Overview

The function “Stator ground fault protection with 3rd harmonic” detects stator ground faults in the generator neutral point (approx. 10% to 25%). It is used for generators in a unit connection and evaluates the 3rd harmonic of the residual voltage (zero voltage V0 3 harm). This function can only be used if the generator has generated sufficient 3rd harmonics.

For more detailed information on “Stator ground fault protection with 3rd harmonic” function, refer to SIPROTEC 5 devices, V8.30 & higher manuals.

To see other supported functions, click here.


Structure/Embedding of the Function

Structure/Embedding of the Function

Possible Assignment of the Stage Types to the Measuring Points of the Function Group Generator Stator

Possible Assignment of the Stage Types to the Measuring Points of the Function Group Generator Stator

Setting Parameters


General setting parameters

Addr. Parameter C Setting Options Default Setting
General
_:2311:101 General:Threshold P min   0.0 % to 100.0 % 40.0 %
_:2311:102 General:Threshold V1 min   0.300 V to 200.000 V 46.000 V
_:2311:103 General:Corr. factor for V03H>   0.000 V to 40.000 V 0.000 V
_:2311:104 General:V03H Gen./ V03H neut. pt   0.10 to 10.00 1.00
_:2311:105 General:Corr. factor for ΔV03H>   – 40.000 V to 40.000 V 0.000 V
_:2311:106 General:Dropout delay   0.00 s to 60.00 s 1.00 s

Setting parameters for Stage V0 3rd Harm. <

Addr. Parameter C Setting Options Default Setting
V0 3. Harm< 1
_:16801:1 V0 3. Harm< 1:Mode   off
on
test
off
_:16801:2 V0 3. Harm< 1:Operate & flt.rec. blocked   no
yes
no
_:16801:101 V0 3. Harm< 1:Threshold   0.300 V to 100.000 V 1.000 V
_:16801:102 V0 3. Harm< 1:Dropout delay   0.00 s to 60.00 s 0.00 s
_:16801:6 V0 3. Harm< 1:Operate delay   0.00 s to 60.00 s 0.50 s

Setting parameters for Stage V0 3rd Harm. >

Addr. Parameter C Setting Options Default Setting
V0 3. Harm> #
_:1 V0 3. Harm> #:Mode   off
on
test
off
_:2 V0 3. Harm> #:Operate & flt.rec. blocked   no
yes
no
_:101 V0 3. Harm> #:Threshold   0.300 V to 100.000 V 10.000 V
_:102 V0 3. Harm> #:Dropout delay   0.00 s to 60.00 s 0.00 s
_:6 V0 3. Harm> #:Operate delay   0.00 s to 60.00 s 0.50 s

Setting parameters for Stage ΔV0 3rd Harm. >

Addr. Parameter C Setting Options Default Setting
ΔV0 3. Harm> #
_:1 ΔV0 3. Harm> #:Mode   off
on
test
off
_:2 ΔV0 3. Harm> #:Operate & flt.rec. blocked   no
yes
no
_:101 ΔV0 3. Harm>
#:Threshold
  0.300 V to 100.000 V 3.000 V
_:102 ΔV0 3. Harm> #:Dropout delay   0.00 s to 60.00 s 0.00 s
_:6 ΔV0 3. Harm> #:Operate delay   0.00 s to 60.00 s 0.50 s

Logic Diagrams & highlights


Course of the 3rd Harmonic along the Stator Winding

Course of the 3rd Harmonic along the Stator Winding

Logic Diagram Function Block General

Logic Diagram Function Block General

Logic of the Stage V0 3rd Harm. <

Logic of the Stage V0 3rd Harm. <

Logic of the Stage V0 3rd Harm. >

Logic of the Stage V0 3rd Harm. >

Correction factor for V03H>

Correction factor for V03H>

3rd Harmonic of the Voltage (Secondary) as a Function of the Active Power (Reactive Power as a Parameter)

3rd Harmonic of the Voltage (Secondary) as a Function of the Active Power (Reactive Power as a Parameter)

Logic of the Stage V0 3rd Harm. Delta

Logic of the Stage V0 3rd Harm. Delta

Connection type recommendation & Difference method calculations

Connection type recommendation & Difference method calculations

Correction factor for ΔV03H>

Correction factor for ΔV03H>