Overview
The “Trip output” element is primarily used to collect trip requests from protection elements and other inputs to generate output operands to initiate trip operations. Three pole trips only initiate reclosure if programmed to do so, whereas single pole trips always automatically initiate reclosure.
For more detailed information on “Trip output” element, refer to GE, Universal Relay (UR) family of products, Version 8.0x manuals.
To see other supported elements, click here.
Setting Parameters
Modbus memory map for Setting parameters
Products | Hex address | Register name | Range | Units | Step | Format | Default |
C60, C95, D60, L60, L90 | D934 | Trip Mode | 0 to 2 | — | 1 | F195 | 0 (Disabled) |
" | D935 | Trip 3-Pole Input1 | 0 to 4294967295 | — | 1 | F300 | 0 |
" | D937 | Trip 3-Pole Input2 | 0 to 4294967295 | — | 1 | F300 | 0 |
" | D939 | Trip 3-Pole Input3 | 0 to 4294967295 | — | 1 | F300 | 0 |
" | D93B | Trip 3-Pole Input4 | 0 to 4294967295 | — | 1 | F300 | 0 |
" | D93D | Trip 3-Pole Input5 | 0 to 4294967295 | — | 1 | F300 | 0 |
" | D93F | Trip 3-Pole Input6 | 0 to 4294967295 | — | 1 | F300 | 0 |
" | D941 | Trip 1-Pole Input1 | 0 to 4294967295 | — | 1 | F300 | 0 |
" | D943 | Trip 1-Pole Input2 | 0 to 4294967295 | — | 1 | F300 | 0 |
" | D945 | Trip 1-Pole Input3 | 0 to 4294967295 | — | 1 | F300 | 0 |
" | D947 | Trip 1-Pole Input4 | 0 to 4294967295 | — | 1 | F300 | 0 |
" | D949 | Trip 1-Pole Input5 | 0 to 4294967295 | — | 1 | F300 | 0 |
" | D94B | Trip 1-Pole Input6 | 0 to 4294967295 | — | 1 | F300 | 0 |
" | D94D | Trip Reclose Input1 | 0 to 4294967295 | — | 1 | F300 | 0 |
" | D94F | Trip Reclose Input2 | 0 to 4294967295 | — | 1 | F300 | 0 |
" | D951 | Trip Reclose Input3 | 0 to 4294967295 | — | 1 | F300 | 0 |
" | D953 | Trip Reclose Input4 | 0 to 4294967295 | — | 1 | F300 | 0 |
" | D955 | Trip Reclose Input5 | 0 to 4294967295 | — | 1 | F300 | 0 |
" | D957 | Trip Reclose Input6 | 0 to 4294967295 | — | 1 | F300 | 0 |
" | D959 | Trip Seal-In Delay | 0 to 65.535 | s | 0.001 | F001 | 0 |
" | D95A | Trip Reset | 0 to 2 | — | 1 | F609 | 0 (Pole Curr OR Custom) |
" | D95B | Phase Selector Reset Delay | 0.5 to 3 | s | 0.001 | F001 | 500 |
" | D95C | Phase Selector Reset | 0 to 4294967295 | — | 1 | F300 | 0 |
" | D95E | Breaker Phase A Open | 0 to 4294967295 | — | 1 | F300 | 0 |
" | D960 | Breaker Phase B Open | 0 to 4294967295 | — | 1 | F300 | 0 |
" | D962 | Breaker Phase C Open | 0 to 4294967295 | — | 1 | F300 | 0 |
" | D964 | Trip Force 3-Pole | 0 to 4294967295 | — | 1 | F300 | 0 |
" | D966 | Trip Pilot Priority | 0 to 65.535 | s | 0.001 | F001 | 0 |
" | D967 | Reverse Fault Operand | 0 to 4294967295 | — | 1 | F300 | 0 |
" | D969 | Trip Delay On Evolving Faults | 0 to 65.535 | s | 0.001 | F001 | 0 |
" | D96A | Trip Events | 0 to 1 | — | 1 | F102 | 0 (Disabled) |
" | D96B | Start Timer Zone 2 Phase Input 1 | 0 to 4294967295 | — | 1 | F300 | 0 |
" | D96D | Start Timer Zone 2 Phase Input 2 | 0 to 4294967295 | — | 1 | F300 | 0 |
" | D96F | Start Timer Zone 2 Ground Input 1 | 0 to 4294967295 | — | 1 | F300 | 0 |
" | D971 | Start Timer Zone 2 Ground Input 2 | 0 to 4294967295 | — | 1 | F300 | 0 |
" | D973 | Start Timer Zone 3 Phase Input 1 | 0 to 4294967295 | — | 1 | F300 | 0 |
" | D975 | Start Timer Zone 3 Phase Input 2 | 0 to 4294967295 | — | 1 | F300 | 0 |
" | D977 | Start Timer Zone 3 Ground Input 1 | 0 to 4294967295 | — | 1 | F300 | 0 |
" | D979 | Start Timer Zone 3 Ground Input 2 | 0 to 4294967295 | — | 1 | F300 | 0 |
" | D97B | Start Timer Zone 4 Phase Input 1 | 0 to 4294967295 | — | 1 | F300 | 0 |
" | D97D | Start Timer Zone 4 Phase Input 2 | 0 to 4294967295 | — | 1 | F300 | 0 |
" | D97F | Start Timer Zone 4 Ground Input 1 | 0 to 4294967295 | — | 1 | F300 | 0 |
" | D981 | Start Timer Zone 4 Ground Input 2 | 0 to 4294967295 | — | 1 | F300 | 0 |
" | D983 | Start Timer Zone 5 Phase Input 1 | 0 to 4294967295 | — | 1 | F300 | 0 |
" | D985 | Start Timer Zone 5 Phase Input 2 | 0 to 4294967295 | — | 1 | F300 | 0 |
" | D987 | Start Timer Zone 5 Ground Input 1 | 0 to 4294967295 | — | 1 | F300 | 0 |
" | D989 | Start Timer Zone 5 Ground Input 2 | 0 to 4294967295 | — | 1 | F300 | 0 |
" | D98B | Start Timer Zone 6 Phase Input 1 | 0 to 4294967295 | — | 1 | F300 | 0 |
" | D98D | Start Timer Zone 6 Phase Input 2 | 0 to 4294967295 | — | 1 | F300 | 0 |
" | D98F | Start Timer Zone 6 Ground Input 1 | 0 to 4294967295 | — | 1 | F300 | 0 |
" | D991 | Start Timer Zone 6 Ground Input 2 | 0 to 4294967295 | — | 1 | F300 | 0 |
" | D993 | Reserved (4 items) | 0 to 1 | — | 1 | F001 | 0 |
F102 | 0 = Disabled, 1 = Enabled | ||||||
F195 | 0 = Disabled, 1 = 3 Pole Only, 2 = 3 Pole & 1 Pole | ||||||
F609 | 0 = Pole Curr OR Custom, 1 = CBaux OR Custom, 2 = Custom | ||||||