Overview

The “Thermal overload protection, 3-phase advanced” function is used to protect the equipment (motors, generators, transformers, capacitors, overhead lines, and cables) against thermal overloads, and monitor the thermal state of motors, generators, transformers, capacitors, overhead lines, and cables.

For more detailed information on “Thermal overload protection, 3-phase advanced” function, refer to SIPROTEC 5 devices, V8.30 & higher manuals.

To see other supported functions, click here.


Structure/Embedding of the Function

Structure/Embedding of the Thermal overload protection, 3-phase advanced Function

Setting Parameters


Setting parameters of Filter for RMS Value Gain

Addr. Parameter C Setting Options Default Setting
Filter
_:1 Filter:Enable filter   no
yes
no
_:2 Filter:h(0)   -100.000 to 100.000 0.000
_:3 Filter:h(1)   -100.000 to 100.000 0.000
_:4 Filter:h(2)   -100.000 to 100.000 0.000
_:5 Filter:h(3)   -100.000 to 100.000 0.000
_:6 Filter:h(4)   -100.000 to 100.000 1.000

Setting parameters for Stage with Thermal Overload Protection, 3-Phase – Advanced

Addr. Parameter C Setting Options Default Setting
49 Th.overl. #
_:1 49 Th.overl. #:Mode   off
on
test
off
_:2 49 Th.overl. #:Operate & flt.rec. blocked   no
yes
no
_:101 49 Th.overl. #:Threshold current warning 1 A @ 100 Irated 0.030 A to 35.000 A 1.000 A
5 A @ 100 Irated 0.15 A to 175.00 A 5.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.000 A
5 A @ 50 Irated 0.15 A to 175.00 A 5.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.000 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 5.000 A
_:104 49 Th.overl. #:Threshold thermal warn.   50 % to 100 % 90 %
_:105 49 Th.overl. #:Dropout threshold operate   50 % to 99 % 90 %
_:112 49 Th.overl. #:Emerg. start T overtravel   0 s to 15000 s 300 s
_:106 49 Th.overl. #:K-factor   0.10 to 4.00 1.10
_:110 49 Th.overl. #:Thermal time constant   10 s to 60000 s 900 s
_:111 49 Th.overl. #:Cooling time constant   10 s to 60000 s 3600 s
_:107 49 Th.overl. #:Imax thermal 1 A @ 100 Irated 0.030 A to 10.000 A 2.500 A
5 A @ 100 Irated 0.15 A to 50.00 A 12.50 A
1 A @ 50 Irated 0.030 A to 10.000 A 2.500 A
5 A @ 50 Irated 0.15 A to 50.00 A 12.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 2.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 12.500 A
_:108 49 Th.overl. #:Imin cooling 1 A @ 100 Irated 0.000 A to 10.000 A 0.500 A
5 A @ 100 Irated 0.00 A to 50.00 A 2.50 A
1 A @ 50 Irated 0.000 A to 10.000 A 0.500 A
5 A @ 50 Irated 0.00 A to 50.00 A 2.50 A
1 A @ 1.6 Irated 0.000 A to 1.600 A 0.500 A
5 A @ 1.6 Irated 0.000 A to 8.000 A 2.500 A
_:109 49 Th.overl. #:Temperature rise at Irated   40 K to 200 K 70 K
_:113 49 Th.overl. #:Storage of thermal replica   no
yes
no
_:114 49 Th.overl. #:Behav. at I> Imax therm.   current limiting
freeze therm. rep.
current limiting
_:118 49 Th.overl. #:Default temperature   -55°C to 55°C 40°C
_:117 49 Th.overl. #:Minimal temperature   -55°C to 40°C -20°C
_:44 49 Th.overl. #:Temperature sensor   Setting options depend on configuration  

Logic Diagrams & highlights


Logic Diagram of the Function Block Filter

Logic Diagram of the Function Block Filter

Logic Diagram of the Thermal Overload Protection, 3-Phase – Advanced Stage

Logic Diagram of the Thermal Overload Protection, 3-Phase - Advanced Stage

Logic Diagram of the Stage Control

Logic Diagram of the Stage Control