Overview
The “Three phase overcurrent” function is designed for overcurrent conditions. It is a single definite time stage trip function that has phase wise start and trip signals.
For more detailed information on “Three phase overcurrent” function, refer to ABB, Relion 670 Series manuals.
To see other supported functions, click here.
Function Identification
Function description | IEC 61850 identification |
IEC 60617 identification |
ANSI/IEEE C37.2 device number |
Three phase overcurrent | LCP3PTOC | – | 51 |
Signals & Setting Parameters
LCP3PTOC Function block
LCP3PTOC Input signals
LCP3PTOC Input signals | |||
Name | Type | Default | Description |
I3P | GROUP SIGNAL | – | Three phase group signal for current inputs |
BLOCK | BOOLEAN | 0 | Block all binary outputs by resetting timers |
BLKTR | BOOLEAN | 0 | Block trip of the function |
LCP3PTOC Output signals
LCP3PTOC Output signals | |||
Name | Type | Description | |
TRIP | BOOLEAN | Common trip signal | |
TRL1 | BOOLEAN | Trip signal from phase L1 | |
TRL2 | BOOLEAN | Trip signal from phase L2 | |
TRL3 | BOOLEAN | Trip signal from phase L3 | |
START | BOOLEAN | Common start signal | |
STL1 | BOOLEAN | Start signal from phase L1 | |
STL2 | BOOLEAN | Start signal from phase L2 | |
STL3 | BOOLEAN | Start signal from phase L3 | |
LCP3PTOC Group settings (basic)
LCP3PTOC Group settings (basic) | |||||
Name | Values (Range) | Unit | Step | Default | Description |
Operation | Off On |
– | – | Off | Operation On / Off |
IOC> | 5 – 2500 | %IB | 1 | 1000 | Start value for 3 phase over current
in % of IBase |
tOC | 0.000 – 60.000 | s | 0.001 | 0.020 | Time delay to operate |
LCP3PTOC Non group settings (basic)
LCP3PTOC Non group settings (basic) | |||||
Name | Values (Range) | Unit | Step | Default | Description |
GlobalBaseSel | 1 – 12 | – | 1 | 1 | Selection of one of the Global Base Value groups |
LCP3PTOC Monitored data
LCP3PTOC Monitored data | ||||
Name | Type | Values (Range) | Unit | Description |
IL1 | REAL | – | A | Current RMS value for phase L1 |
IL2 | REAL | – | A | Current RMS value for phase L2 |
IL3 | REAL | – | A | Current RMS value for phase L3 |