GE / Split phase protection (ANSI 50P) _ Element settings & highlights _ GU8050

Table of Contents

Overview

“Split phase protection” element can be applied to detect inter-turn faults when the generator is wound with two three-phase windings, each brought separately out of the machine and connected in parallel. The currents in the two windings are compared, any difference indicating an inter-turn fault.

For more detailed information on “Split phase protection” element, refer to GE, Universal Relay (UR) family of products, Version 8.0x manuals.

To see other supported elements, click here.


Setting Parameters


Modbus memory map for Setting parameters

Products Hex address Register name Range Units Step Format Default
G30, G60 41C1 Split Phase Protection Function 0 to 1 1 F102 0 (Disabled)
" 41C2 Split Phase Protection Source 0 to 5 1 F167 0 (SRC1)
" 41C3 Split Phase Protection Load Source 0 to 5 1 F167 0 (SRC1)
" 41C4 Split Phase Protection Phase A Pickup 0.02 to 1.5 pu 0.001 F001 200
" 41C5 Split Phase Protection Phase A Offset 0 to 1 pu 0.001 F001 0
" 41C6 Split Phase Protection Phase A Slope 0 to 100 % 0.1 F001 0
" 41C7 Split Phase Protection Phase B Pickup 0.02 to 1.5 pu 0.001 F001 200
" 41C8 Split Phase Protection Phase B Offset 0 to 1 pu 0.001 F001 0
" 41C9 Split Phase Protection Phase B Slope 0 to 100 % 0.1 F001 0
" 41CA Split Phase Protection Phase C Pickup 0.02 to 1.5 pu 0.001 F001 200
" 41CB Split Phase Protection Phase C Offset 0 to 1 pu 0.001 F001 0
" 41CC Split Phase Protection Phase C Slope 0 to 100 % 0.1 F001 0
" 41CD Split Phase Protection Minimum Load 0 to 1 pu 0.01 F001 0
" 41CE Split Phase Protection Mode 0 to 1 1 F225 0 (Over)
" 41CF Split Phase Protection Delay 0 to 65.535 s 0.001 F001 0
" 41D0 Split Phase Protection Block 0 to 4294967295 1 F300 0
" 41D2 Split Phase Protection Target 0 to 2 1 F109 0 (Self-Reset)
" 41D3 Split Phase Protection Events 0 to 1 1 F102 0 (Disabled)
" 41D4 Reserved (6 items) 0 to 65535 1 F001 0
F102 0 = Disabled, 1 = Enabled
F109 0 = Self-reset, 1 = Latched, 2 = Disabled
F167 0 = SRC 1, 1 = SRC 2, 2 = SRC 3, 3 = SRC 4, 4 = SRC 5, 5 = SRC 6
F225 0 = Over, 1 = Over-Under

Logics & highlights


Split phase protection for two CTs

Split phase protection for two CTs

Split phase protection for one CT

Split phase protection for one CT

Principle of operation

Principle of operation

Split phase protection operating characteristics

Split phase protection operating characteristics

Split phase protection logic

Split phase protection logic