Siemens / SIPROTEC 7VK61 V4.7 setting parameters & highlights (SI4015)

Table of Contents

Overview

The SIPROTEC 7VK61 is a highly flexible autoreclosure, synchro-check and circuitbreaker failure protection unit. This unit is used for the single and threepole auto-reclosure of a circuit-breaker, after this circuit-breaker has tripped due to a fault. The synchro-check function ensures that the two circuits being reconnected by closing the circuit-breaker are within a defined safe operating state before the CLOSE command is issued.

For more detailed information on “SIPROTEC 7VK61 V4.7” relays, refer to SIPROTEC 4 devices manuals.

To see other supported devices, click here.


Functional Scope

Addr. Parameter C Setting Options Default Setting Comments
103 Grp Chge OPTION   Disabled
Enabled
Disabled Setting Group Change Option
106 VT CONNECTION   3phase
1phase
NO
3phase Voltage transformer connection
107 CT CONNECTION   YES
NO
YES Current transformer connection
110 Trip mode   3pole only
1-/3pole
3pole only Trip mode
126 Back-Up O/C   Disabled
TOC IEC
TOC ANSI
TOC IEC /w 3ST
Disabled Backup overcurrent
133 Auto Reclose   1 AR-cycle
2 AR-cycles
3 AR-cycles
4 AR-cycles
5 AR-cycles
6 AR-cycles
7 AR-cycles
8 AR-cycles
ADT
Disabled
Disabled Auto-Reclose Function
134 AR control mode   Pickup w/ Tact
Pickup w/o Tact
Trip w/ Tact
Trip w/o Tact
Trip w/ Tact Auto-Reclose control mode
135 Synchro-Check   Disabled
Enabled
Disabled Synchronism and Voltage Check
137 U/O VOLTAGE   Disabled
Enabled
Disabled Under / Overvoltage Protection
139 BREAKER FAILURE   Disabled
Enabled
enabled w/ 3I0>
Disabled Breaker Failure Protection
140 Trip Cir. Sup.   Disabled
1 trip circuit
2 trip circuits
3 trip circuits
Disabled Trip Circuit Supervision

Device

Addr. Parameter C Setting Options Default Setting Comments
610 FltDisp.LED/LCD   Target on PU
Target on TRIP
Target on PU Fault Display on LED / LCD
625A T MIN LED HOLD   0 .. 60 min 0 min Minimum hold time of latched LEDs
640 Start image DD   image 1
image 2
image 3
image 4
image 5
image 6
image 1 Start image Default Display

Power System Data 1

Addr. Parameter C Setting Options Default Setting Comments
201 CT Starpoint   towards Line
towards Busbar
towards Line CT Starpoint
203 Unom PRIMARY   1.0 .. 1200.0 kV 400.0 kV Rated Primary Voltage
204 Unom SECONDARY   80 .. 125 V 100 V Rated Secondary Voltage (Ph-Ph)
205 CT PRIMARY   10 .. 5000 A 1000 A CT Rated Primary Current
206 CT SECONDARY   1A
5A
1A CT Rated Secondary Current
207 SystemStarpoint   Solid Earthed
Peterson-Coil
Isolated
Solid Earthed System Starpoint is
210 U4 transformer   Not connected
Udelta transf.
Usy2 transf.
Ux transformer
Not connected U4 voltage transformer is
211 Uph / Udelta   0.10 .. 9.99 1.73 Matching ratio Phase-VT To Open- Delta-VT
212 Usy2 connection   L1-E
L2-E
L3-E
L1-L2
L2-L3
L3-L1
L1-L2 VT connection for Usy2
214A φ Usy2-Usy1   0 .. 360 ° 0 ° Angle adjustment Usy2-Usy1
215 Usy1/Usy2 ratio   0.50 .. 2.00 1.00 Matching ratio Usy1 / Usy2
220 I4 transformer   Not connected
In prot. line
In prot. line I4 current transformer is
221 I4/Iph CT   0.010 .. 5.000 1.000 Matching ratio I4/Iph for CT’s
230 Rated Frequency   50 Hz
60 Hz
50 Hz Rated Frequency
235 PHASE SEQ.   L1 L2 L3
L1 L3 L2
L1 L2 L3 Phase Sequence
239 T-CB close   0.01 .. 0.60 sec 0.06 sec Closing (operating) time of CB
240A TMin TRIP CMD   0.02 .. 30.00 sec 0.10 sec Minimum TRIP Command Duration
241A TMax CLOSE CMD   0.01 .. 30.00 sec 0.10 sec Maximum Close Command Dura- tion
242 T-CBtest-dead   0.00 .. 30.00 sec 0.10 sec Dead Time for CB test-autoreclo- sure

Change Group

Addr. Parameter C Setting Options Default Setting Comments
302 CHANGE   Group A
Group B
Group C
Group D
Binary Input
Protocol
Group A Change to Another Setting Group

Power System Data 2

Addr. Parameter C Setting Options Default Setting Comments
1103 FullScaleVolt.   1.0 .. 1200.0 kV 400.0 kV Measurement: Full Scale Voltage (100%)
1104 FullScaleCurr.   10 .. 5000 A 1000 A Measurement: Full Scale Current (100%)
1107 P,Q sign   not reversed
reversed
not reversed P,Q operational measured values sign
1130A PoleOpenCurrent 1A 0.05 .. 1.00 A 0.10 A Pole Open Current Threshold
5A 0.25 .. 5.00 A 0.50 A
1131A PoleOpenVoltage   2 .. 70 V 30 V Pole Open Voltage Threshold
1135 Reset Trip CMD   CurrentOpenPole
Current AND CB Pickup
Reset
CurrentOpenPole RESET of Trip Command
1136 OpenPoleDetect.   OFF
Current AND CB
w/ measurement
w/ measurement open pole detector
1150A SI Time Man.Cl   0.01 .. 30.00 sec 0.30 sec Seal-in Time after MANUAL closures
1151 MAN. CLOSE   with Sync-check
w/o Sync-check NO
NO Manual CLOSE COMMAND
generation
1152 Man.Clos. Imp.   (Einstellmoglichkeiten anwendungsabhangig) none MANUAL Closure Impulse after CONTROL

Oscillographic Fault Records

Addr. Parameter C Setting Options Default Setting Comments
402A WAVEFORMTRIGGER   Save w. Pickup
Save w. TRIP
Start w. TRIP
Save w. Pickup Waveform Capture
403A WAVEFORM DATA   Fault event
Pow.Sys.Flt.
Fault event Scope of Waveform Data
410 MAX. LENGTH   0.30 .. 5.00 sec 2.00 sec Max. length of a Waveform Capture Record
411 PRE. TRIG. TIME   0.05 .. 0.50 sec 0.25 sec Captured Waveform Prior to Trigger
412 POST REC. TIME   0.05 .. 0.50 sec 0.10 sec Captured Waveform after Event
415 BinIn CAPT.TIME   0.10 .. 5.00 sec 0.50 sec Capture Time via Binary Input

Automatic reclosure function (optional)

Addr. Parameter C Setting Options Default Setting Comments
3401 AUTO RECLOSE   OFF
ON
ON Auto-Reclose function
3402 CB? 1.TRIP   YES
NO
NO CB ready interrogation at 1st trip
3403 T-RECLAIM   0.50 .. 300.00 sec 3.00 sec Reclaim time after successful AR cycle
3404 T-BLOCK MC   0.50 .. 300.00 sec 1.00 sec AR blocking duration after manual close
3406 EV. FLT. RECOG.   with PICKUP
with TRIP
with TRIP Evolving fault recognition
3407 EV. FLT. MODE   blocks AR
starts 3p AR
starts 3p AR Evolving fault (during the dead time)
3408 T-Start MONITOR   0.01 .. 300.00 sec 0.20 sec AR start-signal monitoring time
3409 CB TIME OUT   0.01 .. 300.00 sec 3.00 sec Circuit Breaker (CB) Supervision Time
3410 T RemoteClose   0.00 .. 300.00 sec 2147483647 sec Send delay for remote close command
3411A T-DEAD EXT.   0.50 .. 300.00 sec 2147483647 sec Maximum dead time extension
3425 AR w/ BackUpO/C   YES
NO
YES AR with back-up overcurrent
3430 AR TRIP 3pole   YES
NO
YES 3pole TRIP by AR
3431 DLC or RDT   WITHOUT
RDT
DLC
WITHOUT Dead Line Check or Reduced Dead Time
3433 T-ACTION ADT   0.01 .. 300.00 sec 0.20 sec Action time
3434 T-MAX ADT   0.50 .. 3000.00 sec 5.00 sec Maximum dead time
3435 ADT 1p allowed   YES
NO
NO 1pole TRIP allowed
3436 ADT CB? CLOSE   YES
NO
NO CB ready interrogation before reclosing
3437 ADT SynRequest   YES
NO
NO Request for synchro-check after 3pole AR
3438 T U-stable   0.10 .. 30.00 sec 0.10 sec Supervision time for dead/ live voltage
3440 U-live>   30 .. 90 V 48 V Voltage threshold for live line or bus
3441 U-dead<   2 .. 70 V 30 V Voltage threshold for dead line or bus
3450 1.AR: START   YES
NO
YES Start of AR allowed in this cycle
3451 1.AR: T-ACTION   0.01 .. 300.00 sec 0.20 sec Action time
3453 1.AR Tdead 1Flt   0.01 .. 1800.00 sec 1.20 sec Dead time after 1phase faults
3454 1.AR Tdead 2Flt   0.01 .. 1800.00 sec 1.20 sec Dead time after 2phase faults
3455 1.AR Tdead 3Flt   0.01 .. 1800.00 sec 0.50 sec Dead time after 3phase faults
3456 1.AR Tdead1Trip   0.01 .. 1800.00 sec 1.20 sec Dead time after 1pole trip
3457 1.AR Tdead3Trip   0.01 .. 1800.00 sec 0.50 sec Dead time after 3pole trip
3458 1.AR: Tdead EV.   0.01 .. 1800.00 sec 1.20 sec Dead time after evolving fault
3459 1.AR: CB? CLOSE   YES
NO
NO CB ready interrogation before reclosing
3460 1.AR SynRequest   YES
NO
NO Request for synchro-check after 3pole AR
3461 2.AR: START   YES
NO
NO AR start allowed in this cycle
3462 2.AR: T-ACTION   0.01 .. 300.00 sec 0.20 sec Action time
3464 2.AR Tdead 1Flt   0.01 .. 1800.00 sec 1.20 sec Dead time after 1phase faults
3465 2.AR Tdead 2Flt   0.01 .. 1800.00 sec 1.20 sec Dead time after 2phase faults
3466 2.AR Tdead 3Flt   0.01 .. 1800.00 sec 0.50 sec Dead time after 3phase faults
3467 2.AR Tdead1Trip   0.01 .. 1800.00 sec 2147483647 sec Dead time after 1pole trip
3468 2.AR Tdead3Trip   0.01 .. 1800.00 sec 0.50 sec Dead time after 3pole trip
3469 2.AR: Tdead EV.   0.01 .. 1800.00 sec 1.20 sec Dead time after evolving fault
3470 2.AR: CB? CLOSE   YES
NO
NO CB ready interrogation before reclosing
3471 2.AR SynRequest   YES
NO
NO Request for synchro-check after 3pole AR
3472 3.AR: START   YES
NO
NO AR start allowed in this cycle
3473 3.AR: T-ACTION   0.01 .. 300.00 sec 0.20 sec Action time
3475 3.AR Tdead 1Flt   0.01 .. 1800.00 sec 1.20 sec Dead time after 1phase faults
3476 3.AR Tdead 2Flt   0.01 .. 1800.00 sec 1.20 sec Dead time after 2phase faults
3477 3.AR Tdead 3Flt   0.01 .. 1800.00 sec 0.50 sec Dead time after 3phase faults
3478 3.AR Tdead1Trip   0.01 .. 1800.00 sec 2147483647 sec Dead time after 1pole trip
3479 3.AR Tdead3Trip   0.01 .. 1800.00 sec 0.50 sec Dead time after 3pole trip
3480 3.AR: Tdead EV.   0.01 .. 1800.00 sec 1.20 sec Dead time after evolving fault
3481 3.AR: CB? CLOSE   YES
NO
NO CB ready interrogation before reclosing
3482 3.AR SynRequest   YES
NO
NO Request for synchro-check after 3pole AR
3483 4.AR: START   YES
NO
NO AR start allowed in this cycle
3484 4.AR: T-ACTION   0.01 .. 300.00 sec 0.20 sec Action time
3486 4.AR Tdead 1Flt   0.01 .. 1800.00 sec 1.20 sec Dead time after 1phase faults
3487 4.AR Tdead 2Flt   0.01 .. 1800.00 sec 1.20 sec Dead time after 2phase faults
3488 4.AR Tdead 3Flt   0.01 .. 1800.00 sec 0.50 sec Dead time after 3phase faults
3489 4.AR Tdead1Trip   0.01 .. 1800.00 sec 2147483647 sec Dead time after 1pole trip
3490 4.AR Tdead3Trip   0.01 .. 1800.00 sec 0.50 sec Dead time after 3pole trip
3491 4.AR: Tdead EV.   0.01 .. 1800.00 sec 1.20 sec Dead time after evolving fault
3492 4.AR: CB? CLOSE   YES
NO
NO CB ready interrogation before reclosing
3493 4.AR SynRequest   YES
NO
NO Request for synchro-check after 3pole AR

Overcurrent protection (optional)

Addr. Parameter C Setting Options Default Setting Comments
2601 Operating Mode   ON
OFF
ON Operating mode
2610 Iph>> 1A 0.05 .. 50.00 A 2.00 A Iph>> Pickup
5A 0.25 .. 250.00 A 10.00 A
2611 T Iph>>   0.00 .. 30.00 sec 0.30 sec T Iph>> Time delay
2612 3I0>> PICKUP 1A 0.05 .. 25.00 A 0.50 A 3I0>> Pickup
5A 0.25 .. 125.00 A 2.50 A
2613 T 3I0>>   0.00 .. 30.00 sec 2.00 sec T 3I0>> Time delay
2614 I>> InstTrip BI   NO
YES
YES Instantaneous trip via BI
2615 I>> SOTF   NO
YES
NO Instantaneous trip after SwitchOnToFault
2620 Iph> 1A 0.05 .. 50.00 A 1.50 A Iph> Pickup
5A 0.25 .. 250.00 A 7.50 A
2621 T Iph>   0.00 .. 30.00 sec 0.50 sec T Iph> Time delay
2622 3I0> 1A 0.05 .. 25.00 A 0.20 A 3I0> Pickup
5A 0.25 .. 125.00 A 1.00 A
2623 T 3I0>   0.00 .. 30.00 sec 2.00 sec T 3I0> Time delay
2624 I> Telep/BI   NO
YES
NO Instantaneous trip via Tele- prot./BI
2625 I> SOTF   NO
YES
NO Instantaneous trip after SwitchOnToFault
2630 Iph> STUB 1A 0.05 .. 50.00 A 1.50 A Iph> STUB Pickup
5A 0.25 .. 250.00 A 7.50 A
2631 T Iph STUB   0.00 .. 30.00 sec 0.30 sec T Iph STUB Time delay
2632 3I0> STUB 1A 0.05 .. 25.00 A 0.20 A 3I0> STUB Pickup
5A 0.25 .. 125.00 A 1.00 A
2633 T 3I0 STUB   0.00 .. 30.00 sec 2.00 sec T 3I0 STUB Time delay
2634 I-STUB Telep/BI   NO
YES
NO Instantaneous trip via Tele- prot./BI
2635 I-STUB SOTF   NO
YES
NO Instantaneous trip after SwitchOnToFault
2640 Ip> 1A 0.10 .. 4.00 A 2147483647 A Ip> Pickup
5A 0.50 .. 20.00 A 2147483647 A
2642 T Ip Time Dial   0.05 .. 3.00 sec 0.50 sec T Ip Time Dial
2643 Time Dial TD Ip   0.50 .. 15.00 5.00 Time Dial TD Ip
2646 T Ip Add   0.00 .. 30.00 sec 0.00 sec T Ip Additional Time Delay
2650 3I0p PICKUP 1A 0.05 .. 4.00 A 2147483647 A 3I0p Pickup
5A 0.25 .. 20.00 A 2147483647 A
2652 T 3I0p TimeDial   0.05 .. 3.00 sec 0.50 sec T 3I0p Time Dial
2653 TimeDial TD3I0p   0.50 .. 15.00 5.00 Time Dial TD 3I0p
2656 T 3I0p Add   0.00 .. 30.00 sec 0.00 sec T 3I0p Additional Time Delay
2660 IEC Curve   Normal Inverse
Very Inverse
Extremely Inv.
LongTimeInverse
Normal Inverse IEC Curve
2661 ANSI Curve   Inverse
Short Inverse
Long Inverse
Moderately Inv.
Very Inverse
Extremely Inv.
Definite Inv.
Inverse ANSI Curve
2670 I(3I0)p Tele/BI   NO
YES
NO Instantaneous trip via Tele- prot./BI
2671 I(3I0)p SOTF   NO
YES
NO Instantaneous trip after SwitchOnToFault
2680 SOTF Time DELAY   0.00 .. 30.00 sec 0.00 sec Trip time delay after SOTF

Synchronism and voltage check (optional)

Addr. Parameter C Setting Options Default Setting Comments
3501 FCT Synchronism   ON
OFF
ON:w/o CloseCmd
ON Synchronism and Voltage Check function
3502 Dead Volt. Thr.   1 .. 100 V 5 V Voltage threshold dead line / bus
3503 Live Volt. Thr.   20 .. 125 V 90 V Voltage threshold live line / bus
3504 Umax   20 .. 140 V 110 V Maximum permissible voltage
3507 T-SYN. DURATION   0.01 .. 600.00 sec 1.00 sec Maximum duration of synchronism-check
3508 T SYNC-STAB   0.00 .. 30.00 sec 0.00 sec Synchronous condition stability timer
3509 SyncCB   (Einstellmoglichkeiten anwendungsabhongig) none Synchronizable circuit breaker
3510 Op.mode with AR   with T-CB close
w/o T-CB close
w/o T-CB close Operating mode with AR
3511 AR maxVolt.Diff   1.0 .. 60.0 V 2.0 V Maximum voltage difference
3512 AR maxFreq.Diff   0.03 .. 2.00 Hz 0.10 Hz Maximum frequency difference
3513 AR maxAngleDiff   2 .. 80 � 10 � Maximum angle difference
3515A AR SYNC-CHECK   YES
NO
YES AR at Usy2>, Usy1>, and Synchr.
3516 AR Usy1<Usy2>   YES
NO
NO AR at Usy1< and Usy2>
3517 AR Usy1>Usy2<   YES
NO
NO AR at Usy1> and Usy2<
3518 AR Usy1<Usy2<   YES
NO
NO AR at Usy1< and Usy2<
3519 AR OVERRIDE   YES
NO
NO Override of any check before AR
3530 Op.mode with MC   with T-CB close
w/o T-CB close
w/o T-CB close Operating mode with Man.Cl
3531 MC maxVolt.Diff   1.0 .. 60.0 V 2.0 V Maximum voltage difference
3532 MC maxFreq.Diff   0.03 .. 2.00 Hz 0.10 Hz Maximum frequency difference
3533 MC maxAngleDiff   2 .. 80 � 10 � Maximum angle difference
3535A MC SYNCHR   YES
NO
YES Manual Close at Usy2>, Usy1>, and Synchr
3536 MC Usy1< Usy2>   YES
NO
NO Manual Close at Usy1< and Usy2>
3537 MC Usy1> Usy2<   YES
NO
NO Manual Close at Usy1> and Usy2<
3538 MC Usy1< Usy2<   YES
NO
NO Manual Close at Usy1< and Usy2<
3539 MC OVERRIDE   YES
NO
NO Override of any check before Man.Cl

Under and over-voltage protection (optional)

Addr. Parameter C Setting Options Default Setting Comments
3701 Uph-e>(>)   OFF
Alarm Only
ON
U>Alarm U>>Trip
OFF Operating mode Uph-e overvoltage prot.
3702 Uph-e>   1.0 .. 170.0 V 85.0 V Uph-e> Pickup
3703 T Uph-e>   0.00 .. 100.00 sec 2.00 sec T Uph-e> Time Delay
3704 Uph-e>>   1.0 .. 170.0 V 100.0 V Uph-e>> Pickup
3705 T Uph-e>>   0.00 .. 100.00 sec 1.00 sec T Uph-e>> Time Delay
3709A Uph-e>(>) RESET   0.30 .. 0.99 0.98 Uph-e>(>) Reset ratio
3711 Uph-ph>(>)   OFF
Alarm Only
ON
U>Alarm U>>Trip
OFF Operating mode Uph-ph overvoltage prot.
3712 Uph-ph>   2.0 .. 220.0 V 150.0 V Uph-ph> Pickup
3713 T Uph-ph>   0.00 .. 100.00 sec 2.00 sec T Uph-ph> Time Delay
3714 Uph-ph>>   2.0 .. 220.0 V 175.0 V Uph-ph>> Pickup
3715 T Uph-ph>>   0.00 .. 100.00 sec 1.00 sec T Uph-ph>> Time Delay
3719A Uphph>(>) RESET   0.30 .. 0.99 0.98 Uph-ph>(>) Reset ratio
3721 3U0>(>) (or Ux)   OFF
Alarm Only
ON
U>Alarm U>>Trip
OFF Operating mode 3U0 (or Ux) over- voltage
3722 3U0>   1.0 .. 220.0 V 30.0 V 3U0> Pickup (or Ux>)
3723 T 3U0>   0.00 .. 100.00 sec 2.00 sec T 3U0> Time Delay (or T Ux>)
3724 3U0>>   1.0 .. 220.0 V 50.0 V 3U0>> Pickup (or Ux>>)
3725 T 3U0>>   0.00 .. 100.00 sec 1.00 sec T 3U0>> Time Delay (or T Ux>>)
3728A 3U0>(>) Stabil.   ON
OFF
ON 3U0>(>): Stabilization 3U0-Meas- urement
3729A 3U0>(>) RESET   0.30 .. 0.99 0.95 3U0>(>) Reset ratio (or Ux)
3731 U1>(>)   OFF
Alarm Only
ON
U>Alarm U>>Trip
OFF Operating mode U1 overvoltage prot.
3732 U1>   2.0 .. 220.0 V 150.0 V U1> Pickup
3733 T U1>   0.00 .. 100.00 sec 2.00 sec T U1> Time Delay
3734 U1>>   2.0 .. 220.0 V 175.0 V U1>> Pickup
3735 T U1>>   0.00 .. 100.00 sec 1.00 sec T U1>> Time Delay
3739A U1>(>) RESET   0.30 .. 0.99 0.98 U1>(>) Reset ratio
3741 U2>(>)   OFF
Alarm Only
ON
U>Alarm U>>Trip
OFF Operating mode U2 overvoltage prot.
3742 U2>   2.0 .. 220.0 V 30.0 V U2> Pickup
3743 T U2>   0.00 .. 100.00 sec 2.00 sec T U2> Time Delay
3744 U2>>   2.0 .. 220.0 V 50.0 V U2>> Pickup
3745 T U2>>   0.00 .. 100.00 sec 1.00 sec T U2>> Time Delay
3749A U2>(>) RESET   0.30 .. 0.99 0.98 U2>(>) Reset ratio
3751 Uph-e<(<)   OFF
Alarm Only
ON
U>Alarm U>>Trip
OFF Operating mode Uph-e under- voltage prot.
3752 Uph-e<   1.0 .. 100.0 V 30.0 V Uph-e< Pickup
3753 T Uph-e<   0.00 .. 100.00 sec 2.00 sec T Uph-e< Time Delay
3754 Uph-e<<   1.0 .. 100.0 V 10.0 V Uph-e<< Pickup
3755 T Uph-e<<   0.00 .. 100.00 sec 1.00 sec T Uph-e<< Time Delay
3758 CURR.SUP. Uphe<   ON
OFF
ON Current supervision (Uph-e)
3759A Uph-e<(<) RESET   1.01 .. 1.20 1.05 Uph-e<(<) Reset ratio
3761 Uph-ph<(<)   OFF
Alarm Only
ON
U>Alarm U>>Trip
OFF Operating mode Uph-ph under- voltage prot.
3762 Uph-ph<   1.0 .. 175.0 V 50.0 V Uph-ph< Pickup
3763 T Uph-ph<   0.00 .. 100.00 sec 2.00 sec T Uph-ph< Time Delay
3764 Uph-ph<<   1.0 .. 175.0 V 17.0 V Uph-ph<< Pickup
3765 T Uphph<<   0.00 .. 100.00 sec 1.00 sec T Uph-ph<< Time Delay
3768 CURR.SUP.Uphph<   ON
OFF
ON Current supervision (Uph-ph)
3769A Uphph<(<) RESET   1.01 .. 1.20 1.05 Uph-ph<(<) Reset ratio
3771 U1<(<)   OFF
Alarm Only
ON
U>Alarm U>>Trip
OFF Operating mode U1 undervoltage prot.
3772 U1<   1.0 .. 100.0 V 30.0 V U1< Pickup
3773 T U1<   0.00 .. 100.00 sec 2.00 sec T U1< Time Delay
3774 U1<<   1.0 .. 100.0 V 10.0 V U1<< Pickup
3775 T U1<<   0.00 .. 100.00 sec 1.00 sec T U1<< Time Delay
3778 CURR.SUP.U1<   ON
OFF
ON Current supervision (U1)
3779A U1<(<) RESET   1.01 .. 1.20 1.05 U1<(<) Reset ratio

Circuit breaker failure protection (optional)

Addr. Parameter C Setting Options Default Setting Comments
3901 FCT BreakerFail   ON
OFF
ON Breaker Failure Protection
3902 I> BF 1A 0.05 .. 20.00 A 0.10 A Pick-up threshold I>
5A 0.25 .. 100.00 A 0.50 A
3903 1p-RETRIP (T1)   NO
YES
YES 1pole retrip with stage T1 (local trip)
3904 T1-1pole   0.00 .. 30.00 sec 0.00 sec T1, Delay after 1pole start (local trip)
3905 T1-3pole   0.00 .. 30.00 sec 0.00 sec T1, Delay after 3pole start (local trip)
3906 T2   0.00 .. 30.00 sec 0.15 sec T2, Delay of 2nd stage (busbar trip)
3907 T3-BkrDefective   0.00 .. 30.00 sec 0.00 sec T3, Delay for start with defective bkr.
3908 Trip BkrDefect.   NO
with T1-trip
with T2-trip
w/ T1/T2-trip
NO Trip output selection with defective bkr
3909 Chk BRK CONTACT   NO
YES
YES Check Breaker contacts
3912 3I0> BF 1A 0.05 .. 20.00 A 0.10 A Pick-up threshold 3I0>
5A 0.25 .. 100.00 A 0.50 A
3913 T2StartCriteria   With exp. of T1
Parallel withT1
Parallel withT1 T2 Start Criteria
3921 End Flt. stage   ON
OFF
OFF End fault protection
3922 T-EndFault   0.00 .. 30.00 sec 2.00 sec Trip delay of end fault protection
3931 PoleDiscrepancy   ON
OFF
OFF Pole Discrepancy supervi- sion
3932 T-PoleDiscrep.   0.00 .. 30.00 sec 2.00 sec Trip delay with pole discrepancy

Measurement Supervision

Addr. Parameter C Setting Options Default Setting Comments
2901 MEASURE. SUPERV   ON
OFF
ON Measurement Supervision
2902A BALANCE U-LIMIT   10 .. 100 V 50 V Voltage Threshold for Balance Monitoring
2903A BAL. FACTOR U   0.58 .. 0.95 0.75 Balance Factor for Voltage Monitor
2904A BALANCE I LIMIT 1A 0.10 .. 1.00 A 0.50 A Current Balance Monitor
5A 0.50 .. 5.00 A 2.50 A
2905A BAL. FACTOR I   0.10 .. 0.95 0.50 Balance Factor for Current Monitor
2906A ΣI THRESHOLD 1A 0.05 .. 2.00 A 0.10 A Summated Current Moni- toring Threshold
5A 0.25 .. 10.00 A 0.50 A
2907A ΣI FACTOR   0.00 .. 0.95 0.10 Summated Current Moni- toring Factor
2908A T BAL. U LIMIT   5 .. 100 sec 5 sec T Balance Factor for Voltage Monitor
2909A T BAL. I LIMIT   5 .. 100 sec 5 sec T Current Balance Monitor
2910 FUSE FAIL MON.   ON
OFF
ON Fuse Failure Monitor
2911A FFM U>(min)   10 .. 100 V 30 V Minimum Voltage Threshold U>
2912A FFM I< (max) 1A 0.10 .. 1.00 A 0.10 A Maximum Current Threshold I<
5A 0.50 .. 5.00 A 0.50 A
2913A FFM U<max (3ph)   2 .. 100 V 15 V Maximum Voltage Threshold U< (3phase)
2914A FFM Idelta (3p) 1A 0.05 .. 1.00 A 0.10 A Delta Current Threshold (3phase)
5A 0.25 .. 5.00 A 0.50 A
2915 V-Supervision   w/ CURR.SUP
w/ I> & CBaux
OFF
w/ CURR.SUP Voltage Failure Supervision
2916A T V-Supervision   0.00 .. 30.00 sec 3.00 sec Delay Voltage Failure Supervision
2941 φA   0 .. 359 ° 200 ° Limit setting PhiA
2942 φB   0 .. 359 ° 340 ° Limit setting PhiB
2943 I1> 1A 0.05 .. 2.00 A 0.05 A Minimum value I1>
5A 0.25 .. 10.00 A 0.25 A
2944 U1>   2 .. 70 V 20 V Minimum value U1>

Trip circuit supervision

Addr. Parameter C Setting Options Default Setting Comments
4001 FCT TripSuperv.   ON
OFF
OFF TRIP Circuit Supervision is
4002 No. of BI   1 .. 2 2 Number of Binary Inputs per trip circuit
4003 Alarm Delay   1 .. 30 sec 2 sec Delay Time for alarm