Overview

The “Underfrequency load shedding” function detects underfrequencies in the electrical power systems, switches off the medium-voltage busbar or feeders that consume active power to stabilize the frequency, and maintains operations for the medium-voltage busbar or feeders that generate active power.

For more detailed information on “Underfrequency load shedding” function, refer to SIPROTEC 5 devices, V8.30 & higher manuals.

To see other supported functions, click here.


Structure/Embedding of the Function

Structure/Embedding of the Underfrequency load shedding Function

Setting Parameters


Setting parameters for Underfrequency load shedding Function

Addr. Parameter C Setting Options Default Setting
General
_:18121:101 General:Minimum voltage   0.300 p.u. to 0.900 p.u. 0.700 p.u.
_:18121:103 General:Power criterion   no
yes
yes
_:18121:104 General:Min. current (power crit.)   0.020 p.u. to 0.200 p.u. 0.050 p.u.
_:18121:115 General:Positive power direction   inv. to CT neu.pnt sett.
acc. to CT neu.pnt sett.
inv. to CT neu.pnt sett.
_:18121:106 General:Phi (power crite- rion)   -30° to 30° -5°
_:18121:107 General:df/dt-rising blk. criterion   no
yes
no
_:18121:108 General:df/dt-rising blk. threshold   0.1 Hz/s to 20.0 Hz/s 1.0 Hz/s
_:18121:109 General:df/dt-falling blk. criterion   no
yes
no
_:18121:110 General:df/dt-falling blk. threshold   0.1 Hz/s to 20.0 Hz/s 3.0 Hz/s
_:18121:111 General:df/dt measuring window   2 periods to 5 periods 5 periods
_:18121:112 General:df/dt dropout differential   0.02 Hz/s to 0.99 Hz/s 0.10 Hz/s
_:18121:113 General:f< stabilization counter   1 to 20 6
Stage 1
_:18151:1 Stage 1:Mode   off
on
test
off
_:18151:2 Stage 1:Operate & flt.rec. blocked   no
yes
no
_:18151:3 Stage 1:Threshold   40.00 Hz to 70.00 Hz 49.00 Hz
_:18151:5 Stage 1:Dropout differ- ential   20 mHz to 2000 mHz 20 mHz
_:18151:6 Stage 1:Operate delay   0.00 s to 60.00 s 0.10 s

Logic Diagrams & highlights


Logic Diagram of the General Functionality

Logic Diagram of the General Functionality

Power-Criterion Checking at Phi (power criterion) ≤ 0

Power-Criterion Checking at Phi (power criterion) ≤ 0

Power-Criterion Checking at Phi (power criterion) > 0

Power-Criterion Checking at Phi (power criterion) > 0

Application Scenarios

Application Scenarios

Logic Diagram of the Underfrequency Load Shedding Stage

Logic Diagram of the Underfrequency Load Shedding Stage