To enable selective and non-delayed fault clearance of all faults, on the entire line length, information exchange with the remote line end is applied. The “Teleprotection with distance protection” function is used in protection function groups with voltage-measuring point in combination with the distance protection function.
For more detailed information on “Teleprotection with distance protection”, refer to SIPROTEC 5 devices, V8.30 & higher manuals.
To see other supported functions, click here.
Structure/Embedding of the Function
Function control and the function blocks
Setting Parameters
Setting parameters for Permissive Underreach Transfer Trip
Addr. | Parameter | C | Setting Options | Default Setting |
85-21Perm.unde | ||||
_:5671:1 | 85-21Perm.unde:Mode | off on test |
on | |
_:5671:101 | 85-21Perm.unde:Send prolongation | 0.00 s to 60.00 s | 0.05 s | |
_:5671:11 | 85-21Perm.unde:1-pole operate allowed | no yes |
yes | |
_:5671:102 | 85-21Perm.unde:Operate delay (1-phase) | 0.00 s to 60.00 s | 0.00 s | |
_:5671:103 | 85-21Perm.unde:Operate delay (multi-ph.) | 0.00 s to 60.00 s | 0.00 s | |
_:5671:140 | 85-21Perm.unde:Send with | Setting options depend on configuration | ||
_:5671:141 | 85-21Perm.unde:Operate with | Setting options depend on configuration | ||
Setting parameters for Permissive Overreach Transfer Trip
Addr. | Parameter | C | Setting Options | Default Setting |
85-21Perm.over | ||||
_:5701:1 | 85-21Perm.over:Mode | off on test |
on | |
_:5701:101 | 85-21Perm.over:Send prolongation | 0.00 s to 60.00 s | 0.05 s | |
_:5701:102 | 85-21Perm.over:Send delay | 0.00 s to 60.00 s | 0.00 s | |
_:5701:105 | 85-21Perm.over:Trans. blk. pickup delay | 0.00 s to 60.00 s | 0.04 s | |
_:5701:106 | 85-21Perm.over:Trans. blk. dropout delay | 0.00 s to 60.00 s | 0.05 s | |
_:5701:11 | 85-21Perm.over:1-pole operate allowed |
no yes |
yes | |
_:5701:103 | 85-21Perm.over:Operate delay (1-phase) | 0.00 s to 60.00 s | 0.00 s | |
_:5701:104 | 85-21Perm.over:Operate delay (multi-ph.) | 0.00 s to 60.00 s | 0.00 s | |
_:5701:140 | 85-21Perm.over:Send with | Setting options depend on configuration | ||
_:5701:141 | 85-21Perm.over:Operate with | Setting options depend on configuration | ||
_:5701:142 | 85-21Perm.over:Trans. block. with | Setting options depend on configuration | ||
Setting parameters for Blocking Method
Addr. | Parameter | C | Setting Options | Default Setting |
85-21 Blocking | ||||
_:5731:1 | 85-21 Blocking:Mode | off on test |
on | |
_:5731:101 | 85-21 Blocking:Send prolongation | 0.00 s to 60.00 s | 0.05 s | |
_:5731:102 | 85-21 Blocking:Send with jump | no yes |
yes | |
_:5731:108 | 85-21 Blocking:Send phase segregated | no yes |
no | |
_:5731:105 | 85-21 Blocking:Trans. blk. pickup delay | 0.00 s to 60.00 s | 0.04 s | |
_:5731:106 | 85-21 Blocking:Trans. blk. dropout delay | 0.00 s to 60.00 s | 0.05 s | |
_:5731:107 | 85-21 Blocking:Release delay | 0.000 s to 60.000 s | 0.020 s | |
_:5731:11 | 85-21 Blocking:1-pole operate allowed | no yes |
yes | |
_:5731:103 | 85-21 Blocking:Operate delay (1-phase) | 0.00 s to 60.00 s | 0.00 s | |
_:5731:104 | 85-21 Blocking:Operate delay (multi-ph.) | 0.00 s to 60.00 s | 0.00 s | |
_:5731:140 | 85-21 Blocking:Operate with | Setting options depend on configuration | ||
_:5731:141 | 85-21 Blocking:Trans. block. with | Setting options depend on configuration | ||
Setting parameters for Reverse Interlocking
Addr. | Parameter | C | Setting Options | Default Setting |
85-21Rev.interlock | ||||
_:14311:1 | 85-21Rev.interlock:Mode | off on test |
on | |
_:14311:106 | 85-21Rev.interlock:Trans. blk. dropout delay | 0.00 s to 60.00 s | 0.05 s | |
_:14311:11 | 85-21Rev.interlock:1-pole operate allowed | no yes |
yes | |
_:14311:103 | 85-21Rev.interlock:Operate delay (1-phase) | 0.00 s to 60.00 s | 0.04 s | |
_:14311:104 | 85-21Rev.interlock:Operate delay (multi-ph.) | 0.00 s to 60.00 s | 0.04 s | |
_:14311:140 | 85-21Rev.interlock:Operate with | Setting options depend on configuration | ||