Table of Contents

GE / Trip bus _ Element settings & highlights _ GU8242

Table of Contents

Overview

The “Trip bus” element allows aggregating outputs of protection and control elements without using FlexLogic and assigning them a simple and effective manner. Each trip bus can be assigned for either trip or alarm actions. Simple trip conditioning such as latch, delay, and seal-in delay are available.

For more detailed information on “Trip bus” element, refer to GE, Universal Relay (UR) family of products, Version 8.0x manuals.

To see other supported elements, click here.


Setting Parameters


Modbus memory map for Setting parameters

Products Hex address Register name Range Units Step Format Default
All 5B3D Trip Bus 1 Function 0 to 1 1 F102 0 (Disabled)
" 5B3E Trip Bus 1 Block 0 to 4294967295 1 F300 0
" 5B40 Trip Bus 1 Pickup Delay 0 to 600 s 0.01 F001 0
" 5B41 Trip Bus 1 Reset Delay 0 to 600 s 0.01 F001 0
" 5B42 Trip Bus 1 Input (16 items) 0 to 4294967295 1 F300 0
" 5B62 Trip Bus 1 Latching 0 to 1 1 F102 0 (Disabled)
" 5B63 Trip Bus 1 Reset 0 to 4294967295 1 F300 0
" 5B65 Trip Bus 1 Target 0 to 2 1 F109 0 (Self-reset)
" 5B66 Trip Bus 1 Events 0 to 1 1 F102 0 (Disabled)
" 5B67 Reserved (8 items) 0 to 1 1 F001 0
" 5B6F …Repeated for Trip Bus 2          
" 5BA1 …Repeated for Trip Bus 3          
" 5BD3 …Repeated for Trip Bus 4          
" 5C05 …Repeated for Trip Bus 5          
" 5C37 …Repeated for Trip Bus 6          
F102 0 = Disabled, 1 = Enabled
F109 0 = Self-reset, 1 = Latched, 2 = Disabled

Logics & highlights


Trip bus fields in the protection summary

Trip bus fields in the protection summary

Trip bus logic