Overview
The “Three phase undercurrent” function is designed for detecting loss of load conditions. It is a single definite time stage trip function with Phase wise start and trip signals.
For more detailed information on “Three phase undercurrent” function, refer to ABB, Relion 670 Series manuals.
To see other supported functions, click here.
Function Identification
Function description | IEC 61850 identification |
IEC 60617 identification |
ANSI/IEEE C37.2 device number |
Three phase undercurrent | LCP3PTUC | – | 37 |
Signals & Setting Parameters
LCP3PTUC Function block
LCP3PTUC Input signals
LCP3PTUC Input signals | |||
Name | Type | Default | Description |
I3P | GROUP SIGNAL | – | Three phase group signal for current inputs |
BLOCK | BOOLEAN | 0 | Block all binary outputs by resetting timers |
BLKTR | BOOLEAN | 0 | Block trip of the function |
LCP3PTUC Output signals
LCP3PTUC Output signals | |||
Name | Type | Description | |
TRIP | BOOLEAN | Common trip signal | |
TRL1 | BOOLEAN | Trip signal from phase L1 | |
TRL2 | BOOLEAN | Trip signal from phase L2 | |
TRL3 | BOOLEAN | Trip signal from phase L3 | |
START | BOOLEAN | Common start signal | |
STL1 | BOOLEAN | Start signal from phase L1 | |
STL2 | BOOLEAN | Start signal from phase L2 | |
STL3 | BOOLEAN | Start signal from phase L3 | |
LCP3PTUC Group settings (basic)
LCP3PTUC Group settings (basic) | |||||
Name | Values (Range) | Unit | Step | Default | Description |
Operation | Off On |
– | – | Off | Operation On / Off |
IUC< | 1.00 – 100.00 | %IB | 0.01 | 50.00 | Start value for 3 phase under current in % of IBase |
tUC | 0.000 – 60.000 | s | 0.001 | 0.000 | Time delay to operate |
LCP3PTUC Non group settings (basic)
LCP3PTUC Non group settings (basic) | |||||
Name | Values (Range) | Unit | Step | Default | Description |
GlobalBaseSel | 1 – 12 | – | 1 | 1 | Selection of one of the Global Base Value groups |
LCP3PTUC Monitored data
LCP3PTUC Monitored data | ||||
Name | Type | Values (Range) | Unit | Description |
IL1 | REAL | – | A | Current RMS value for phase L1 |
IL2 | REAL | – | A | Current RMS value for phase L2 |
IL3 | REAL | – | A | Current RMS value for phase L3 |