Overview
Information is exchanged with the remote station so that the ground-fault protection switches off immediately and selectively on the entire line for all errors. The “Teleprotection with ground fault protection” methods are used in protection function groups with a voltage-measuring point in combination with the Ground-fault protection function.
For more detailed information on “Teleprotection with ground fault protection” methods, refer to SIPROTEC 5 devices, V8.30 & higher manuals.
To see other supported functions, click here.
Structure/Embedding of the Function

Function Blocks and Function Control

Setting Parameters
Setting parameters for Permissive Overreach Transfer Trip
Addr. | Parameter | C | Setting Options | Default Setting |
85-67N Dir.com | ||||
_:5761:1 | 85-67N Dir.com:Mode | off on test |
on | |
_:5761:101 | 85-67N Dir.com:Send prolongation | 0.00 s to 60.00 s | 0.05 s | |
_:5761:102 | 85-67N Dir.com:Send delay | 0.00 s to 60.00 s | 0.00 s | |
_:5761:105 | 85-67N Dir.com:Trans. blk. pickup delay | 0.00 s to 60.00 s | 0.04 s | |
_:5761:106 | 85-67N Dir.com:Trans. blk. dropout delay | 0.00 s to 60.00 s | 0.05 s | |
_:5761:104 | 85-67N Dir.com:3I0 threshold rev./forw. |
0 % to 100 % | 75 % | |
_:5761:11 | 85-67N Dir.com:1-pole operate allowed | no yes |
yes | |
_:5761:103 | 85-67N Dir.com:Operate delay (1-phase) | 0.00 s to 60.00 s | 0.00 s | |
_:5761:140 | 85-67N Dir.com:Send with | Setting options depend on configuration | ||
_:5761:141 | 85-67N Dir.com:Operate with | Setting options depend on configuration | ||
_:5761:142 | 85-67N Dir.com:Trans. block. with | Setting options depend on configuration | ||
Setting parameters for Blocking Method
Addr. | Parameter | C | Setting Options | Default Setting |
85-67N Block. | ||||
_:5791:1 | 85-67N Block.:Mode | off on test |
on | |
_:5791:101 | 85-67N Block.:Send prolon- gation | 0.00 s to 60.00 s | 0.05 s | |
_:5791:102 | 85-67N Block.:Send with jump | no yes |
yes | |
_:5791:108 | 85-67N Block.:Send phase segregated | no yes |
no | |
_:5791:105 | 85-67N Block.:Trans. blk. pickup delay | 0.00 s to 60.00 s | 0.04 s | |
_:5791:106 | 85-67N Block.:Trans. blk. dropout delay | 0.00 s to 60.00 s | 0.05 s | |
_:5791:107 | 85-67N Block.:Release delay | 0.000 s to 60.000 s | 0.020 s | |
_:5791:104 | 85-67N Block.:3I0 threshold rev./forw. |
0 % to 100 % | 75 % | |
_:5791:11 | 85-67N Block.:1-pole operate allowed | no yes |
yes | |
_:5791:103 | 85-67N Block.:Operate delay (1-phase) | 0.00 s to 60.00 s | 0.00 s | |
_:5791:140 | 85-67N Block.:Operate with | Setting options depend on configuration | ||
_:5791:141 | 85-67N Block.:Trans. block. with | Setting options depend on configuration | ||
Logic Diagrams & highlights
Logic Diagram of the Receive Block: Binary Reception

Logic Diagram of the Receive Block: Unblock Reception

Logic Diagram of the Receive Block: Protection Interface

Function Block: Permissive Overreach Transfer Trip

Sending Logic for Permissive Overreach Transfer Trip

Trip Logic for Permissive Overreach Transfer Trip

Function Scheme of the Directional Comparison Procedure

Function Scheme of the Directional-Unblocking Method

Function Block: Blocking Method

Transmission Logic for the Blocking Method

Trip Logic for the Blocking Method

Function Scheme of the Blocking Method

Logic Diagram of the Transient Blocking

Possible Current Distribution with an External Ground-Fault

Logic of the Sensitive Ground-Fault Protection

Possible Inconvenient Current Distribution through a Teed Feeder in the Event of an External Ground Fault
