Positive-Sequence Voltage