Overview
The individual function group types are stored in the “Transformer diff” function group folder. The “Transf. diff.” function group contains the differential protection function and protection function relevant measured values. In the “Transformer side” function group, all of the functions that are necessary for protecting and monitoring a transformer side can be used. In the “Transf. neutral point” function group all the necessary functions for protection and for supervision of a transformer which are related to a neutral-point current, are used
For more detailed information on “Transformer differential” function group, refer to SIPROTEC 5 devices, V8.30 & higher manuals.
To see other supported function groups, click here.
Transformer Diff Function-Group Types
Function-Group Type Transformer Differential Protection
Structure of the Transformer Differential Function Group
Generation of Pickup Indication of the Transf. Diff. Function Group
Generation of Operate Indication of the Transf. Diff. Function Group
Function-Group Type Transformer Side
Structure of the Transformer Side Function Group
Write-Protected Settings
Addr. | Parameters | C | Range of Values | Default Setting |
Rated values | ||||
_:91:101 | General:Rated current | 1 A to 100 000 A | 1 000 A | |
Side data | ||||
_:91:130 | General:Side number | not assigned Side 1 Side 2 Side 3 Side 4 Side 5 |
not assigned | |
_:91:210 | General:MI3ph1 uses- MeasP with ID | 0 to 100 | 0 | |
_:91:211 | General:MI3ph2 uses- MeasP with ID | 0 to 100 | 0 | |
_:91:212 | General:MI3ph3 uses- MeasP with ID | 0 to 100 | 0 | |
_:91:213 | General:MI3ph4 uses- MeasP with ID | 0 to 100 | 0 | |
_:91:214 | General:M I-1ph uses MeasP with ID | 0 to 100 | 0 | |
_:91:215 | General:CT mismatch M I-3ph 1 | 0.000 to 100.000 | 0.000 | |
_:91:216 | General:CT mismatch M I-3ph 1 IN | 0.000 to 100.000 | 0.000 | |
Rated values | ||||
_:91:217 | General:CT mismatch M I-3ph 2 | 0.000 to 100.000 | 0.000 | |
_:91:218 | General:CT mismatch M I-3ph 2 IN | 0.000 to 100.000 | 0.000 | |
_:91:219 | General:CT mismatch M I-3ph 3 | 0.000 to 100.000 | 0.000 | |
_:91:220 | General:CT mismatch M I-3ph 3 IN | 0.000 to 100.000 | 0.000 | |
_:91:221 | General:CT mismatch M I-3ph 4 | 0.000 to 100.000 | 0.000 | |
_:91:222 | General:CT mismatch M I-3ph 4 IN | 0.000 to 100.000 | 0.000 | |
_:91:223 | General:CT mismatch M I-1ph | 0.000 to 100.000 | 0.000 | |
Settings
Addr. | Parameter | C | Setting Options | Default Setting |
Rated values | ||||
_:91:103 | General:Rated apparent power | 0.20 MVA to 5000.00 MVA | 692.82 MVA | |
_:91:102 | General:Rated voltage | 0.300 V to 340.000 V | 40 000.000 V | |
Side data | ||||
_:91:149 | General:Neutral point | grounded isolated |
grounded | |
_:91:104 | General:Winding config- uration | Y (Wye) D (Delta) Z (Zig-Zag) |
Y (Wye) | |
_:91:163 | General:Vector group numeral | 0 1 2 3 4 5 6 7 8 9 10 11 user-defined |
0 | |
Measurements | ||||
_:91:158 | General:P, Q sign | not reversed reversed |
not reversed | |
Possible Operational Measured Values of the Transformer Side Function Group
Generation of Pickup Indication of the Transformer Side Function Group
Generation of an Operate Indication of the Transformer Side Function Group
Function-Group Type Transformer Neutral Point
Structure of the Transf. Neutral Point Function Group
Write-Protected Settings
Addr. | Parameter | C | Range of Values | Default Setting |
Rated values | ||||
_:9421:103 | General:Rated apparent power | 0.20 MVA to 5 000.00 MVA | 692.82 MVA | |
_:9421:104 | General:Rated current | 1 A to 100 000 A | 1 000 A | |
_:9421:105 | General:Rated voltage | 0.20 kV to 1 200.00 kV | 400 kV | |
Power-system data | ||||
_:9421:214 | General:M I-1ph uses MeasP with ID | 0 to 100 | 0 | |
_:9421:223 | General:CT mismatch M I-1ph | 0.00 to 100.00 | 0.000 | |