Siemens / Temperature supervision _ Setting & highlights _ SI5061

Table of Contents

Overview

The “Temperature supervision” function checks the thermal state of motors, generators, and transformers. In rotating machines, it also checks bearing temperatures for a limit violation.

For more detailed information on “Temperature Supervision” function, refer to SIPROTEC 5 devices, V8.30 & higher manuals.

To see other supported functions, click here.


Structure/Embedding of the Function

Structure/Embedding of the Temperature supervision Function

Setting Parameters


Setting parameters for Temperature supervision function

Addr. Parameter C Setting Options Default Setting
Point 1
_:11101:46 Point 1:Sensor location   Oil
Ambient
Turn
Bearing
Other
Other
_:11101:1 Point 1:Mode   off
on
test
off
_:11101:40 Point 1:Threshold stage 1   -50°C to 250°C 100°C
_:11101:41 Point 1:Operate delay of stage 1   0 s to 60 s; ∞ 5 s
_:11101:42 Point 1:Threshold stage 2   -50°C to 250°C 120°C
_:11101:43 Point 1:Operate delay of stage 2   0 s to 60 s; ∞ 0 s
_:11101:44 Point 1:Sensor   Setting options depend on config- uration  
Point 2
_:11102:46 Point 2:Sensor location   Oil
Ambient
Turn
Bearing
Other
Other
_:11102:1 Point 2:Mode   off
on
test
off
_:11102:40 Point 2:Threshold stage 1   -50°C to 250°C 100°C
_:11102:41 Point 2:Operate delay of stage 1   0 s to 60 s; ∞ 5 s
_:11102:42 Point 2:Threshold stage 2   -50°C to 250°C 120°C
_:11102:43 Point 2:Operate delay of stage 2   0 s to 60 s; ∞ 0 s
_:11102:44 Point 2:Sensor   Setting options depend on config- uration  
Point 3
_:11103:46 Point 3:Sensor location   Oil
Ambient
Turn
Bearing
Other
Other
_:11103:1 Point 3:Mode   off
on
test
off
_:11103:40 Point 3:Threshold stage 1   -50°C to 250°C 100°C
_:11103:41 Point 3:Operate delay of stage 1   0 s to 60 s; ∞ 5 s
_:11103:42 Point 3:Threshold stage 2   -50°C to 250°C 120°C
_:11103:43 Point 3:Operate delay of stage 2   0 s to 60 s; ∞ 0 s
_:11103:44 Point 3:Sensor   Setting options depend on config- uration  
Point 4
_:11104:46 Point 4:Sensor location   Oil
Ambient
Turn
Bearing
Other
Other
_:11104:1 Point 4:Mode   off
on
test
off
_:11104:40 Point 4:Threshold stage 1   -50°C to 250°C 100°C
_:11104:41 Point 4:Operate delay of stage 1   0 s to 60 s; ∞ 5 s
_:11104:42 Point 4:Threshold stage 2   -50°C to 250°C 120°C
_:11104:43 Point 4:Operate delay of stage 2   0 s to 60 s; ∞ 0 s
_:11104:44 Point 4:Sensor   Setting options depend on config- uration  
Point 5
_:11105:46 Point 5:Sensor location   Oil
Ambient
Turn
Bearing
Other
Other
_:11105:1 Point 5:Mode   off
on
test
off
_:11105:40 Point 5:Threshold stage 1   -50°C to 250°C 100°C
_:11105:41 Point 5:Operate delay of stage 1   0 s to 60 s; ∞ 5 s
_:11105:42 Point 5:Threshold stage 2   -50°C to 250°C 120°C
_:11105:43 Point 5:Operate delay of stage 2   0 s to 60 s; ∞ 0 s
_:11105:44 Point 5:Sensor   Setting options depend on config- uration  
Point 6
_:11106:46 Point 6:Sensor location   Oil
Ambient
Turn
Bearing
Other
 
_:11106:1 Point 6:Mode   off
on
test
off
_:11106:40 Point 6:Threshold stage 1   -50°C to 250°C 100°C
_:11106:41 Point 6:Operate delay of stage 1   0 s to 60 s; ∞ 5 s
_:11106:42 Point 6:Threshold stage 2   -50°C to 250°C 120°C
_:11106:43 Point 6:Operate delay of stage 2   0 s to 60 s; ∞ 0 s
_:11106:44 Point 6:Sensor   Setting options depend on config- uration  
Point 7
_:11107:46 Point 7:Sensor location   Oil
Ambient
Turn
Bearing
Other
Other
_:11107:1 Point 7:Mode   off
on
test
off
_:11107:40 Point 7:Threshold stage 1   -50°C to 250°C 100°C
_:11107:41 Point 7:Operate delay of stage 1   0 s to 60 s; ∞ 5 s
_:11107:42 Point 7:Threshold stage 2   -50°C to 250°C 120°C
_:11107:43 Point 7:Operate delay of stage 2   0 s to 60 s; ∞ 0 s
_:11107:44 Point 7:Sensor   Setting options depend on config- uration  
Point 8
_:11108:46 Point 8:Sensor location   Oil
Ambient
Turn
Bearing
Other
Other
_:11108:1 Point 8:Mode   off
on
test
off
_:11108:40 Point 8:Threshold stage 1   -50°C to 250°C 100°C
_:11108:41 Point 8:Operate delay of stage 1   0 s to 60 s; ∞ 5 s
_:11108:42 Point 8:Threshold stage 2   -50°C to 250°C 120°C
_:11108:43 Point 8:Operate delay of stage 2   0 s to 60 s; ∞ 0 s
_:11108:44 Point 8:Sensor   Setting options depend on config- uration  
Point 9
_:11109:46 Point 9:Sensor location   Oil
Ambient
Turn
Bearing
Other
Other
_:11109:1 Point 9:Mode   off
on
test
off
_:11109:40 Point 9:Threshold stage 1   -50°C to 250°C 100°C
_:11109:41 Point 9:Operate delay of stage 1   0 s to 60 s; ∞ 5 s
_:11109:42 Point 9:Threshold stage 2   -50°C to 250°C 120°C
_:11109:43 Point 9:Operate delay of stage 2   0 s to 60 s; ∞ 0 s
_:11109:44 Point 9:Sensor   Setting options depend on config- uration  
Point 10
_:11110:46 Point 10:Sensor location   Oil
Ambient
Turn
Bearing
Other
Other
_:11110:1 Point 10:Mode   off
on
test
off
_:11110:40 Point 10:Threshold stage 1   -50°C to 250°C 100°C
_:11110:41 Point 10:Operate delay of stage 1   0 s to 60 s; ∞ 5 s
_:11110:42 Point 10:Threshold stage 2   -50°C to 250°C 120°C
_:11110:43 Point 10:Operate delay of stage 2   0 s to 60 s; ∞ 0 s
_:11110:44 Point 10:Sensor   Setting options depend on config- uration  
Point 11
_:11111:46 Point 11:Sensor location   Oil
Ambient
Turn
Bearing
Other
Other
_:11111:1 Point 11:Mode   off
on
test
off
_:11111:40 Point 11:Threshold stage 1   -50°C to 250°C 100°C
_:11111:41 Point 11:Operate delay of stage 1   0 s to 60 s; ∞ 5 s
_:11111:42 Point 11:Threshold stage 2   -50°C to 250°C 120°C
_:11111:43 Point 11:Operate delay of stage 2   0 s to 60 s; ∞ 0 s
_:11111:44 Point 11:Sensor   Setting options depend on config- uration  
Point 12
_:11112:46 Point 12:Sensor location   Oil
Ambient
Turn
Bearing
Other
Other
_:11112:1 Point 12:Mode   off
on
test
off
_:11112:40 Point 12:Threshold stage 1   -50°C to 250°C 100°C
_:11112:41 Point 12:Operate delay of stage 1   0 s to 60 s; ∞ 5 s
_:11112:42 Point 12:Threshold stage 2   -50°C to 250°C 120°C
_:11112:43 Point 12:Operate delay of stage 2   0 s to 60 s; ∞ 0 s
_:11112:44 Point 12:Sensor   Setting options depend on config- uration  