Siemens / Tripping with missing or weak infeed according to French specification _ Setting & highlights _ SI5022

Table of Contents

Overview

The “Tripping with missing or weak infeed according to French specification” also switches off the line end with weak infeed with a short circuit on the line, selects the faulty phases via a relative undervoltage threshold, and trips instantaneously or with a delay.

For more detailed information “Tripping with missing or weak infeed according to French specification” function, refer to SIPROTEC 5 devices, V8.30 & higher manuals.

To see other supported functions, click here.


Structure/Embedding of the Function

Structure/Embedding of the Tripping with missing or weak infeed according to French specification Function

Setting Parameters


Setting parameters of the Function

Addr. Parameter C Setting Options Default Setting
General
_:2311:1 General:Mode   off
on
test
off
_:2311:2 General:Vph-g< factor   0.10 to 1.00 0.70
_:2311:3 General:Threshold Vph- gnd<   0.300 V to 100.000 V 30.000 V
_:2311:4 General:Time constant Tau   1 s to 60 s 5 s
_:2311:5 General:3I0> threshold 1 A @ 100 Irated 0.050 A to 1.000 A 0.500 A
5 A @ 100 Irated 0.250 A to 5.000 A 2.500 A
1 A @ 50 Irated 0.050 A to 0.500 A 0.500 A
5 A @ 50 Irated 0.250 A to 2.500 A 2.500 A
_:2311:6 General:T 3I0> extension   0.00 s to 60.00 s 0.60 s
Undelayed
_:15451:1 Undelayed:Operating mode   off
on
on
_:15451:2 Undelayed:Receive extension   0.00 s to 60.00 s 0.65 s
_:15451:3 Undelayed:T 3I0> alarm   0.00 s to 60.00 s 10.00 s
_:15451:11 Undelayed:1-pole operate allowed   no
yes
yes
Delayed
_:15481:1 Delayed:Operating mode   off
on
on receive err.
on
_:15481:2 Delayed:Operate delay 1-ph. (TM)   0.00 s to 60.00 s 0.40 s
_:15481:3 Delayed:Op. delay multi- ph. (TT)   0.00 s to 60.00 s 1.00 s
_:15481:11 Delayed:1-pole operate allowed   no
yes
yes
_:15481:5 Delayed:1-pole operate with 3I0>   no
yes
yes
_:15481:6 Delayed:3-pole operate allowed   no
yes
yes

Logic Diagrams & highlights


Undervoltage and 3I0 Detection Logic

Undervoltage and 3I0 Detection Logic

Logic of the Instantaneous Stage

Logic of the Instantaneous Stage

Logic of the Instantaneous Stage

Logic of the Instantaneous Stage