Table of Contents

Siemens / Thermal overload protection, 1-phase (ANSI 49) _ Setting & highlights _ SI5060

Table of Contents

Overview

The “Thermal overload protection, 1-phase” function is used to protect the equipment (reactors or resistors in the neutral point of a transformer) from thermal overload.

For more detailed information on “Thermal overload protection, 1-phase” function, refer to SIPROTEC 5 devices, V8.30 & higher manuals.

To see other supported functions, click here.


Structure/Embedding of the Function

Structure/Embedding of the Thermal overload protection, 1-phase Function

Setting Parameters


Setting parameters for Thermal overload protection, 1-phase

Addr. Parameter C Setting Options Default Setting
49 Th.overl. #
_:1 49 Th.overl. #:Mode   off
on
test
off
_:2 49 Th.overl. #:Operate & flt.rec. blocked   no
yes
no
_:101 49 Th.overl. #:Threshold current warning 1 A @ 100 Irated 0.030 A to 35.000 A 1.000 A
5 A @ 100 Irated 0.15 A to 175.00 A 5.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.000 A
5 A @ 50 Irated 0.15 A to 175.00 A 5.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.000 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 5.000 A
_:104 49 Th.overl. #:Threshold thermal warn.   50 % to 100 % 90 %
_:105 49 Th.overl. #:Dropout threshold operate   50 % to 99 % 90 %
_:106 49 Th.overl. #:K-factor   0.10 to 4.00 1.10
_:110 49 Th.overl. #:Thermal time constant   10 s to 60000 s 900 s
_:107 49 Th.overl. #:Imax thermal 1 A @ 100 Irated 0.030 A to 10.000 A 2.500 A
5 A @ 100 Irated 0.15 A to 50.00 A 12.50 A
1 A @ 50 Irated 0.030 A to 10.000 A 2.500 A
5 A @ 50 Irated 0.15 A to 50.00 A 12.50 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 2.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 12.500 A
_:109 49 Th.overl. #:Tempera- ture rise at Irated   40 K to 200 K 70 K
_:113 49 Th.overl. #:Storage of thermal replica   no
yes
no
_:114 49 Th.overl. #:Behav. at I> Imax therm.   current limiting
freeze therm. rep.
current limiting
_:118 49 Th.overl. #:Default temperature   -55°C to 55°C 40°C
_:117 49 Th.overl. #:Minimal temperature   -55°C to 40°C -20°C
_:44 49 Th.overl. #:Tempera- ture sensor   Setting options depend on configuration  

Logic Diagrams & highlights


Logic Diagram of the Thermal Overload Protection Function

Logic Diagram of the Thermal Overload Protection Function

Temperature History for Different Overload Currents (K-factor = 1.1)

Temperature History for Different Overload Currents (K-factor = 1.1)