Siemens / Undervoltage protection with 3 phase voltage (ANSI 27) _ Setting & highlights _ SI5045

Table of Contents

Overview

The “Undervoltage protection with 3 phase voltage” function monitors the permissible voltage range, protects equipment (for example, plant components and machines) against damages caused by undervoltage and handles disconnection or load shedding tasks in a system.

For more detailed information on “Undervoltage protection with 3 phase voltage” function, refer to SIPROTEC 5 devices, V8.30 & higher manuals.

To see other supported functions, click here.


Structure/Embedding of the Function

Structure/Embedding of the Undervoltage protection with 3 phase voltage Function

Setting Parameters


Setting parameters for Stage with Definite-Time Characteristic Curve

Addr. Parameter C Setting Options Default Setting
General
_:2311:104 General:Current-flow criterion   off
on
on
_:2311:101 General:Threshold I> 1 A @ 100 Irated 0.030 A to 10.000 A 0.050 A
5 A @ 100 Irated 0.15 A to 50.00 A 0.25 A
1 A @ 50 Irated 0.030 A to 10.000 A 0.050 A
5 A @ 50 Irated 0.15 A to 50.00 A 0.25 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 0.050 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 0.250 A
_:2311:103 General:Stabilization counter   0 to 10 0
Definite-T 1
_:421:1 Definite-T 1:Mode   off
on
test
off
_:421:2 Definite-T 1:Operate & flt.rec. blocked   no
yes
no
_:421:10 Definite-T 1:Blk. by meas.-volt. failure   no
yes
yes
_:421:9 Definite-T 1:Measured value   phase-to-ground
phase-to-phase
phase-to-phase
_:421:8 Definite-T 1:Method of measurement   fundamental comp.
RMS value
fundamental comp.
_:421:101 Definite-T 1:Pickup mode   1 out of 3
3 out of 3
1 out of 3
_:421:102 Definite-T 1:Pickup delay   no
yes
no
_:421:3 Definite-T 1:Threshold   0.300 V to 175.000 V 80.000 V
_:421:4 Definite-T 1:Dropout ratio   1.01 to 1.20 1.05
_:421:6 Definite-T 1:Operate delay   0.00 s to 60.00 s 3.00 s
Definite-T 2
_:422:1 Definite-T 2:Mode   off
on
test
off
_:422:2 Definite-T 2:Operate & flt.rec. blocked   no
yes
no
_:422:10 Definite-T 2:Blk. by meas.-volt. failure   no
yes
yes
_:422:9 Definite-T 2:Measured value   phase-to-ground
phase-to-phase
phase-to-phase
_:422:8 Definite-T 2:Method of measurement   fundamental comp.
RMS value
fundamental comp.
_:422:101 Definite-T 2:Pickup mode   1 out of 3
3 out of 3
1 out of 3
_:422:102 Definite-T 2:Pickup delay   no
yes
no
_:422:3 Definite-T 2:Threshold   0.300 V to 175.000 V 65.000 V
_:422:4 Definite-T 2:Dropout ratio   1.01 to 1.20 1.05
_:422:6 Definite-T 2:Operate delay   0.00 s to 60.00 s 0.50 s

Setting parameters for Stage with Inverse-Time Characteristic Curve

Addr. Parameter C Setting Options Default Setting
Inverse-T #
_:1 Inverse-T #:Mode   off
on
test
off
_:2 Inverse-T #:Operate & flt.rec. blocked   no
yes
no
_:10 Inverse-T #:Blk. by meas.-volt. failure   no
yes
yes
_:9 Inverse-T #:Measured value   phase-to-ground
phase-to-phase
phase-to-phase
_:8 Inverse-T #:Method of measurement   fundamental comp.
RMS value
fundamental comp.
_:101 Inverse-T #:Pickup mode   1 out of 3
3 out of 3
1 out of 3
_:102 Inverse-T #:Pickup delay   no
yes
no
_:3 Inverse-T #:Threshold   0.300 V to 175.000 V 80.000 V
_:109 Inverse-T #:Pickup factor   0.80 to 1.00 0.90
_:103 Inverse-T #:Charact. constant k   0.00 to 300.00 1.00
_:104 Inverse-T #:Charact. constant α   0.010 to 5.000 1.000
_:105 Inverse-T #:Charact. constant c   0.000 to 5.000 0.000
_:106 Inverse-T #:Time dial   0.05 to 15.00 1.00
_:107 Inverse-T #:Additional time delay   0.00 s to 60.00 s 0.00 s
_:108 Inverse-T #:Reset time   0.00 s to 60.00 s 0.00 s

Logic Diagrams & highlights


Logic Diagram of the Stage Control

Logic Diagram of the Stage Control

Logic Diagram of the Definite-Time Undervoltage Protection with 3-Phase Voltage

Logic Diagram of the Definite-Time Undervoltage Protection with 3-Phase Voltage

Logic Diagram of the Stage Control

Logic Diagram of the Stage Control

Logic Diagram of the Inverse-Time Undervoltage Protection with 3-Phase Voltage

Logic Diagram of the Inverse-Time Undervoltage Protection with 3-Phase Voltage

Inverse-Time Characteristics for Undervoltage Protection

Inverse-Time Characteristics for Undervoltage Protection