Siemens / Startup overcurrent protection (ANSI 51) _ Setting & highlights _ SI5090

Table of Contents

Overview

The “Startup overcurrent protection” function protects Gas-turbine generators that can be started by static‑frequency converters (SFC) at low frequencies during the startup, Pumped-storage generators or motors that meet two special conditions, and Hydraulic power plant that is in the electric-braking mode.

For more detailed information on “Startup overcurrent protection” function, refer to SIPROTEC 5 devices, V8.30 & higher manuals.

To see other supported functions, click here.


Structure/Embedding of the Function

Structure/Embedding of the Function

Setting Parameters


Setting parameters for Startup overcurrent protection

Addr. Parameter C Setting Options Default Setting
Stage 1
_:17551:1 Stage 1:Mode   off
on
test
off
_:17551:2 Stage 1:Operate & flt.rec. blocked   no
yes
no
_:17551:3 Stage 1:Threshold 1 A @ 100 Irated 0.100 A to 35.000 A 1.300 A
5 A @ 100 Irated 0.50 A to 175.00 A 6.50 A
1 A @ 50 Irated 0.100 A to 35.000 A 1.300 A
5 A @ 50 Irated 0.50 A to 175.00 A 6.50 A
1 A @ 1.6 Irated 0.003 A to 1.600 A 1.300 A
5 A @ 1.6 Irated 0.017 A to 8.000 A 6.500 A
_:17551:7 Stage 1:Dropout delay   0.00 s to 60.00 s 0.00 s
_:17551:6 Stage 1:Operate delay   0.00 s to 60.00 s 0.50 s

Logic Diagrams & highlights


Characteristic Quantities During Startup of a Gas Turbine

Characteristic Quantities During Startup of a Gas Turbine

Operating Range and Possible Pickup Threshold of Short-Circuit Protection Functions

Operating Range and Possible Pickup Threshold of Short-Circuit Protection Functions

Logic Diagram of the General Functionality

Logic Diagram of the General Functionality

Logic Diagram of the Startup Overcurrent Protection Stage

Logic Diagram of the Startup Overcurrent Protection Stage

Short-Circuit Currents in the Generator During Startup (Srated, Gen = 300 MVA, Vrated, Gen = 15.75 kV, and frated = 50 Hz)

Short-Circuit Currents in the Generator During Startup (Srated, Gen = 300 MVA, Vrated, Gen = 15.75 kV, and frated = 50 Hz)