Overview
The “Temperature supervision” function checks the thermal state of motors, generators, and transformers. In rotating machines, it also checks bearing temperatures for a limit violation.
For more detailed information on “Temperature Supervision” function, refer to SIPROTEC 5 devices, V8.30 & higher manuals.
To see other supported functions, click here.
Structure/Embedding of the Function
Setting Parameters
Setting parameters for Temperature supervision function
Addr. | Parameter | C | Setting Options | Default Setting |
Point 1 | ||||
_:11101:46 | Point 1:Sensor location | Oil Ambient Turn Bearing Other |
Other | |
_:11101:1 | Point 1:Mode | off on test |
off | |
_:11101:40 | Point 1:Threshold stage 1 | -50°C to 250°C | 100°C | |
_:11101:41 | Point 1:Operate delay of stage 1 | 0 s to 60 s; ∞ | 5 s | |
_:11101:42 | Point 1:Threshold stage 2 | -50°C to 250°C | 120°C | |
_:11101:43 | Point 1:Operate delay of stage 2 | 0 s to 60 s; ∞ | 0 s | |
_:11101:44 | Point 1:Sensor | Setting options depend on config- uration | ||
Point 2 | ||||
_:11102:46 | Point 2:Sensor location | Oil Ambient Turn Bearing Other |
Other | |
_:11102:1 | Point 2:Mode | off on test |
off | |
_:11102:40 | Point 2:Threshold stage 1 | -50°C to 250°C | 100°C | |
_:11102:41 | Point 2:Operate delay of stage 1 | 0 s to 60 s; ∞ | 5 s | |
_:11102:42 | Point 2:Threshold stage 2 | -50°C to 250°C | 120°C | |
_:11102:43 | Point 2:Operate delay of stage 2 | 0 s to 60 s; ∞ | 0 s | |
_:11102:44 | Point 2:Sensor | Setting options depend on config- uration | ||
Point 3 | ||||
_:11103:46 | Point 3:Sensor location | Oil Ambient Turn Bearing Other |
Other | |
_:11103:1 | Point 3:Mode | off on test |
off | |
_:11103:40 | Point 3:Threshold stage 1 | -50°C to 250°C | 100°C | |
_:11103:41 | Point 3:Operate delay of stage 1 | 0 s to 60 s; ∞ | 5 s | |
_:11103:42 | Point 3:Threshold stage 2 | -50°C to 250°C | 120°C | |
_:11103:43 | Point 3:Operate delay of stage 2 | 0 s to 60 s; ∞ | 0 s | |
_:11103:44 | Point 3:Sensor | Setting options depend on config- uration | ||
Point 4 | ||||
_:11104:46 | Point 4:Sensor location | Oil Ambient Turn Bearing Other |
Other | |
_:11104:1 | Point 4:Mode | off on test |
off | |
_:11104:40 | Point 4:Threshold stage 1 | -50°C to 250°C | 100°C | |
_:11104:41 | Point 4:Operate delay of stage 1 | 0 s to 60 s; ∞ | 5 s | |
_:11104:42 | Point 4:Threshold stage 2 | -50°C to 250°C | 120°C | |
_:11104:43 | Point 4:Operate delay of stage 2 | 0 s to 60 s; ∞ | 0 s | |
_:11104:44 | Point 4:Sensor | Setting options depend on config- uration | ||
Point 5 | ||||
_:11105:46 | Point 5:Sensor location | Oil Ambient Turn Bearing Other |
Other | |
_:11105:1 | Point 5:Mode | off on test |
off | |
_:11105:40 | Point 5:Threshold stage 1 | -50°C to 250°C | 100°C | |
_:11105:41 | Point 5:Operate delay of stage 1 | 0 s to 60 s; ∞ | 5 s | |
_:11105:42 | Point 5:Threshold stage 2 | -50°C to 250°C | 120°C | |
_:11105:43 | Point 5:Operate delay of stage 2 | 0 s to 60 s; ∞ | 0 s | |
_:11105:44 | Point 5:Sensor | Setting options depend on config- uration | ||
Point 6 | ||||
_:11106:46 | Point 6:Sensor location | Oil Ambient Turn Bearing Other |
||
_:11106:1 | Point 6:Mode | off on test |
off | |
_:11106:40 | Point 6:Threshold stage 1 | -50°C to 250°C | 100°C | |
_:11106:41 | Point 6:Operate delay of stage 1 | 0 s to 60 s; ∞ | 5 s | |
_:11106:42 | Point 6:Threshold stage 2 | -50°C to 250°C | 120°C | |
_:11106:43 | Point 6:Operate delay of stage 2 | 0 s to 60 s; ∞ | 0 s | |
_:11106:44 | Point 6:Sensor | Setting options depend on config- uration | ||
Point 7 | ||||
_:11107:46 | Point 7:Sensor location | Oil Ambient Turn Bearing Other |
Other | |
_:11107:1 | Point 7:Mode | off on test |
off | |
_:11107:40 | Point 7:Threshold stage 1 | -50°C to 250°C | 100°C | |
_:11107:41 | Point 7:Operate delay of stage 1 | 0 s to 60 s; ∞ | 5 s | |
_:11107:42 | Point 7:Threshold stage 2 | -50°C to 250°C | 120°C | |
_:11107:43 | Point 7:Operate delay of stage 2 | 0 s to 60 s; ∞ | 0 s | |
_:11107:44 | Point 7:Sensor | Setting options depend on config- uration | ||
Point 8 | ||||
_:11108:46 | Point 8:Sensor location | Oil Ambient Turn Bearing Other |
Other | |
_:11108:1 | Point 8:Mode | off on test |
off | |
_:11108:40 | Point 8:Threshold stage 1 | -50°C to 250°C | 100°C | |
_:11108:41 | Point 8:Operate delay of stage 1 | 0 s to 60 s; ∞ | 5 s | |
_:11108:42 | Point 8:Threshold stage 2 | -50°C to 250°C | 120°C | |
_:11108:43 | Point 8:Operate delay of stage 2 | 0 s to 60 s; ∞ | 0 s | |
_:11108:44 | Point 8:Sensor | Setting options depend on config- uration | ||
Point 9 | ||||
_:11109:46 | Point 9:Sensor location | Oil Ambient Turn Bearing Other |
Other | |
_:11109:1 | Point 9:Mode | off on test |
off | |
_:11109:40 | Point 9:Threshold stage 1 | -50°C to 250°C | 100°C | |
_:11109:41 | Point 9:Operate delay of stage 1 | 0 s to 60 s; ∞ | 5 s | |
_:11109:42 | Point 9:Threshold stage 2 | -50°C to 250°C | 120°C | |
_:11109:43 | Point 9:Operate delay of stage 2 | 0 s to 60 s; ∞ | 0 s | |
_:11109:44 | Point 9:Sensor | Setting options depend on config- uration | ||
Point 10 | ||||
_:11110:46 | Point 10:Sensor location | Oil Ambient Turn Bearing Other |
Other | |
_:11110:1 | Point 10:Mode | off on test |
off | |
_:11110:40 | Point 10:Threshold stage 1 | -50°C to 250°C | 100°C | |
_:11110:41 | Point 10:Operate delay of stage 1 | 0 s to 60 s; ∞ | 5 s | |
_:11110:42 | Point 10:Threshold stage 2 | -50°C to 250°C | 120°C | |
_:11110:43 | Point 10:Operate delay of stage 2 | 0 s to 60 s; ∞ | 0 s | |
_:11110:44 | Point 10:Sensor | Setting options depend on config- uration | ||
Point 11 | ||||
_:11111:46 | Point 11:Sensor location | Oil Ambient Turn Bearing Other |
Other | |
_:11111:1 | Point 11:Mode | off on test |
off | |
_:11111:40 | Point 11:Threshold stage 1 | -50°C to 250°C | 100°C | |
_:11111:41 | Point 11:Operate delay of stage 1 | 0 s to 60 s; ∞ | 5 s | |
_:11111:42 | Point 11:Threshold stage 2 | -50°C to 250°C | 120°C | |
_:11111:43 | Point 11:Operate delay of stage 2 | 0 s to 60 s; ∞ | 0 s | |
_:11111:44 | Point 11:Sensor | Setting options depend on config- uration | ||
Point 12 | ||||
_:11112:46 | Point 12:Sensor location | Oil Ambient Turn Bearing Other |
Other | |
_:11112:1 | Point 12:Mode | off on test |
off | |
_:11112:40 | Point 12:Threshold stage 1 | -50°C to 250°C | 100°C | |
_:11112:41 | Point 12:Operate delay of stage 1 | 0 s to 60 s; ∞ | 5 s | |
_:11112:42 | Point 12:Threshold stage 2 | -50°C to 250°C | 120°C | |
_:11112:43 | Point 12:Operate delay of stage 2 | 0 s to 60 s; ∞ | 0 s | |
_:11112:44 | Point 12:Sensor | Setting options depend on config- uration | ||