Table of Contents

Siemens / “Transformer diff” function group _ Setting & highlights _ SI5205

Table of Contents

Overview

The individual function group types are stored in the “Transformer diff” function group folder. The “Transf. diff.” function group contains the differential protection function and protection function relevant measured values. In the “Transformer side” function group, all of the functions that are necessary for protecting and monitoring a transformer side can be used. In the “Transf. neutral point” function group all the necessary functions for protection and for supervision of a transformer which are related to a neutral-point current, are used

For more detailed information on “Transformer differential” function group, refer to SIPROTEC 5 devices, V8.30 & higher manuals.

To see other supported function groups, click here.


Transformer Diff Function-Group Types

Transformer Diff Function-Group Types

Function-Group Type Transformer Differential Protection


Structure of the Transformer Differential Function Group

Structure of the Transformer Differential Function Group

Generation of Pickup Indication of the Transf. Diff. Function Group

Generation of Pickup Indication of the Transf. Diff. Function Group

Generation of Operate Indication of the Transf. Diff. Function Group

Generation of Operate Indication of the Transf. Diff. Function Group

Function-Group Type Transformer Side


Structure of the Transformer Side Function Group

Structure of the Transformer Side Function Group

Write-Protected Settings

Addr. Parameters C Range of Values Default Setting
Rated values
_:91:101 General:Rated current   1 A to 100 000 A 1 000 A
Side data
_:91:130 General:Side number   not assigned
Side 1
Side 2
Side 3
Side 4
Side 5
not assigned
_:91:210 General:MI3ph1 uses- MeasP with ID   0 to 100 0
_:91:211 General:MI3ph2 uses- MeasP with ID   0 to 100 0
_:91:212 General:MI3ph3 uses- MeasP with ID   0 to 100 0
_:91:213 General:MI3ph4 uses- MeasP with ID   0 to 100 0
_:91:214 General:M I-1ph uses MeasP with ID   0 to 100 0
_:91:215 General:CT mismatch M I-3ph 1   0.000 to 100.000 0.000
_:91:216 General:CT mismatch M I-3ph 1 IN   0.000 to 100.000 0.000
Rated values
_:91:217 General:CT mismatch M I-3ph 2   0.000 to 100.000 0.000
_:91:218 General:CT mismatch M I-3ph 2 IN   0.000 to 100.000 0.000
_:91:219 General:CT mismatch M I-3ph 3   0.000 to 100.000 0.000
_:91:220 General:CT mismatch M I-3ph 3 IN   0.000 to 100.000 0.000
_:91:221 General:CT mismatch M I-3ph 4   0.000 to 100.000 0.000
_:91:222 General:CT mismatch M I-3ph 4 IN   0.000 to 100.000 0.000
_:91:223 General:CT mismatch M I-1ph   0.000 to 100.000 0.000

Settings

Addr. Parameter C Setting Options Default Setting
Rated values
_:91:103 General:Rated apparent power   0.20 MVA to 5000.00 MVA 692.82 MVA
_:91:102 General:Rated voltage   0.300 V to 340.000 V 40 000.000 V
Side data
_:91:149 General:Neutral point   grounded
isolated
grounded
_:91:104 General:Winding config- uration   Y (Wye)
D (Delta)
Z (Zig-Zag)
Y (Wye)
_:91:163 General:Vector group numeral   0
1
2
3
4
5
6
7
8
9
10
11
user-defined
0
Measurements
_:91:158 General:P, Q sign   not reversed
reversed
not reversed

Possible Operational Measured Values of the Transformer Side Function Group

Possible Operational Measured Values of the Transformer Side Function Group

Generation of Pickup Indication of the Transformer Side Function Group

Generation of Pickup Indication of the Transformer Side Function Group

Generation of an Operate Indication of the Transformer Side Function Group

Generation of an Operate Indication of the Transformer Side Function Group

Function-Group Type Transformer Neutral Point


Structure of the Transf. Neutral Point Function Group

Structure of the Transf. Neutral Point Function Group

Write-Protected Settings

Addr. Parameter C Range of Values Default Setting
Rated values
_:9421:103 General:Rated apparent power   0.20 MVA to 5 000.00 MVA 692.82 MVA
_:9421:104 General:Rated current   1 A to 100 000 A 1 000 A
_:9421:105 General:Rated voltage   0.20 kV to 1 200.00 kV 400 kV
Power-system data
_:9421:214 General:M I-1ph uses MeasP with ID   0 to 100 0
_:9421:223 General:CT mismatch M I-1ph   0.00 to 100.00 0.000

Operational Measured Values of the Transformer Neutral Point Function Group

Operational Measured Values of the Transformer Neutral Point Function Group

Generation of Pickup Indication of the Transf. Neutral Point Function Group

Generation of Pickup Indication of the Transf. Neutral Point Function Group

Generation of Operate Indication of the Transf. Neutral Point Function Group

Generation of Operate Indication of the Transf. Neutral Point Function Group