Overview

The “Third harmonic neutral undervoltage” element detects a loss of third harmonic voltage at the generator neutral. The percentage of stator winding covered by this function depends on the pickup setting and the amount of third harmonic generated by the machine at the time of the fault. A settable window of forward power can supervise this element for enhanced security.

For more detailed information on “Third harmonic neutral undervoltage” element, refer to GE, Universal Relay (UR) family of products, Version 8.0x manuals.

To see other supported elements, click here.


Setting Parameters


Modbus memory map for Setting parameters

Stator Ground Source element

Products Hex address Register name Range Units Step Format Default
G30, G60 41A2 Stator Ground Source 0 to 5 1 F167 0 (SRC 1)
F167 0 = SRC 1, 1 = SRC 2, 2 = SRC 3, 3 = SRC 4, 4 = SRC 5, 5 = SRC 6

Third harmonic neutral undervoltage element

Products Hex address Register name Range Units Step Format Default
G30, G60 4180 Third Harmonic Neutral Undervoltage Function 0 to 1 1 F102 0 (Disabled)
" 4181 Third Harmonic Neutral Undervoltage Pickup 0.001 to 3 pu 0.000
1
F003 3000
" 4183 Third Harmonic Neutral Undervoltage Delay 0 to 600 s 0.01 F001 0
" 4184 Third Harmonic Neutral Undervoltage Max Power 0 to 1.25 pu 0.001 F003 200
" 4186 Third Harmonic Neutral Undervoltage Min Power 0 to 1.25 pu 0.001 F003 200
" 4188 Third Harmonic Neutral Undervoltage Volt Supervision 0 to 1.25 pu 0.001 F001 500
" 4189 Third Harmonic Neutral Undervoltage Block 0 to 4294967295 1 F300 0
" 418B Third Harmonic Neutral Undervoltage Target 0 to 2 1 F109 0 (Self-reset)
" 418C Third Harmonic Neutral Undervoltage Events 0 to 1 1 F102 0 (Disabled)
" 418D Reserved (4 items) 0 to 65535 1 F001 0
F102 0 = Disabled, 1 = Enabled
F109 0 = Self-reset, 1 = Latched, 2 = Disabled

Logics & highlights


Third harmonic neutral undervoltage logic

Third harmonic neutral undervoltage logic