ABB / Under impedance protection for generators and transformers (ZGVPDIS) _ Setting & highlights _ AB2125

Table of Contents

Overview

The “Under impedance protection” function is a three zone full scheme impedance protection using offset mho characteristics for detecting faults in the generator, generator-transformer and transmission system. The three zones have fully independent measuring loops and settings.

For more detailed information on “Under impedance protection for generators and transformers”, refer to ABB, Relion 670 Series manuals.

To see other supported functions, click here.


Function Identification

Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Under impedance function for generators and transformers ZGVPDIS Z < 21G

Signals & Setting Parameters


ZGVPDIS function block

ZGVPDIS function block

ZGVPDIS Input signals

ZGVPDIS Input signals
Name Type Default Description
I3P GROUP SIGNAL Connection for current sample signals
U3P GROUP SIGNAL Connection for voltage sample signals
BLOCK BOOLEAN 0 Block of the function
BLKZ BOOLEAN 0 Block due to fuse failure
BLKUV BOOLEAN 0 Block of the under voltage seal in

ZGVPDIS Output signals

ZGVPDIS Output signals
Name Type Description
TRIP BOOLEAN General Trip
TRZ1 BOOLEAN Trip signal Zone 1
TRZ2 BOOLEAN Trip signal Zone 2
TRZ3 BOOLEAN Trip signal Zone 3
TRUV BOOLEAN Trip from Under voltage seal in
START BOOLEAN General start
STZ1 BOOLEAN Start signal Zone 1
STZ2 BOOLEAN Start signal Zone 2
STZ3 BOOLEAN Start signal Zone 3
STUV BOOLEAN Start of under voltage seal in

ZGVPDIS Group settings (basic)

ZGVPDIS Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off
On
Off Operation Off / On
ImpedanceAng 5 – 90 Deg 1 80 Impedance angle in degrees, common for all zones
IMinOp 5 – 80 %IB 1 10 Minimum operate phase current
OpModeZ1 Off
PP Loops
PP Loops Operation mode of Zone 1: Off/Ph-Ph loops
Z1Fwd 3.0 – 100.0 % Zb 0.1 8.0 Zone 1 forward reach in % of rated impedance, 100%=full load
Z1Rev 3.0 – 100.0 % Zb 0.1 8.0 Zone 1 reverse reach in % of rated impedance, 100%=full load
tZ1 0.000 – 60.000 s 0.001 0.000 Time delay to operate for Zone 1
OpModeZ2 Off
PP Loops
EnhancedReach
EnhancedReach Operation mode of Zone 2: Off/Ph- Ph/EnhancedReach
Z2Fwd 3.0 – 200.0 % Zb 0.1 15.0 Zone 2 forward reach in % of rated impedance, 100%=full load
Z2Rev 3.0 – 200.0 % Zb 0.1 8.0 Zone 2 reverse reach in % of rated impedance, 100%=full load
tZ2 0.000 – 60.000 s 0.001 0.500 Time delay to operate for Zone 2
OpModeZ3 Off
PP Loops
EnhancedReach
EnhancedReach Operation mode of Zone 3: Off/Ph- Ph/EnhancedReach
Z3Fwd 3.0 – 200.0 % Zb 0.1 75.0 Zone 3 forward reach in % of rated impedance, 100%=full load
Z3Rev 3.0 – 200.0 % Zb 0.1 8.0 Zone 3 reverse reach in % of rated impedance, 100%=full load
tZ3 0.000 – 60.000 s 0.001 1.500 Time delay to operate for Zone 3
OpModeU< Off
Z2Start
Z3Start
Off Enable under voltage seal in (Off/ Z2Start/Z3Start)
U< 5 – 90 %UB 1 70 Start value of under voltage seal in
tU< 0.000 – 60.000 s 0.001 5.000 Time delay to operate for under voltage seal in

ZGVPDIS Group settings (advanced)

ZGVPDIS Group settings (advanced)
Name Values (Range) Unit Step Default Description
RLd 5 – 120 % Zb 1 50 Resistive reach in % for load encroachment charateristics
ArgLd 5 – 85 Deg 1 38 Load encroachment inclination of load angular sector
LoadEnchModZ2 Off
On
Off Enable load encroachement for Zone 2 Off/On
LoadEnchModZ3 Off
On
On Enable load encroachement for Zone 3 Off/On

ZGVPDIS Non group settings (basic)

ZGVPDIS Non group settings (basic)
Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 – 12 1 1 Selection of one of the Global Base Value groups

ZGVPDIS Monitored data

ZGVPDIS Monitored data
Name Type Values (Range) Unit Description
UL1 REAL kV Voltage in phase L1
UL2 REAL kV Voltage in phase L2
UL3 REAL kV Voltage in phase L3
IL1 REAL A Current in phase L1
IL2 REAL A Current in phase L2
IL3 REAL A Current in phase L3

Logics & highlights


Base value of impedance calculation

Base value of impedance calculation

Offset mho characteristics of three zones

Offset mho characteristics of three zones

Block diagram of ZGVPDIS

Block diagram of ZGVPDIS

Block diagram of zone 1

Block diagram of zone 1

Simplified offset mho characteristics for L1-L2 fault in zone 1

Simplified offset mho characteristics for L1-L2 fault in zone 1

Block diagram of zone 2

Block diagram of zone 2

Logic diagram for the selection of the maximum current loop

Logic diagram for the selection of the maximum current loop

Simplified offset mho characteristics for L1-to-E fault in zone 2

Simplified offset mho characteristics for L1-to-E fault in zone 2

Simplified offset mho characteristics for L1-to-L2 fault in zone 2

Simplified offset mho characteristics for L1-to-L2 fault in zone 2

Load encroachment characteristics

Load encroachment characteristics

Under voltage seal-in for zone 2 and zone 3

Under voltage seal-in for zone 2 and zone 3