Overview
The “Startup overcurrent protection” function protects Gas-turbine generators that can be started by static‑frequency converters (SFC) at low frequencies during the startup, Pumped-storage generators or motors that meet two special conditions, and Hydraulic power plant that is in the electric-braking mode.
For more detailed information on “Startup overcurrent protection” function, refer to SIPROTEC 5 devices, V8.30 & higher manuals.
To see other supported functions, click here.
Structure/Embedding of the Function
Setting Parameters
Setting parameters for Startup overcurrent protection
Addr. | Parameter | C | Setting Options | Default Setting |
Stage 1 | ||||
_:17551:1 | Stage 1:Mode | off on test |
off | |
_:17551:2 | Stage 1:Operate & flt.rec. blocked | no yes |
no | |
_:17551:3 | Stage 1:Threshold | 1 A @ 100 Irated | 0.100 A to 35.000 A | 1.300 A |
5 A @ 100 Irated | 0.50 A to 175.00 A | 6.50 A | ||
1 A @ 50 Irated | 0.100 A to 35.000 A | 1.300 A | ||
5 A @ 50 Irated | 0.50 A to 175.00 A | 6.50 A | ||
1 A @ 1.6 Irated | 0.003 A to 1.600 A | 1.300 A | ||
5 A @ 1.6 Irated | 0.017 A to 8.000 A | 6.500 A | ||
_:17551:7 | Stage 1:Dropout delay | 0.00 s to 60.00 s | 0.00 s | |
_:17551:6 | Stage 1:Operate delay | 0.00 s to 60.00 s | 0.50 s | |