Siemens / SIPROTEC 7VU683 V4.76 setting parameters & highlights (SI4020)

Table of Contents

Overview

The SIPROTEC 7VU683 high speed busbar transfer (HBST) device is a compact multifunction unit which has been developed for very fast power supply transfer of busbar which is installed with big rotating loads.

For more detailed information on “SIPROTEC 7VU683” relays, refer to SIPROTEC 4 devices manuals.

To see other supported devices, click here.


HSBT General Settings

Addr. Parameter C Range Default Setting Note
Device Configuration
0103 Setting group change option   Disable
Enable
Disable  
0158 High speed busbar transfer   Disable
Enable
Enable  
0160 Protection functions   Disable
Enable
Enable Sectionalized single busbar w. 3-CB
Power System Data 1-> Power System
0211 Rated frequency   50 Hz
60 Hz
50 Hz  
0213 VT connection of Line1   Ua
Ub
Uc
Uab
Ubc
Uca
Uab  
0214 VT connection of Line2   Ua
Ub
Uc
Uab
Ubc
Uca
Uab  
0218 VT connection of Line3   Ua
Ub
Uc
Uab
Ubc
Uca
Uab Single busbar with 3-CB
0280 CT connection of Line1   IA
IB
IC
not connected
IB  
0281 CT connection of Line2   IA
IB
IC
not connected
IB  
0282 CT connection of Line3   IA
IB
IC
not connected
IB Single busbar with 3-CB
0283 Voltage balancing factor of Line1   0.500<= … <=2.000 1.000  
0284 Voltage angle adjustment of Line1   0.0<= … <=359.9 0.0°  
0285 Voltage balancing factor of Line2   0.500<= … <=2.000 1.000  
0286 Voltage angle adjustment of Line2   0.0<= … <=359.9 0.0°  
0287 Voltage balancing factor of Line3   0.500<= … <=2.000 1.000 Single busbar with 3-CB
0288 Voltage angle adjustment of Line3   0.0<= … <=359.9 0.0° Single busbar with 3-CB
8900 Busbar live voltage threshold   0.550<= … <=0.900 0.700 U/Un  
8901 Busbar dead voltage threshold   0.100<= … <=0.450 0.300 U/Un  
8902 Line live voltage threshold   0.550<= … <=0.900 0.700 U/Un  
8903 Line dead voltage threshold   0.100<= … <=0.450 0.300 U/Un  
8904 Line dead current threshold   0.05<= … <=0.50 0.10 I/In  
Power System Data 1-> Function
0221 High speed busbar transfer   ON
OFF
ON  
0226 Protection functions   ON
OFF
ON Sectionalized single busbar
Power System Data 1-> VT’s
0231 VT rated primary voltage Line1   0.15<= … <=1200.0 6.3 KV  
0232 VT rated secondary voltage Line1   80<= … <=125 100 V  
0233 VT rated primary voltage Line2   0.15<= … <=1200.0 6.3 KV  
0234 VT rated secondary voltage Line2   80<= … <=125 100 V  
0241 VT rated primary voltage Line3   0.15<= … <=1200.0 6.3 KV Single busbar with 3-CB
0242 VT rated secondary voltage Line3   80<= … <=125 100 V Single busbar with 3-CB
0235 VT rated primary voltage Busbar   0.15<= … <=1200.0 6.3 KV  
0236 VT rated secondary voltage Busbar   80<= … <=125 100 V  
Power System Data 1->CT’s
0251 CT rated primary current Line1   100<=…<=20000 3000 A  
0252 CT rated secondary current Line1   1 A
5 A
1 A  
0253 CT rated primary current Line2   100<=…<=20000 3000 A  
0254 CT rated secondary current Line2   1 A
5 A
1 A  
0259 CT rated primary current Line3   100<=…<=20000 3000A Single busbar with 3-CB
0260 CT rated secondary current Line3   1 A
5 A
1 A Single busbar with 3-CB
0255 CT rated primary current Busbar   100<=…<=20000 3000 A Sectionalized single busbar
0256 CT rated secondary current Busbar   1 A
5 A
1 A Sectionalized single busbar
0257A Earth CT rated primary current Busbar   100<=…<=20000 3000 A Sectionalized single busbar
0258A Earth CT rated secondary current Busbar   1 A
5 A
1 A Sectionalized single busbar
Power System Data 1->CB
0261 Minimum TRIP command dura- tion   0.01<=…<=10.00 0.20 sec  
0262 Minimum CLOSE command duration   0.01<=…<=10.00 0.20 sec  

Single Busbar with 2-CB

Addr. Parameter C Range Default Setting Note
HSBT->General
8801 CB1 closing time   20<=…<=150 70 ms  
8802 CB2 closing time   20<=…<=150 70 ms  
8804 Maximum permitted HSBT operating Time   10<=…<=60 20 sec  
8805 Switching direction Line1->Line2   ON
OFF
OFF  
8806 Switching direction Line2->Line1   ON
OFF
OFF  
8811 Line1->Line2 LVLSH permitted   YES
NO
NO  
8812 Line2->Line1 LVLSH permitted   YES
NO
NO  
8817 Manually reset   YES
NO
NO  
8818 Time delay to readiness   5<=…<=60 10 sec  
8819 Time delay to un-readiness   10<=…<=60 10 sec  
8820 HSBT test mode   ON
OFF
OFF  
8837 Fault Detection Ubus   ON
OFF
ON  
8838 Motor Start Detection Ubus   ON
OFF
ON  
HSBT->Start Condition
8821 NORMAL   OFF
PARALLEL Auto
PARAL. Half-Auto
SIMULTANEOUS
SEQUENTIAL
PARALLEL Auto  
8822 FAULT start type A   OFF
SIMULTANEOUS
SEQUENTIAL
SEQUENTIAL  
8898 FAULT start type B   OFF
SIMULTANEOUS
SEQUENTIAL
SIMULTANEOUS  
8823 Under-voltage   OFF
SIMULTANEOUS
SEQUENTIAL
SIMULTANEOUS  
8826 Under-voltage threshold   0.200<=…<=0.950 0.880 U/Un  
8827 Under-voltage time Delay   0<= …<=5000 10 ms  
8824 Under-frequency   OFF
SIMULTANEOUS
SEQUENTIAL
SIMULTANEOUS  
8829 Under-frequency threshold   45.00<=…<=49.50 47.50 Hz fn = 50 Hz
8829 Under-frequency threshold   55.00<=…<=59.50 57.00 Hz fn = 60 Hz
8830 Under-frequency time Delay   0<=…<=1000 10 ms  
8832 Reverse power   OFF
SIMULTANEOUS
SEQUENTIAL
OFF  
8833 Reverse power time delay   0<=…<=1000 10 ms  
8834 Change rate of frequency   OFF
SIMULTANEOUS
SEQUENTIAL
OFF  
8835 Change rate of frequency threshold   -10.0<=…<=-0.5 -0.5 Hz/s  
8836 Change rate of frequency time delay   0<=…<=1000 10 ms  
8825 Inadvertent CB Open   OFF
ON
ON  
8831 Mono-direction against NORMAL   YES
NO
NO  
HSBT->Transfer Mode
8841 FAST   OFF
ON
ON  
8842 REAL-TIME FAST   OFF
ON
ON  
8843. IN-PHASE   OFF
ON
ON  
8844 RES-VOLT   OFF
ON
ON  
8845 LONG-TIME   OFF
ON
ON  
HSBT-->Transfer Set
8851 PARALLEL sequence: delta frequency   0.02<=…<=2.00 0.10 Hz  
8852 PARALLEL sequence: delta U   1.0<=…<=40.0 2.0 V  
8853 PARALLEL sequence: delta phase angle   2.0<=…<=80.0 10.0 °  
8854 PARALLEL Auto: CB open time delay   0.00<=…<=2.00 0.10 sec  
8857 SIMULTANEOUS sequence: CB close time delay   0<=…<=40 0 ms  
8873 SIMULTANEOUS sequence: CB open time delay   0<=…<=40 0 ms  
8858 FAST mode: delta frequency   0.50<=…<=5.00 3.00 Hz  
8859 FAST mode: delta phase angle   10.0<=…<=50.0 20.0 °  
8860 FAST mode: under-voltage block   0.500<=…<=0.900 0.700 U/Un  
8861 REAL-TIME FAST mode: delta frequency   1.00<=…<=15.00 3.00 Hz  
8862 REAL-TIME FAST mode: Udiff/f   1.00<=…<=1.33 1.33 p.u.  
8863 REAL-TIME FAST mode: delta phase angle   70.0<=…<=90.0 90.0 °  
8864 REAL-TIME FAST mode: under-voltage block   0.500<=…<=0.900 0.700 U/Un  
8868 IN-PHASE mode: delta frequency   1.00<=…<=15.00 5.00 Hz  
8869 IN-PHASE mode: delta phase angle   0.5<=…<=20.0 5.0 °  
8870 IN-PHASE mode: under-voltage block   0.200<=…<=0.800 0.400 U/Un  
8871 RES-VOLT mode: threshold   0.200<=…<=0.600 0.300 U/Un  
8872 LONG-TIME mode: threshold   0.50<=…<=10.00 3.00 sec  

Sectionalized Single Busbar with 3-CB

Addr. Parameter C Range Default Setting Note
HSBT->General
8801 CB1 Closing Time   20<=…<=150 70 ms  
8802 CB2 Closing Time   20<=…<=150 70 ms  
8803 CB3 Closing Time   20<=…<=150 70 ms  
8804 Maximum permitted HSBT operating time   10<=…<=60 20 sec  
8805 Switching direction Line1->Line2   ON
OFF
OFF  
8806 Switching direction Line2->Line1   ON
OFF
OFF  
8807 Switching direction Busbar1->Busbar2   ON
OFF
OFF  
8808 Switching direction Busbar1->Line1   ON
OFF
OFF  
8809 Switching direction Busbar2->Busbar1   ON
OFF
OFF  
8810 Switching direction Busbar2->Line2   ON
OFF
OFF  
8811 Line1->Line2 LVLSH permitted   YES
NO
NO  
8812 Line2->Line1 LVLSH permitted   YES
NO
NO  
8813 Busbar1->Busbar2 LVLSH permitted   YES
NO
NO  
8814 Busbar2->Busbar1 LVLSH permitted   YES
NO
NO  
8815 Busbar1->Line1 LVLSH permitted   YES
NO
NO  
8816 Busbar2->Line2 LVLSH permitted   YES
NO
NO  
8817 Manually reset   YES
NO
NO  
8818 Time delay to readiness   5<=…<=60 10 sec  
8819 Time delay to un-readiness   10<=…<=60 10 sec  
8820 HSBT test mode   ON
OFF
OFF  
8837 Fault Detection Ubus   ON
OFF
ON  
8838 Motor Start Detection Ubus   ON
OFF
ON  
HSBT->Start Condition
8821 NORMAL   OFF
PARALLEL Auto
PARAL. Half-Auto
SIMULTANEOUS
SEQUENTIAL
PARALLEL Auto  
8822 FAULT start type A   OFF
SIMULTANEOUS
SEQUENTIAL
SEQUENTIAL  
8898 FAULT start type B   OFF
SIMULTANEOUS
SEQUENTIAL
SIMULTANEOUS  
8823 Under-voltage   OFF
SIMULTANEOUS
SEQUENTIAL
SIMULTANEOUS  
8826 Under-voltage threshold   0.200<=…<=0.950 0.880 U/Un  
8827 Under-voltage time delay   0<= …<=5000 10 ms  
8824 Under-frequency   OFF
SIMULTANEOUS
SEQUENTIAL
SIMULTANEOUS  
8829 Under-frequency threshold   45.00<=…<=49.50 47.50 Hz fn = 50 Hz
8829 Under-frequency threshold   55.00<=…<=59.50 57.00 Hz fn = 60 Hz
8830 Under-frequency time delay   0<= …<=1000 10 ms  
8832 Reverse power   OFF
SIMULTANEOUS
SEQUENTIAL
OFF  
8833 Reverse power time delay   0<=…<=1000 10 ms  
8834 Change rate of frequency   OFF
SIMULTANEOUS
SEQUENTIAL
OFF  
8835 Change rate of frequency threshold   -10.0<=…<=-0.5 -0.5 Hz/s  
8836 Change rate of frequency time delay   0<= …<=1000 10 ms  
8825 Inadvertent CB open   OFF
ON
ON  
8831 Mono-direction against NORMAL   YES
NO
NO  
HSBT->Transfer Mode
8841 FAST   OFF
ON
ON  
8842 REAL-TIME FAST   OFF
ON
ON  
8843 IN-PHASE   OFF
ON
ON  
8844 RES-VOLT   OFF
ON
ON  
8845 LONG-TIME   OFF
ON
ON  
HSBT-->Transfer Set
8851 PARALLEL sequence: delta frequency   0.02<=…<=2.00 0.10 Hz  
8852 PARALLEL sequence: delta U   1.0<=…<=40.0 2.0 V  
8853 PARALLEL sequence: delta phase angle   2.0<=…<=80.0 10.0 °  
8854 PARALLEL Auto: CB open time delay   0.00<=…<=2.00 0.10 sec  
8857 SIMULTANEOUS sequence: CB close time delay   0<=…<=40 0 ms  
8873 SIMULTANEOUS sequence: CB open time delay   0<=…<=40 0 ms  
8858 FAST mode: delta frequency   0.50<=…<=5.00 3.00 Hz  
8859 FAST mode: delta phase angle   10.0<=…<=50.0 20.0 °  
8860 FAST mode: under-voltage block   0.500<=…<=0.900 0.700 U/Un  
8861 REAL-TIME FAST mode: delta frequency   1.00<=…<=15.00 3.00 Hz  
8862 REAL-TIME FAST mode: Udiff/f   1.00<=…<=1.33 1.33 p.u.  
8863 REAL-TIME FAST mode: delta phase angle   70.0<=…<=90.0 90.0 °  
8864 REAL-TIME FAST mode: under-voltage block   0.500<=…<=0.900 0.700 U/Un  
8868 IN-PHASE mode: delta frequency   1.00<=…<=15.00 5.00 Hz  
8869 IN-PHASE mode: delta phase angle   0.5<=…<=20.0 5.0 °  
8870 IN-PHASE mode: under-voltage block   0.200<=…<=0.800 0.400 U/Un  
8871 RES-VOLT mode: threshold   0.200<=…<=0.600 0.300 U/Un  
8872 LONG-TIME mode: threshold   0.50<=…<=10.00 3.00 sec  

Single Busbar with 3-CB

Addr. Parameter C Range Default Setting Note
HSBT->General
8801 CB1 closing time   20<=…<=150 70 ms  
8802 CB2 closing time   20<=…<=150 70 ms  
8803 CB3 closing time   20<=…<=150 70 ms  
8804 Maximum permitted HSBT operating Time   10<=…<=60 20 sec  
8805 Switching direction Line1->Line2   ON OFF OFF  
8806 Switching direction Line2->Line1   ON OFF OFF  
8890 Switching direction Line1->Line3   ON OFF OFF  
8891 Switching direction Line3->Line1   ON OFF OFF  
8892 Switching direction Line2->Line3   ON OFF OFF  
8893 Switching direction Line3 ->Line2   ON OFF OFF  
8811 Line1->Line2 LVLSH permitted   YES NO NO  
8812 Line2->Line1 LVLSH permitted   YES NO NO  
8894 Line1->Line3 LVLSH permitted   YES NO NO  
8895 Line3->Line1 LVLSH permitted   YES NO NO  
8896 Line2->Line3 LVLSH permitted   YES NO NO  
8897 Line3 ->Line2 LVLSH permitted   YES NO NO  
8817 Manually reset   YES NO NO  
8818 Time delay to readiness   5<=…<=60 10 sec  
8819 Time delay to un-readiness   10<=…<=60 10 sec  
8820 HSBT test mode   ON OFF OFF  
8837 Fault Detection Ubus   ON OFF ON  
8838 Motor Start Detection Ubus   ON OFF ON  
HSBT->Start Condition
8821 NORMAL   OFF
PARALLEL Auto
PARAL. Half-Auto SIMULTANEOUS SEQUENTIAL
PARALLEL Auto  
8822 FAULT start type A   OFF SIMULTANEOUS SEQUENTIAL SEQUENTIAL  
8898 FAULT start type B   OFF SIMULTANEOUS SEQUENTIAL SIMULTANEOUS  
8823 Under-voltage   OFF SIMULTANEOUS SEQUENTIAL SIMULTANEOUS  
8826 Under-voltage threshold   0.200<=…<=0.950 0.880 U/Un  
8827 Under-voltage time delay   0<= …<=5000 10 ms  
8824 Under-frequency   OFF SIMULTANEOUS SEQUENTIAL SIMULTANEOUS  
8829 Under-frequency threshold   45.00<=…<=49.50 47.50 Hz fn = 50 Hz
8829 Under-frequency threshold   55.00<=…<=59.50 57.00 Hz fn = 60 Hz
8830 Under-frequency time delay   0<= …<=1000 10 ms  
8832 Reverse power   OFF SIMULTANEOUS SEQUENTIAL OFF  
8833 Reverse power time delay   0<= …<=1000 10 ms  
8834 Change rate of frequency   OFF SIMULTANEOUS SEQUENTIAL OFF  
8835 Change rate of frequency threshold   -10.0<=…<=-0.5 -0.5 Hz/s  
8836 Change rate of frequency time delay   0<= …<=1000 10 ms  
8825 Inadvertent CB open   OFF ON ON  
8831 Mono-direction against NORMAL   YES NO NO  
HSBT->Transfer Mode
8841 FAST   OFF ON ON  
8842 REAL-TIME FAST   OFF ON ON  
8843 IN-PHASE   OFF ON ON  
8844 RES-VOLT   OFF ON ON  
8845 LONG-TIME   OFF ON ON  
HSBT-->Transfer Set
8851 PARALLEL sequence: delta frequency   0.02<=…<=2.00 0.10 Hz  
8852 PARALLEL sequence: delta U   1.0<=…<=40.0 2.0 V  
8853 PARALLEL sequence: delta phase angle   2.0<=…<=80.0 10.0 °  
8854 PARALLEL Auto: CB open time delay   0.00<=…<=2.00 0.10 sec  
8857 SIMULTANEOUS sequence: CB close time delay   0<=…<=40 0 ms  
8873 SIMULTANEOUS sequence: CB open time delay   0<=…<=40 0 ms  
8858 FAST mode: delta frequency   0.50<=…5.00 3.00 Hz  
8859 FAST mode: delta phase angle   10.0<=…<=50.0 20.0 °  
8860 FAST mode: under-voltage block   0.500<=…<=0.900 0.700 U/Un  
8861 REAL-TIME FAST mode: delta frequency   1.00<=…<=15.00 3.00 Hz  
8862 REAL-TIME FAST mode: Udiff/f   1.00<=…<=1.33 1.33 p.u.  
8863 REAL-TIME FAST mode: delta phase angle   70.0<=…<=90.0 90.0 °  
8864 REAL-TIME FAST mode: under-voltage block   0.500<=…<=0.900 0.700 U/Un  
8868 IN-PHASE mode: delta frequency   1.00<=…<=15.00 5.00 Hz  
8869 IN-PHASE mode: phase angle   0.5<=…<=20.0 5.0 °  
8870 IN-PHASE mode: under-voltage block   0.200<=…<=0.800 0.400 U/Un  
8871 RES-VOLT mode: threshold   0.200<=…<=0.600 0.300 U/Un  
8872 LONG-TIME mode: threshold   0.50<=…<=10.00 3.00 sec  

Phase OverCurrent Protection

Addr. Parameter C Range Default Setting Note
Protection Functions->General
9000 Phase over-current protection   ON
OFF
OFF  
Protection Functions -> Voltage Control
9002 Ph-ph under-voltage threshold   1.0<=…<=125.0, 0 70.0 V  
9003 U2 over-voltage threshold   1.0<=…<=125.0, ∞ 8.0 V  
Protection Functions -> Phase O/C
9001 Compound voltage control   YES
NO
YES  
9004 Phase over-current I>threshold   0.10<=…<=35.00 3.00 A  
9005 Phase over-current I> time delay   0.00<=…<=60.00, ∞ 0.50 s  
9006 Phase over-current I>>threshold   0.10<=…<=35.00 5.00 A  
9007 Phase over-current I>> time delay   0.00<=…<=60.00, ∞ 0.10 s  

Ground Overcurrent Protection

Addr. Parameter C Range Default Setting Note
Protection Functions-> General
9010 Earth over-current protection   ON
OFF
OFF  
9018 3I0/IE assignment   IE 3I0 3I0  
Protection Functions -> Voltage Control
9012 3U0 over-voltage threshold   1<=…<=200 30 V  
Protection Functions -> Earth O/C
9011 3U0 Control   Yes
No
Yes  
9013 Earth over-current le > threshold   0.10<=…<=35.00 3.00 A  
9014 Earth over-current le > time delay   0.00<=…<=60.00, 0.50 s  
9015 Earth over-current le >> threshold   0.10<=…<=35.00 5.00 A  
9016 Earth over-current le >> time delay   0.00<=…<=60.00, 0.10 s  

Phase OverCurrent Protection against Switch-Onto-Fault

Addr. Parameter C Range Default Setting Note
Protection Functions -> General
9020 Phase O/C switch-onto-fault protection   ON
OFF
OFF  
9019A Active time for switch-onto-fault protection   0.01<=…<=600.00 5.00 s  
Protection Functions -> Voltage Control
9002 Ph-ph under-voltage threshold   1.0<=…<=125.0, 0 70.0 V  
9003 U2 over-voltage threshold   1.0<=…<=125.0,∞ 8.0 V  
Protection Functions -> Ph. O/C SOF
9021 Compound voltage control   Yes
No
No  
9024 Phase O/C I> switch-onto-fault threshold   0.10<=…<=35.00 2.00 A  
9025 Phase O/C I>switch-onto-fault time delay   0.00<=…<=60.00, 0.50 s  
9026 Phase O/C I>>switch-onto-fault threshold   0.10<=…<=35.00 4.00 A  
9027 Phase O/C I>>switch-onto-fault time delay   0.00<=…<=60.00, 0.10 s  

Ground OverCurrent Protection against Switch-Onto-Fault

Addr. Parameter C Range Default Setting Note
Protection Functions -> General
9030 Earth O/C switch-onto-fault protection   ON
OFF
OFF  
9018 3I0/IE assignment   IE
3I0
3I0  
9019A Active time for switch-onto-fault protection   0.01<=…<=600.00 5.00 s  
Protection Functions -> Voltage Control
9012 3U0 over-voltage threshold   1<=…<=200 30 V  
Protection Functions -> Earth O/C SOF
9031 3U0 Control   Yes
No
Yes  
9033 Earth O/C le >switch-onto-fault threshold   0.10<=…<=35.00 2.00 A  
9034 Earth O/C le >switch-onto-fault time-delay   0.00<=…<=60.00, ∞ 0.50 s  
9035 Earth O/C le >> switch-onto-fault threshold   0.10<=…<=35.00 4.00 A  
9036 Earth O/C le >>switch-onto-fault time-delay   0.00<=…<=60.00, ∞ 0.10 s  

VT Broken Wire Supervision

Addr. Parameter C Range Default Setting Note
Supervision
9101 VT Broken Wire   ON
OFF
OFF  

Bus Voltage Sequence Supervision

Addr. Parameter C Range Default Setting Note
Supervision
9102 Phase Sequence Busbar Voltage   ON
OFF
OFF  