Overview
The “Stator ground fault protection 90 %” function detects ground faults in the stator of generators and motors. It can be used for unit connections and busbar connections, and evaluates the fundamental signals of the residual voltage (zero-sequence voltage V0) and of the ground current (zero-sequence current 3I0). By using this function, between 80 % and 95 % of the stator ground fault protection can be implemented depending on the design of the load equipment.
For more detailed information on “Stator ground fault protection 90 %” function, refer to SIPROTEC 5 devices, V8.30 & higher manuals.
To see other supported functions, click here.
Possible Assignment of the Stage Types to the Measuring Points of the Function Group Generator Stator with a Unit Connection
Possible Assignment of the Stage Types to the Measuring Points of the Function Group Generator Stator with a Bus Connection
Structure/Embedding of the Function
Setting Parameters
General Setting parameters
Addr. | Parameter | C | Setting Options | Default Setting |
General | ||||
_:2311:103 | General:Dropout delay | 0.00 s to 60.00 s | 1.00 s | |
_:2311:104 | General:Core balance CT- current 1 | 1 A @ 100 Irated | 0.030 A to 35.000 A | 0.050 A |
5 A @ 100 Irated | 0.15 A to 175.00 A | 0.25 A | ||
1 A @ 1.6 Irated | 0.001 A to 1.600 A | 0.050 A | ||
5 A @ 1.6 Irated | 0.005 A to 8.000 A | 0.250 A | ||
_:2311:105 | General:Core balance CT- current 2 | 1 A @ 100 Irated | 0.030 A to 35.000 A | 1.000 A |
5 A @ 100 Irated | 0.15 A to 175.00 A | 5.00 A | ||
1 A @ 1.6 Irated | 0.001 A to 1.600 A | 1.000 A | ||
5 A @ 1.6 Irated | 0.005 A to 8.000 A | 5.000 A | ||
_:2311:106 | General:CT angle error at I1 | 0.0 ° to 5.0 ° | 0.0 ° | |
_:2311:107 | General:CT angle error at I2 | 0.0 ° to 5.0 ° | 0.0 ° | |