Siemens / Undercurrent protection (ANSI 37) _ Setting & highlights _ SI5038

Table of Contents

Overview

The “Undercurrent protection” function detects the going current in a feeder after the opening of the infeed circuit breaker and the loss of loads. It detects and protects pumps from running idle.

For more detailed information on “Undercurrent protection” function, refer to SIPROTEC 5 devices, V8.30 & higher manuals.

To see other supported functions, click here.


Structure/Embedding of the Function

Structure/Embedding of the Undercurrent protection Function

Setting Parameters


Setting parameters for Undercurrent protection function

Addr. Parameter C Setting Options Default Setting
Stage 1
_:13051:1 Stage 1:Mode   off
on
test
off
_:13051:2 Stage 1:Operate & flt.rec. blocked   no
yes
no
_:13051:103 Stage 1:Activation   always active
with CB closed
with CB closed
_:13051:8 Stage 1:Method of measurement   fundamental comp.
RMS value
fundamental comp.
_:13051:102 Stage 1:Pickup mode   1 out of 3
3 out of 3
3 out of 3
_:13051:3 Stage 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 0.050 A
5 A @ 100 Irated 0.15 A to 175.00 A 0.25 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 0.050 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 0.250 A
_:13051:104 Stage 1:Pickup delay   0.00 s to 60.00 s 0.00 s
_:13051:6 Stage 1:Operate delay   0.00 s to 60.00 s 0.50 s

Logic Diagrams & highlights


Logic Diagram of the Undercurrent Protection

Logic Diagram of the Undercurrent Protection