Siemens / Undervoltage protection with any voltage (ANSI 27) _ Setting & highlights _ SI5047

Table of Contents

Overview

The “Undervoltage protection with any voltage” function detects any 1-phase undervoltage and is intended for special applications.

For more detailed information on “Undervoltage protection with any voltage” function, refer to SIPROTEC 5 devices, V8.30 & higher manuals.

To see other supported functions, click here.


Structure/Embedding of the Function

Structure/Embedding of the Undervoltage protection with any voltage Function

Setting Parameters


Setting parameters for Undervoltage protection with any voltage

Addr. Parameter C Setting Options Default Setting
General
_:2311:101 General:Current-flow criterion   off
on
on
Stage 1
_:571:1 Stage 1:Mode   off
on
test
off
_:571:2 Stage 1:Operate & flt.rec. blocked   no
yes
no
_:571:9 Stage 1:Measured value   VA measured
VB measured
VC measured
VAB measured
VBC measured
VCA measured
VAB calculated
VBC calculated
VCA calculated
V0 calculated
VA measured
_:571:8 Stage 1:Method of measurement   fundamental comp.
RMS value
fundamental comp.
_:571:3 Stage 1:Threshold   0.300 V to 340.000 V 80.000 V
_:571:4 Stage 1:Dropout ratio   1.01 to 1.20 1.05
_:571:6 Stage 1:Operate delay   0.00 s to 60.00 s 3.00 s
Stage 2
_:572:1 Stage 2:Mode   off
on
test
off
_:572:2 Stage 2:Operate & flt.rec. blocked   no
yes
no
_:572:9 Stage 2:Measured value   VA measured
VB measured
VC measured
VAB measured
VBC measured
VCA measured
VAB calculated
VBC calculated
VCA calculated
V0 calculated
VA measured
_:572:8 Stage 2:Method of measurement   fundamental comp.
RMS value
fundamental comp.
_:572:3 Stage 2:Threshold   0.300 V to 340.000 V 65.000 V
_:572:4 Stage 2:Dropout ratio   1.01 to 1.20 1.05
_:572:6 Stage 2:Operate delay   0.00 s to 60.00 s 0.50 s

Logic Diagrams & highlights


Logic Diagram of an Undervoltage Protection with Any Voltage Stage

Logic Diagram of an Undervoltage Protection with Any Voltage Stage