Siemens / Undervoltage controlled reactive power protection (ANSI 27/Q) _ Setting & highlights _ SI5049

Table of Contents

Overview

The “Undervoltage controlled reactive power protection” function detects critical power-system situations, mainly in case of regenerative generation. It prevents a voltage collapse in power system by disconnecting the power-generation facility from the main power systems and ensures reconnection under stable power-system conditions.

For more detailed information on “Undervoltage controlled reactive power protection” function, refer to SIPROTEC 5 devices, V8.30 & higher manuals.

To see other supported functions, click here.


Structure/Embedding of the Function

Structure/Embedding of the Undervoltage controlled reactive power protection Function

Setting Parameters


Setting parameters for Protection Stage

Addr. Parameter C Setting Options Default Setting
Prot. stage 1
_:13921:1 Prot. stage 1:Mode   off
on
test
off
_:13921:2 Prot. stage 1:Operate & flt.rec. blocked   no
yes
no
_:13921:10 Prot. stage 1:Blk. by meas.-volt. failure   no
yes
yes
_:13921:27 Prot. stage 1:Blk. w. inrush curr. detect.   no
yes
no
_:13921:101 Prot. stage 1:Trip inter- face contains   no operate
operate (generator)
operate (grid)
operate (grid)
_:13921:102 Prot. stage 1:Q sign   not reversed
reversed
not reversed
_:13921:3 Prot. stage 1:Q> threshold value   1.00 % to 200.00 % 5.00 %
_:13921:103 Prot. stage 1:V< threshold value   3.000 V to 175.000 V 85.000 V
_:13921:105 Prot. stage 1:I> release threshold 1 A @ 100 Irated 0.030 A to 10.000 A 0.100 A
5 A @ 100 Irated 0.15 A to 50.00 A 0.50 A
1 A @ 50 Irated 0.030 A to 10.000 A 0.100 A
5 A @ 50 Irated 0.15 A to 50.00 A 0.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 0.100 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 0.500 A
_:13921:108 Prot. stage 1:Oper. delay generator CB   0.00 s to 60.00 s 0.50 s
_:13921:6 Prot. stage 1:Operate delay grid CB   0.00 s to 60.00 s 1.50 s

Setting parameters for Reclosure Stage

Addr. Parameter C Setting Options Default Setting
Reclos. stage
_:13951:1 Reclos. stage:Mode   off
on
test
off
_:13951:101 Reclos. stage:V> threshold value   3.000 V to 340.000 V 95.000 V
_:13951:104 Reclos. stage:f difference positive   0.01 Hz to 5.00 Hz 0.05 Hz
_:13951:105 Reclos. stage:f difference negative   -5.00 Hz to -0.01 Hz -2.50 Hz
_:13951:106 Reclos. stage:I> release threshold 1 A @ 100 Irated 0.030 A to 10.000 A 0.100 A
5 A @ 100 Irated 0.15 A to 50.00 A 0.50 A
1 A @ 50 Irated 0.030 A to 10.000 A 0.100 A
5 A @ 50 Irated 0.15 A to 50.00 A 0.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 0.100 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 0.500 A
_:13951:108 Reclos. stage:Time delay   0.00 s to 3600.00 s 0.00 s
_:13951:102 Reclos. stage:Configura- tion   Setting options depend on configuration  

Logic Diagrams & highlights


Logic Diagram of the Protection Stage of the Undervoltage-Controlled Reactive-Power Protection

Logic Diagram of the Protection Stage of the Undervoltage-Controlled Reactive-Power Protection

Logic Diagram of Reclosure Stage in Undervoltage-Controlled Reactive-Power Protection