Overview

The “Underexcitation protection” function detects failures in the excitation (partial or complete failure) of synchronous machines. It responds to faulty voltage control (of the automatic voltage controller or done manually) during underexcited operation, and prevents asynchronous operation of synchronous machines and, therefore, a prohibited stress of the turbo-generator set.

For more detailed information on “Underexcitation protection” function, refer to SIPROTEC 5 devices, V8.30 & higher manuals.

To see other supported functions, click here.


Structure/Embedding of the Function

Structure/Embedding of the Function

Setting Parameters


Setting parameters for Stage with 3 Characteristic Curves

Addr. Parameter C Setting Options Default Setting
General
_:2311:103 General:Threshold V1 min   0.300 V to 200.000 V 15.000 V
_:2311:10 General:Blk. by meas.- volt. failure   no
yes
yes
Characteristic
_:16531:1 Characteristic:Mode   off
on
test
off
_:16531:2 Characteristic:Operate & flt.rec. blocked   no
yes
no
_:16531:3 Characteristic:1/xd char- acteristic 1   0.10 to 5.00 0.70
_:16531:4 Characteristic:Angle characteristic 1   50 ° to 120 ° 70 °

Setting parameters for Stage V Excitation <

Addr. Parameter C Setting Options Default Setting
V excitation<
_:1 V excitation<:Mode   off
on
test
off
_:2 V excitation<:Operate & flt.rec. blocked   no
yes
no
_:4 V excitation<:Vexc<   -110.000 V to 110.000 V 0.000 V
_:5 V excitation<:Operate delay   0.00 s to 60.00 s 0.50 s
_:101 V excitation<:Sensor   MT fast 1.MT in 1
MT fast 1.MT in 2
MT fast 1.MT in 3
MT fast 1.MT in 4
none
MT fast 1.MT in

Setting parameters for Stage with 1 Additional Characteristic Curves

Addr. Parameter C Setting Options Default Setting
Add. char. #
_:1 Add. char. #:Mode   off
on
test
off
_:2 Add. char. #:Operate & flt.rec. blocked   no
yes
no
_:3 Add. char. #:1/xd charac- teristic   0.10 to 5.00 1.40
_:4 Add. char. #:Angle char- acteristic   50 ° to 120 ° 90 °
_:5 Add. char. #:Operate delay   0.00 s to 60.00 s 0.30 s

Logic Diagrams & highlights


Stabilization Limits of a Synchronous Machine

Stabilization Limits of a Synchronous Machine

Capability-Diagram Display

Capability-Diagram Display

Transformation of the Capability Diagram into an Admittance Diagram

Transformation of the Capability Diagram into an Admittance Diagram

Logic Diagram of the General Function Block

Logic Diagram of the General Function Block

Logic Diagram of the Characteristic Curve Stage (Standard Stage)

Logic Diagram of the Characteristic Curve Stage (Standard Stage)

Characteristic Curve of a Standard Stage

Characteristic Curve of a Standard Stage

Operating Range of Synchronous and Asynchronous Machines

Operating Range of Synchronous and Asynchronous Machines

Connection Example

Connection Example

Generator Capability Diagram (Salient-Pole Machine)

Generator Capability Diagram (Salient-Pole Machine)

Characteristic Curve 1 (Red) and Characteristic Curve 2 (Blue) Shown in the Per-Unit Diagram

Characteristic Curve 1 (Red) and Characteristic Curve 2 (Blue) Shown in the Per-Unit Diagram

Capability Diagram of a Cylindrical Rotor Synchronous Machine in the Per-Unit Diagram

Capability Diagram of a Cylindrical Rotor Synchronous Machine in the Per-Unit Diagram

Admittance Diagram of the Turbogenerator

Admittance Diagram of the Turbogenerator

Logic Diagram of Stage V Excitation<

Logic Diagram of Stage V Excitation<

Logic Diagram of the Stage Additional Characteristic Curve

Logic Diagram of the Stage Additional Characteristic Curve