Overview
The “Sudden change in current variation” function is a fast way of finding any abnormality in line currents. When there is a fault in the system, the current changes faster than the voltage. SCCVPTOC finds abnormal condition based on phase-to-phase current variation. The main application is as a local criterion to increase security when transfer trips are used.
For more detailed information on “Sudden change in current variation” function, refer to ABB, Relion 670 Series manuals.
To see other supported functions, click here.
Function Identification
Function description | IEC 61850 identification |
IEC 60617 identification |
ANSI/IEEE C37.2 device number |
Sudden change in current variation | SCCVPTOC | – | 51 |
Signals & Setting Parameters
SCCVPTOC function block
SCCVPTOC Input signals
SCCVPTOC Input signals | |||
Name | Type | Default | Description |
I3P | GROUP SIGNAL | – | Three phase to phase current samples group |
BLOCK | BOOLEAN | 0 | Block of function |
BLKTR | BOOLEAN | 0 | Block trip signals |
SCCVPTOC Output signals
SCCVPTOC Output signals | |||
Name | Type | Description | |
TRIP | BOOLEAN | Common trip signal | |
START | BOOLEAN | Common start signal | |
SCCVPTOC Group settings (basic)
SCCVPTOC Group settings (basic) | |||||
Name | Values (Range) | Unit | Step | Default | Description |
Operation | Off On |
– | – | Off | Operation Off/On |
I> | 5 – 100 | %IB | 1 | 20 | Fixed threshold setting in % of IBase |
tHold | 0.000 – 60.000 | s | 0.001 | 0.500 | Hold time for operate signals |
SCCVPTOC Group settings (advanced)
SCCVPTOC Group settings (advanced) | |||||
Name | Values (Range) | Unit | Step | Default | Description |
tDelay | 0.000 – 0.005 | s | 0.001 | 0.002 | Time delay for start and trip signals |
SCCVPTOC Non group settings (basic)
SCCVPTOC Non group settings (basic) | |||||
Name | Values (Range) | Unit | Step | Default | Description |
GlobalBaseSel | 1 – 12 | – | 1 | 1 | Selection of one of the Global Base Value groups |