Overview
The “Underexcitation protection” function detects failures in the excitation (partial or complete failure) of synchronous machines. It responds to faulty voltage control (of the automatic voltage controller or done manually) during underexcited operation, and prevents asynchronous operation of synchronous machines and, therefore, a prohibited stress of the turbo-generator set.
For more detailed information on “Underexcitation protection” function, refer to SIPROTEC 5 devices, V8.30 & higher manuals.
To see other supported functions, click here.
Structure/Embedding of the Function

Setting Parameters
Setting parameters for Stage with 3 Characteristic Curves
Addr. | Parameter | C | Setting Options | Default Setting |
General | ||||
_:2311:103 | General:Threshold V1 min | 0.300 V to 200.000 V | 15.000 V | |
_:2311:10 | General:Blk. by meas.- volt. failure | no yes |
yes | |
Characteristic | ||||
_:16531:1 | Characteristic:Mode | off on test |
off | |
_:16531:2 | Characteristic:Operate & flt.rec. blocked | no yes |
no | |
_:16531:3 | Characteristic:1/xd char- acteristic 1 | 0.10 to 5.00 | 0.70 | |
_:16531:4 | Characteristic:Angle characteristic 1 | 50 ° to 120 ° | 70 ° | |
Setting parameters for Stage V Excitation <
Addr. | Parameter | C | Setting Options | Default Setting |
V excitation< | ||||
_:1 | V excitation<:Mode | off on test |
off | |
_:2 | V excitation<:Operate & flt.rec. blocked | no yes |
no | |
_:4 | V excitation<:Vexc< | -110.000 V to 110.000 V | 0.000 V | |
_:5 | V excitation<:Operate delay | 0.00 s to 60.00 s | 0.50 s | |
_:101 | V excitation<:Sensor | MT fast 1.MT in 1 MT fast 1.MT in 2 MT fast 1.MT in 3 MT fast 1.MT in 4 none |
MT fast 1.MT in | |
Setting parameters for Stage with 1 Additional Characteristic Curves
Addr. | Parameter | C | Setting Options | Default Setting |
Add. char. # | ||||
_:1 | Add. char. #:Mode | off on test |
off | |
_:2 | Add. char. #:Operate & flt.rec. blocked | no yes |
no | |
_:3 | Add. char. #:1/xd charac- teristic | 0.10 to 5.00 | 1.40 | |
_:4 | Add. char. #:Angle char- acteristic | 50 ° to 120 ° | 90 ° | |
_:5 | Add. char. #:Operate delay | 0.00 s to 60.00 s | 0.30 s | |
Logic Diagrams & highlights
Stabilization Limits of a Synchronous Machine

Capability-Diagram Display

Transformation of the Capability Diagram into an Admittance Diagram

Logic Diagram of the General Function Block

Logic Diagram of the Characteristic Curve Stage (Standard Stage)

Characteristic Curve of a Standard Stage

Operating Range of Synchronous and Asynchronous Machines

Connection Example

Generator Capability Diagram (Salient-Pole Machine)

Characteristic Curve 1 (Red) and Characteristic Curve 2 (Blue) Shown in the Per-Unit Diagram

Capability Diagram of a Cylindrical Rotor Synchronous Machine in the Per-Unit Diagram

Admittance Diagram of the Turbogenerator

Logic Diagram of Stage V Excitation<

Logic Diagram of the Stage Additional Characteristic Curve