Overview
The SIPROTEC 7UT6 differential protection relays are used for fast and selective fault clearing of short-circuits in transformers of all voltage levels and in rotating electric machines like motors and generators, for short lines and busbars.
For more detailed information on “SIPROTEC 7UT6x V4.67” relays, refer to SIPROTEC 4 devices manuals.
To see other supported devices, click here.
Analog measuring inputs
for 3-phase protected objects1) | for busbar 1-phase | Voltage 3-phase | Voltage 1-phase | |||||
Current 3-phase1) | Current (auxiliary) | Strom 1-phase | Current (auxiliary) | |||||
1-phase | sensitive2) | 1-phase | sensitive2) | |||||
7UT612 | 2 | 2 | 1 | 7 | 2 | 1 | – | – |
7UT613 | 3 | 3 | 1 | 9 | 3 | 1 | 1 | 1 |
7UT633 | 3 | 3 | 1 | 9 | 3 | 1 | 1 | 1 |
7UT635 | 5 | 1 | 1 | – | – | – | – | – |
4 | 4 | 2 | 12 | 4 | 2 | – | – | |
1) also applicable for single-phase power transformers 2) selectable, contained in the number of 1-phase inputs |
||||||||
Device
Addr. | Parameter | C | Setting Options | Default Setting | Comments |
201 | FltDisp.LED/LCD | Target on PU Target on TRIP |
Target on PU | Fault Display on LED / LCD | |
202 | Spont. FltDisp. | NO YES |
NO | Spontaneous display of flt.annun- ciations | |
204 | Start image DD | image 1 image 2 image 3 image 4 image 5 image 6 image 7 |
image 1 | Start image Default Display | |
Functional Scope
Addr. | Parameter | C | Setting Options | Default Setting | Comments |
103 | Grp Chge OPTION | Disabled Enabled |
Disabled | Setting Group Change Option | |
105 | PROT. OBJECT | 3 phase transf. 1 phase transf. Autotransf. Autotr. node Generator/Motor 3ph Busbar 1ph Busbar |
3 phase transf. | Protection Object | |
112 | DIFF. PROT. | Disabled Enabled |
Enabled | Differential Protection | |
113 | REF PROT. | Disabled Enabled |
Disabled | Restricted earth fault protection | |
114 | REF PROT. 2 | Disabled Enabled |
Disabled | Restricted earth fault protection 2 | |
117 | COLDLOAD PICKUP | Disabled Enabled |
Disabled | Cold Load Pickup | |
120 | DMT/IDMT Phase | Disabled Definite Time TOC IEC TOC ANSI User Defined PU User def. Reset |
Disabled | DMT / IDMT Phase | |
122 | DMT/IDMT 3I0 | Disabled Definite Time TOC IEC TOC ANSI User Defined PU User def. Reset |
Disabled | DMT / IDMT 3I0 | |
124 | DMT/IDMT Earth | Disabled Definite Time TOC IEC TOC ANSI User Defined PU User def. Reset |
Disabled | DMT / IDMT Earth | |
127 | DMT 1PHASE | Disabled Enabled |
Disabled | DMT 1Phase | |
130 | DMT/IDMT Phase2 | Disabled Definite Time TOC IEC TOC ANSI User Defined PU User def. Reset |
Disabled | DMT / IDMT Phase 2 | |
132 | DMT/IDMT Phase3 | Disabled Definite Time TOC IEC TOC ANSI User Defined PU User def. Reset |
Disabled | DMT / IDMT Phase 3 | |
134 | DMT/IDMT 3I0 2 | Disabled Definite Time TOC IEC TOC ANSI User Defined PU User def. Reset |
Disabled | DMT / IDMT 3I0 2 | |
136 | DMT/IDMT 3I0 3 | Disabled Definite Time TOC IEC TOC ANSI User Defined PU User def. Reset |
Disabled | DMT / IDMT 3I0 3 | |
138 | DMT/IDMT Earth2 | Disabled Definite Time TOC IEC TOC ANSI User Defined PU User def. Reset |
Disabled | DMT / IDMT Earth 2 | |
140 | UNBALANCE LOAD | Disabled Definite Time TOC IEC TOC ANSI DT/thermal |
Disabled | Unbalance Load (Negative Sequence) | |
142 | THERM. OVERLOAD | Disabled th rep w.o. sen th repl w. sens IEC354 |
Disabled | Thermal Overload Protection | |
143 | OVEREXC. PROT. | Disabled Enabled |
Disabled | Overexcitation Protection (U/f) | |
144 | THERM.OVERLOAD2 | Disabled th rep w.o. sen th repl w. sens IEC354 |
Disabled | Thermal Overload Protection 2 | |
150 | REVERSE POWER | Disabled Enabled |
Disabled | Reverse Power Protection | |
151 | FORWARD POWER | Disabled Enabled |
Disabled | Forward Power Supervision | |
152 | UNDERVOLTAGE | Disabled Enabled |
Disabled | Undervoltage Protection | |
153 | OVERVOLTAGE | Disabled Enabled |
Disabled | Overvoltage Protection | |
156 | FREQUENCY Prot. | Disabled Enabled |
Disabled | Over / Underfrequency Protection | |
170 | BREAKER FAILURE | Disabled Enabled |
Disabled | Breaker Failure Protection | |
171 | BREAKER FAIL. 2 | Disabled Enabled |
Disabled | Breaker Failure Protection 2 | |
180 | DISCON.MEAS.LOC | Disabled Enabled |
Disabled | Disconnect measurment location | |
181 | M.V. SUPERV | Disabled Enabled |
Enabled | Measured Values Supervision | |
182 | Trip Cir. Sup. | Disabled 2 Binary Inputs 1 Binary Input |
Disabled | Trip Circuit Supervision | |
186 | EXT. TRIP 1 | Disabled Enabled |
Disabled | External Trip Function 1 | |
187 | EXT. TRIP 2 | Disabled Enabled |
Disabled | External Trip Function 2 | |
190 | RTD-BOX INPUT | Disabled Port C Port D |
Disabled | External Temperature Input | |
191 | RTD CONNECTION | 6 RTD simplex 6 RTD HDX 12 RTD HDX |
6 RTD simplex | Ext. Temperature Input Connec- tion Type | |
– | FLEXIBLE FcT. 1…12 | Flexible Function 01 Flexible Function 02 Flexible Function 03 Flexible Function 04 Flexible Function 05 Flexible Function 06 Flexible Function 07 Flexible Function 08 Flexible Function 09 Flexible Function 10 Flexible Function 11 Flexible Function 12 |
Please select | Flexible Functions 1…12 | |
– | ADD MV 1…20 | Add. MV 01 Add. MV 02 Add. MV 03 Add. MV 04 Add. MV 05 Add. MV 06 Add. MV 07 Add. MV 08 Add. MV 09 Add. MV 10 Add. MV 11 Add. MV 12 Add. MV 13 Add. MV 14 Add. MV 15 Add. MV 16 Add. MV 17 Add. MV 18 Add. MV 19 Add. MV 20 |
Please select | Additional Measured Value 1…20 | |
Power System Data 1
Addr. | Parameter | C | Setting Options | Default Setting | Comments |
211 | No Conn.MeasLoc | 2 3 4 5 |
3 | Number of connected Measuring Locations | |
212 | No AssigMeasLoc | 2 3 4 5 |
3 | Number of assigned Measuring Locations | |
213 | NUMBER OF SIDES | 2 3 4 5 |
3 | Number of Sides | |
216 | NUMBER OF ENDS | 3 4 5 6 7 8 9 10 11 12 |
6 | Number of Ends for 1 Phase Busbar | |
220 | ASSIGNM. 2M,2S | M1,M2 | M1,M2 | Assignment at 2 assig.Meas.Loc./ 2 Sides | |
221 | ASSIGNM. 3M,2S | M1+M2,M3 M1,M2+M3 |
M1+M2,M3 | Assignment at 3 assig.Meas.Loc./ 2 Sides | |
222 | ASSIGNM. 3M,3S | M1,M2,M3 | M1,M2,M3 | Assignment at 3 assig.Meas.Loc./ 3 Sides | |
223 | ASSIGNM. 4M,2S | M1+M2,M3+M4 M1+M2+M3,M4 M1,M2+M3+M4 |
M1+M2,M3+M4 | Assignment at 4 assig.Meas.Loc./ 2 Sides | |
224 | ASSIGNM. 4M,3S | M1+M2,M3,M4 M1,M2+M3,M4 M1,M2,M3+M4 |
M1+M2,M3,M4 | Assignment at 4 assig.Meas.Loc./ 3 Sides | |
225 | ASSIGNM. 4M,4S | M1,M2,M3,M4 | M1,M2,M3,M4 | Assignment at 4 assig.Meas.Loc./ 4 Sides | |
226 | ASSIGNM. 5M,2S | M1+M2+M3,M4+M5 M1+M2,M3+M4+M5 M1+M2+M3+M4,M5 M1,M2+M3+M4+M5 | M1+M2+M3,M4+M5 | Assignment at 5 assig.Meas.Loc./ 2 Sides | |
227 | ASSIGNM. 5M,3S | M1+M2,M3+M4,M5 M1+M2,M3,M4+M5 M1,M2+M3,M4+M5 M1+M2+M3,M4,M5 M1,M2+M3+M4,M5 M1,M2,M3+M4+M5 | M1+M2,M3+M4,M5 | Assignment at 5 assig.Meas.Loc./ 3 Sides | |
228 | ASSIGNM. 5M,4S | M1+M2,M3,M4,M5 M1,M2+M3,M4,M5 M1,M2,M3+M4,M5 M1,M2,M3,M4+M5 | M1+M2,M3,M4,M5 | Assignment at 5 assig.Meas.Loc./ 4 Sides | |
229 | ASSIGNM. 5M,5S | M1,M2,M3,M4,M5 | M1,M2,M3,M4,M5 | Assignment at 5 assig.Meas.Loc./ 5 Sides | |
230 | ASSIGNM. ERROR | No AssigMeasLoc No of sides |
without | Assignment Error | |
241 | SIDE 1 | auto-connected | auto-connected | Side 1 is assigned to | |
242 | SIDE 2 | auto-connected | auto-connected | Side 2 is assigned to | |
243 | SIDE 3 | auto-connected compensation earth.electrode |
auto-connected | Side 3 is assigned to | |
244 | SIDE 4 | auto-connected compensation earth.electrode |
compensation | Side 4 is assigned to | |
251 | AUX. CT IX1 | Not connected conn/not assig. Side 1 earth Side 2 earth Side 3 earth Side 4 earth MeasLoc.1 earth MeasLoc.2 earth MeasLoc.3 earth MeasLoc.4 earth |
Not connected | Auxiliary CT IX1 is used as | |
252 | AUX. CT IX2 | Not connected conn/not assig. Side 1 earth Side 2 earth Side 3 earth Side 4 earth MeasLoc.1 earth MeasLoc.2 earth MeasLoc.3 earth MeasLoc.4 earth |
Not connected | Auxiliary CT IX2 is used as | |
253 | AUX. CT IX3 | Not connected conn/not assig. Side 1 earth Side 2 earth Side 3 earth Side 4 earth MeasLoc.1 earth MeasLoc.2 earth MeasLoc.3 earth MeasLoc.4 earth |
Not connected | Auxiliary CT IX3 is used as | |
254 | AUX. CT IX4 | Not connected conn/not assig. Side 1
earth Side 2 earth Side 3 earth Side 4 earth Side 5 earth MeasLoc.1 earth MeasLoc.2 earth MeasLoc.3 earth MeasLoc.4 earth MeasLoc.5 earth |
Not connected | Auxiliary CT IX4 is used as | |
255 | AUX CT IX3 TYPE | 1A/5A input sensitiv input |
1A/5A input | Type of auxiliary CT IX3 | |
256 | AUX CT IX4 TYPE | 1A/5A input sensitiv input |
1A/5A input | Type of auxiliary CT IX4 | |
261 | VT SET | Not connected Side 1 Side 2 Side 3 Measuring loc.1 Measuring loc.2 Measuring loc.3 Busbar |
Measuring loc.1 | VT set UL1, UL2, UL3 is assigned | |
262 | VT U4 | Not connected Side 1 Side 2 Side 3 Measuring loc.1 Measuring loc.2 Measuring loc.3 Busbar |
Measuring loc.1 | VT U4 is assigned | |
263 | VT U4 TYPE | Udelta transf. UL1E transform. UL2E transform. UL3E transform. UL12 transform. UL23 transform. UL31 transform. Ux transformer |
Udelta transf. | VT U4 is used as | |
270 | Rated Frequency | 50 Hz 60 Hz 16,7 Hz |
50 Hz | Rated Frequency | |
271 | PHASE SEQ. | L1 L2 L3 L1 L3 L2 |
L1 L2 L3 | Phase Sequence | |
276 | TEMP. UNIT | Celsius Fahrenheit |
Celsius | Unit of temperature measurement | |
311 | UN-PRI SIDE 1 | 0.4 .. 800.0 kV | 110.0 kV | Rated Primary Voltage Side 1 | |
312 | SN SIDE 1 | 0.20 .. 5000.00 MVA | 38.10 MVA | Rated Apparent Power of Transf. Side 1 | |
313 | STARPNT SIDE 1 | Earthed Isolated |
Earthed | Starpoint of Side 1 is | |
314 | CONNECTION S1 | Y D Z |
Y | Transf. Winding Connection Side 1 | |
321 | UN-PRI SIDE 2 | 0.4 .. 800.0 kV | 11.0 kV | Rated Primary Voltage Side 2 | |
322 | SN SIDE 2 | 0.20 .. 5000.00 MVA | 38.10 MVA | Rated Apparent Power of Transf. Side 2 | |
323 | STARPNT SIDE 2 | Earthed Isolated |
Earthed | Starpoint of Side 2 is | |
324 | CONNECTION S2 | Y D Z |
Y | Transf. Winding Connection Side 2 | |
325 | VECTOR GRP S2 | 0 1 2 3 4 5 6 7 8 9 10 11 |
0 | Vector Group Numeral of Side 2 | |
331 | UN-PRI SIDE 3 | 0.4 .. 800.0 kV | 11.0 kV | Rated Primary Voltage Side 3 | |
332 | SN SIDE 3 | 0.20 .. 5000.00 MVA | 10.00 MVA | Rated Apparent Power of Transf. Side 3 | |
333 | STARPNT SIDE 3 | Earthed Isolated |
Earthed | Starpoint of Side 3 is | |
334 | CONNECTION S3 | Y D Z |
Y | Transf. Winding Connection Side 3 | |
335 | VECTOR GRP S3 | 0 1 2 3 4 5 6 7 8 9 10 11 |
0 | Vector Group Numeral of Side 3 | |
341 | UN-PRI SIDE 4 | 0.4 .. 800.0 kV | 11.0 kV | Rated Primary Voltage Side 4 | |
342 | SN SIDE 4 | 0.20 .. 5000.00 MVA | 10.00 MVA | Rated Apparent Power of Transf. Side 4 | |
343 | STARPNT SIDE 4 | Earthed Isolated |
Earthed | Starpoint of Side 4 is | |
344 | CONNECTION S4 | Y D Z |
Y | Transf. Winding Connection Side 4 | |
345 | VECTOR GRP S4 | 0 1 2 3 4 5 6 7 8 9 10 11 |
0 | Vector Group Numeral of Side 4 | |
351 | UN-PRI SIDE 5 | 0.4 .. 800.0 kV | 11.0 kV | Rated Primary Voltage Side 5 | |
352 | SN SIDE 5 | 0.20 .. 5000.00 MVA | 10.00 MVA | Rated Apparent Power of Transf. Side 5 | |
353 | STARPNT SIDE 5 | Earthed Isolated |
Earthed | Starpoint of Side 5 is | |
354 | CONNECTION S5 | Y D Z |
Y | Transf. Winding Connection Side 5 | |
355 | VECTOR GRP S5 | 0 1 2 3 4 5 6 7 8 9 10 11 |
0 | Vector Group Numeral of Side 5 | |
361 | UN GEN/MOTOR | 0.4 .. 800.0 kV | 21.0 kV | Rated Primary Voltage Generator/ Motor | |
362 | SN GEN/MOTOR | 0.20 .. 5000.00 MVA | 70.00 MVA | Rated Apparent Power of the Generator | |
370 | UN BUSBAR | 0.4 .. 800.0 kV | 110.0 kV | Rated Primary Voltage Busbar | |
371 | I PRIMARY OP. | 1 .. 100000 A | 200 A | Primary Operating Current of Busbar | |
372 | I PRIMARY OP S1 | 1 .. 100000 A | 200 A | Primary Operating Current Side 1 | |
373 | I PRIMARY OP S2 | 1 .. 100000 A | 200 A | Primary Operating Current Side 2 | |
374 | I PRIMARY OP S3 | 1 .. 100000 A | 200 A | Primary Operating Current Side 3 | |
375 | I PRIMARY OP S4 | 1 .. 100000 A | 200 A | Primary Operating Current Side 4 | |
376 | I PRIMARY OP S5 | 1 .. 100000 A | 200 A | Primary Operating Current Side 5 | |
381 | I PRIMARY OP 1 | 1 .. 100000 A | 200 A | Primary Operating Current End 1 | |
382 | I PRIMARY OP 2 | 1 .. 100000 A | 200 A | Primary Operating Current End 2 | |
383 | I PRIMARY OP 3 | 1 .. 100000 A | 200 A | Primary Operating Current End 3 | |
384 | I PRIMARY OP 4 | 1 .. 100000 A | 200 A | Primary Operating Current End 4 | |
385 | I PRIMARY OP 5 | 1 .. 100000 A | 200 A | Primary Operating Current End 5 | |
386 | I PRIMARY OP 6 | 1 .. 100000 A | 200 A | Primary Operating Current End 6 | |
387 | I PRIMARY OP 7 | 1 .. 100000 A | 200 A | Primary Operating Current End 7 | |
388 | I PRIMARY OP 8 | 1 .. 100000 A | 200 A | Primary Operating Current End 8 | |
389 | I PRIMARY OP 9 | 1 .. 100000 A | 200 A | Primary Operating Current End 9 | |
390 | I PRIMARY OP 10 | 1 .. 100000 A | 200 A | Primary Operating Current End 10 | |
391 | I PRIMARY OP 11 | 1 .. 100000 A | 200 A | Primary Operating Current End 11 | |
392 | I PRIMARY OP 12 | 1 .. 100000 A | 200 A | Primary Operating Current End 12 | |
396 | PHASE SELECTION | Phase 1 Phase 2 Phase 3 |
Phase 1 | Phase selection | |
403 | I PRIMARY OP M3 | 1 .. 100000 A | 200 A | Primary Operating Current Meas. Loc. 3 | |
404 | I PRIMARY OP M4 | 1 .. 100000 A | 200 A | Primary Operating Current Meas. Loc. 4 | |
405 | I PRIMARY OP M5 | 1 .. 100000 A | 200 A | Primary Operating Current Meas. Loc. 5 | |
408 | UN-PRI M3 | 0.4 .. 800.0 kV | 110.0 kV | Rated Primary Voltage Measuring Loc. 3 | |
409 | UN-PRI U4 | 0.4 .. 800.0 kV | 110.0 kV | Rated Primary Voltage U4 | |
413 | REF PROT. AT | Side 1 Side 2 Side 3 Side 4 Side 5 auto-connected n.assigMeasLoc3 n.assigMeasLoc4 n.assigMeasLoc5 |
Side 1 | Restricted earth fault prot. assigned to | |
414 | REF PROT. 2 AT | Side 1 Side 2 Side 3 Side 4 Side 5 auto-connected n.assigMeasLoc3 n.assigMeasLoc4 n.assigMeasLoc5 |
Side 1 | Restricted earth fault prot2 assigned to | |
420 | DMT/IDMT Ph AT | Side 1 Side 2 Side 3 Side 4 Side 5 Measuring loc.1 Measuring loc.2 Measuring loc.3 Measuring loc.4 Measuring loc.5 |
Side 1 | DMT / IDMT Phase assigned to | |
422 | DMT/IDMT 3I0 AT | Side 1 Side 2 Side 3 Side 4 Side 5 Measuring loc.1 Measuring loc.2 Measuring loc.3 Measuring loc.4 Measuring loc.5 |
Side 1 | DMT / IDMT 3I0 assigned to | |
424 | DMT/IDMT E AT | no assig. poss. AuxiliaryCT IX1 AuxiliaryCT IX2 AuxiliaryCT IX3 AuxiliaryCT IX4 |
AuxiliaryCT IX1 | DMT / IDMT Earth assigned to | |
427 | DMT 1PHASE AT | no assig. poss. AuxiliaryCT IX1 AuxiliaryCT IX2 AuxiliaryCT IX3 AuxiliaryCT IX4 |
AuxiliaryCT IX1 | DMT 1Phase assigned to | |
430 | DMT/IDMT Ph2 AT | Side 1 Side 2 Side 3 Side 4 Side 5 Measuring loc.1 Measuring loc.2 Measuring loc.3 Measuring loc.4 Measuring loc.5 |
Side 1 | DMT / IDMT Phase 2 assigned to | |
432 | DMT/IDMT Ph3 AT | Side 1 Side 2 Side 3 Side 4 Side 5 Measuring loc.1 Measuring loc.2 Measuring loc.3 Measuring loc.4 Measuring loc.5 |
Side 1 | DMT / IDMT Phase 3 assigned to | |
434 | DMT/IDMT3I0-2AT | Side 1 Side 2 Side 3 Side 4 Side 5 Measuring loc.1 Measuring loc.2 Measuring loc.3 Measuring loc.4 Measuring loc.5 |
Side 1 | DMT / IDMT 3I0 2 assigned to | |
436 | DMT/IDMT3I0-3AT | Side 1 Side 2 Side 3 Side 4 Side 5 Measuring loc.1 Measuring loc.2 Measuring loc.3 Measuring loc.4 Measuring loc.5 |
Side 1 | DMT / IDMT 3I0 3 assigned to | |
438 | DMT/IDMT E2 AT | no assig. poss. AuxiliaryCT IX1 AuxiliaryCT IX2 AuxiliaryCT IX3 AuxiliaryCT IX4 |
AuxiliaryCT IX1 | DMT / IDMT Earth 2 assigned to | |
440 | UNBAL. LOAD AT | Side 1 Side 2 Side 3 Side 4 Side 5 Measuring loc.1 Measuring loc.2 Measuring loc.3 Measuring loc.4 Measuring loc.5 |
Side 1 | Unbalance Load (Neg. Seq.) assigned to | |
442 | THERM. O/L AT | Side 1 Side 2 Side 3 Side 4 Side 5 |
Side 1 | Thermal Overload Protection assigned to | |
444 | THERM. O/L 2 AT | Side 1 Side 2 Side 3 Side 4 Side 5 |
Side 1 | Thermal Overload Protection2 assigned to | |
470 | BREAKER FAIL.AT | Side 1 Side 2 Side 3 Side 4 Side 5 Measuring loc.1 Measuring loc.2 Measuring loc.3 Measuring loc.4 Measuring loc.5 Ext. switchg. 1 |
Side 1 | Breaker Failure Protection assigned to | |
471 | BREAKER FAIL2AT | Side 1 Side 2 Side 3 Side 4 Side 5 Measuring loc.1 Measuring loc.2 Measuring loc.3 Measuring loc.4 Measuring loc.5 Ext. switchg. 1 |
Side 1 | Breaker Failure Protection 2 assigned to | |
511 | STRPNT->OBJ M1 | YES NO |
YES | CT-Strpnt. Meas. Loc.1 in Dir. of Object | |
512 | IN-PRI CT M1 | 1 .. 100000 A | 200 A | CT Rated Primary Current Meas. Loc. 1 | |
513 | IN-SEC CT M1 | 1A 5A |
1A | CT Rated Secondary Current Meas. Loc. 1 | |
521 | STRPNT->OBJ M2 | YES NO |
YES | CT-Strpnt. Meas. Loc.2 in Dir. of Object | |
522 | IN-PRI CT M2 | 1 .. 100000 A | 2000 A | CT Rated Primary Current Meas. Loc. 2 | |
523 | IN-SEC CT M2 | 1A 5A |
1A | CT Rated Secondary Current Meas. Loc. 2 | |
531 | STRPNT->OBJ M3 | YES NO |
YES | CT-Strpnt. Meas. Loc.3 in Dir. of Object | |
532 | IN-PRI CT M3 | 1 .. 100000 A | 2000 A | CT Rated Primary Current Meas. Loc. 3 | |
533 | IN-SEC CT M3 | 1A 5A |
1A | CT Rated Secondary Current Meas. Loc. 3 | |
541 | STRPNT->OBJ M4 | YES NO |
YES | CT-Strpnt. Meas. Loc.4 in Dir. of Object | |
542 | IN-PRI CT M4 | 1 .. 100000 A | 2000 A | CT Rated Primary Current Meas. Loc. 4 | |
543 | IN-SEC CT M4 | 1A 5A |
1A | CT Rated Secondary Current Meas. Loc. 4 | |
551 | STRPNT->OBJ M5 | YES NO |
YES | CT-Strpnt. Meas. Loc.5 in Dir. of Object | |
552 | IN-PRI CT M5 | 1 .. 100000 A | 2000 A | CT Rated Primary Current Meas. Loc. 5 | |
553 | IN-SEC CT M5 | 1A 5A |
1A | CT Rated Secondary Current Meas. Loc. 5 | |
561 | STRPNT->BUS I1 | YES NO |
YES | CT-Starpoint I1 in Direction of Busbar | |
562 | IN-PRI CT I1 | 1 .. 100000 A | 200 A | CT Rated Primary Current I1 | |
563 | IN-SEC CT I1 | 1A 5A 0.1A |
1A | CT Rated Secondary Current I1 | |
571 | STRPNT->BUS I2 | YES NO |
YES | CT-Starpoint I2 in Direction of Busbar | |
572 | IN-PRI CT I2 | 1 .. 100000 A | 200 A | CT Rated Primary Current I2 | |
573 | IN-SEC CT I2 | 1A 5A 0.1A |
1A | CT Rated Secondary Current I2 | |
581 | STRPNT->BUS I3 | YES NO |
YES | CT-Starpoint I3 in Direction of Busbar | |
582 | IN-PRI CT I3 | 1 .. 100000 A | 200 A | CT Rated Primary Current I3 | |
583 | IN-SEC CT I3 | 1A 5A 0.1A |
1A | CT Rated Secondary Current I3 | |
591 | STRPNT->BUS I4 | YES NO |
YES | CT-Starpoint I4 in Direction of Busbar | |
592 | IN-PRI CT I4 | 1 .. 100000 A | 200 A | CT Rated Primary Current I4 | |
593 | IN-SEC CT I4 | 1A 5A 0.1A |
1A | CT Rated Secondary Current I4 | |
601 | STRPNT->BUS I5 | YES NO |
YES | CT-Starpoint I5 in Direction of Busbar | |
602 | IN-PRI CT I5 | 1 .. 100000 A | 200 A | CT Rated Primary Current I5 | |
603 | IN-SEC CT I5 | 1A 5A 0.1A |
1A | CT Rated Secondary Current I5 | |
611 | STRPNT->BUS I6 | YES NO |
YES | CT-Starpoint I6 in Direction of Busbar | |
612 | IN-PRI CT I6 | 1 .. 100000 A | 200 A | CT Rated Primary Current I6 | |
613 | IN-SEC CT I6 | 1A 5A 0.1A |
1A | CT Rated Secondary Current I6 | |
621 | STRPNT->BUS I7 | YES NO |
YES | CT-Starpoint I7 in Direction of Busbar | |
622 | IN-PRI CT I7 | 1 .. 100000 A | 200 A | CT Rated Primary Current I7 | |
623 | IN-SEC CT I7 | 1A 5A 0.1A |
1A | CT Rated Secondary Current I7 | |
631 | STRPNT->BUS I8 | YES NO |
YES | CT-Starpoint I8 in Direction of Busbar | |
632 | IN-PRI CT I8 | 1 .. 100000 A | 200 A | CT Rated Primary Current I8 | |
633 | IN-SEC CT I8 | 1A 5A 0.1A |
1A | CT Rated Secondary Current I8 | |
641 | STRPNT->BUS I9 | YES NO |
YES | CT-Starpoint I9 in Direction of Busbar | |
642 | IN-PRI CT I9 | 1 .. 100000 A | 200 A | CT Rated Primary Current I9 | |
643 | IN-SEC CT I9 | 1A 5A 0.1A |
1A | CT Rated Secondary Current I9 | |
651 | STRPNT->BUS I10 | YES NO |
YES | CT-Starpoint I10 in Direction of Busbar | |
652 | IN-PRI CT I10 | 1 .. 100000 A | 200 A | CT Rated Primary Current I10 | |
653 | IN-SEC CT I10 | 1A 5A 0.1A |
1A | CT Rated Secondary Current I10 | |
661 | STRPNT->BUS I11 | YES NO |
YES | CT-Starpoint I11 in Direction of Busbar | |
662 | IN-PRI CT I11 | 1 .. 100000 A | 200 A | CT Rated Primary Current I11 | |
663 | IN-SEC CT I11 | 1A 5A 0.1A |
1A | CT Rated Secondary Current I11 | |
671 | STRPNT->BUS I12 | YES NO |
YES | CT-Starpoint I12 in Direction of Busbar | |
672 | IN-PRI CT I12 | 1 .. 100000 A | 200 A | CT Rated Primary Current I12 | |
673 | IN-SEC CT I12 | 1A 5A 0.1A |
1A | CT Rated Secondary Current I12 | |
711 | EARTH IX1 AT | Terminal Q7 Terminal Q8 |
Terminal Q7 | Earthing electrod IX1 connected to | |
712 | IN-PRI CT IX1 | 1 .. 100000 A | 200 A | CT rated primary current IX1 | |
713 | IN-SEC CT IX1 | 1A 5A |
1A | CT rated secondary current IX1 | |
721 | EARTH IX2 AT | Terminal N7 Terminal N8 |
Terminal N7 | Earthing electrod IX2 connected to | |
722 | IN-PRI CT IX2 | 1 .. 100000 A | 200 A | CT rated primary current IX2 | |
723 | IN-SEC CT IX2 | 1A 5A |
1A | CT rated secondary current IX2 | |
731 | EARTH IX3 AT | Terminal R7 Terminal R8 |
Terminal R7 | Earthing electrod IX3 connected to | |
732 | IN-PRI CT IX3 | 1 .. 100000 A | 200 A | CT rated primary current IX3 | |
733 | IN-SEC CT IX3 | 1A 5A |
1A | CT rated secondary current IX3 | |
734 | FACTOR CT IX3 | 1.0 .. 300.0 | 60.0 | Factor: prim. over sek. current IX3 | |
741 | EARTH IX4 AT | Terminal P7 Terminal P8 |
Terminal P7 | Earthing electrod IX4 connected to | |
742 | IN-PRI CT IX4 | 1 .. 100000 A | 200 A | CT rated primary current IX4 | |
743 | IN-SEC CT IX4 | 1A 5A |
1A | CT rated secondary current IX4 | |
744 | FACTOR CT IX4 | 1.0 .. 300.0 | 60.0 | Factor: prim. over sek. current IX4 | |
801 | UN-PRI VT SET | 0.1 .. 1200.0 kV | 110.0 kV | VT Rated Prim. Voltage Set UL1, UL2, UL3 | |
802 | UN-SEC VT SET | 80 .. 125 V | 100 V | VT Rated Sec. Voltage Set UL1, UL2, UL3 | |
803 | CORRECT. U Ang | -5.00 .. 5.00 ° | 0.00 ° | Angle correction UL1, UL2, UL3 – VT | |
811 | UN-PRI VT U4 | 0.1 .. 1200.0 kV | 110.0 kV | VT Rated Primary Voltage U4 | |
812 | UN-SEC VT U4 | 80 .. 125 V | 100 V | VT Rated Secondary Voltage U4 | |
816 | Uph / Udelta | 0.10 .. 9.99 | 1.73 | Matching ratio Phase-VT to Open- Delta-VT | |
817 | Uph(U4)/Udelta | 0.10 .. 9.99 | 1.73 | Matching ratio Ph-VT(U4) to Open- DeltaVT | |
831 | SwitchgCBaux S1 | (Einstellmoglichkeiten anwendungsabhangig) | Switchgear / CBaux at Side 1 | ||
832 | SwitchgCBaux S2 | (Einstellmoglichkeiten anwendungsabhangig) | none | Switchgear / CBaux at Side 2 | |
833 | SwitchgCBaux S3 | (Einstellmoglichkeiten anwendungsabhangig) | none | Switchgear / CBaux at Side 3 | |
834 | SwitchgCBaux S4 | (Einstellmoglichkeiten anwendungsabhangig) | none | Switchgear / CBaux at Side 4 | |
835 | SwitchgCBaux S5 | (Einstellmoglichkeiten anwendungsabhangig) | none | Switchgear / CBaux at Side 5 | |
836 | SwitchgCBaux M1 | (Einstellmoglichkeiten anwendungsabhangig) | none | Switchgear / CBaux at Measuring Loc. M1 | |
837 | SwitchgCBaux M2 | (Einstellmoglichkeiten anwendungsabhangig) | none | Switchgear / CBaux at Measuring Loc. M2 | |
838 | SwitchgCBaux M3 | (Einstellmoglichkeiten anwendungsabhangig) | none | Switchgear / CBaux at Measuring Loc. M3 | |
839 | SwitchgCBaux M4 | (Einstellmoglichkeiten anwendungsabhangig) | none | Switchgear / CBaux at Measuring Loc. M4 | |
840 | SwitchgCBaux M5 | (Einstellmoglichkeiten anwendungsabhangig) | none | Switchgear / CBaux at Measuring Loc. M5 | |
841 | SwitchgCBaux E1 | (Einstellmoglichkeiten anwendungsabhangig) | none | Switchgear / CBaux at ext. location 1 | |
851A | TMin TRIP CMD | 0.01 .. 32.00 sec | 0.15 sec | Minimum TRIP Command Duration | |
Setting Groups
Addr. | Parameter | C | Setting Options | Default Setting | Comments |
302 | CHANGE | Group A Group B Group C Group D Binary Input Protocol |
Group A | Change to Another Setting Group | |
Power System Data 2
Addr. | Parameter | C | Setting Options | Default Setting | Comments |
1107 | P,Q sign | not reversed reversed |
not reversed | sign of P,Q | |
1111 | PoleOpenCurr.S1 | 0.04 .. 1.00 I/InS | 0.10 I/InS | Pole Open Current Threshold Side 1 | |
1112 | PoleOpenCurr.S2 | 0.04 .. 1.00 I/InS | 0.10 I/InS | Pole Open Current Threshold Side 2 | |
1113 | PoleOpenCurr.S3 | 0.04 .. 1.00 I/InS | 0.16 I/InS | Pole Open Current Threshold Side 3 | |
1114 | PoleOpenCurr.S4 | 0.04 .. 1.00 I/InS | 0.16 I/InS | Pole Open Current Threshold Side 4 | |
1115 | PoleOpenCurr.S5 | 0.04 .. 1.00 I/InS | 0.16 I/InS | Pole Open Current Threshold Side 5 | |
1121 | PoleOpenCurr.M1 | 1A | 0.04 .. 1.00 A | 0.04 A | Pole Open Current Threshold Meas.Loc. M1 |
5A | 0.20 .. 5.00 A | 0.20 A | |||
1122 | PoleOpenCurr.M2 | 1A | 0.04 .. 1.00 A | 0.04 A | Pole Open Current Threshold Meas.Loc. M2 |
5A | 0.20 .. 5.00 A | 0.20 A | |||
1123 | PoleOpenCurr.M3 | 1A | 0.04 .. 1.00 A | 0.04 A | Pole Open Current Threshold Meas.Loc. M3 |
5A | 0.20 .. 5.00 A | 0.20 A | |||
1124 | PoleOpenCurr.M4 | 1A | 0.04 .. 1.00 A | 0.04 A | Pole Open Current Threshold Meas.Loc. M4 |
5A | 0.20 .. 5.00 A | 0.20 A | |||
1125 | PoleOpenCurr.M5 | 1A | 0.04 .. 1.00 A | 0.04 A | Pole Open Current Threshold Meas.Loc. M5 |
5A | 0.20 .. 5.00 A | 0.20 A | |||
1131 | PoleOpenCurr I1 | 1A | 0.04 .. 1.00 A | 0.04 A | Pole Open Current Threshold End 1 |
5A | 0.20 .. 5.00 A | 0.20 A | |||
0.1A | 0.004 .. 0.100 A | 0.004 A | |||
1132 | PoleOpenCurr I2 | 1A | 0.04 .. 1.00 A | 0.04 A | Pole Open Current Threshold End 2 |
5A | 0.20 .. 5.00 A | 0.20 A | |||
0.1A | 0.004 .. 0.100 A | 0.004 A | |||
1133 | PoleOpenCurr I3 | 1A | 0.04 .. 1.00 A | 0.04 A | Pole Open Current Threshold End 3 |
5A | 0.20 .. 5.00 A | 0.20 A | |||
0.1A | 0.004 .. 0.100 A | 0.004 A | |||
1134 | PoleOpenCurr I4 | 1A | 0.04 .. 1.00 A | 0.04 A | Pole Open Current Threshold End 4 |
5A | 0.20 .. 5.00 A | 0.20 A | |||
0.1A | 0.004 .. 0.100 A | 0.004 A | |||
1135 | PoleOpenCurr I5 | 1A | 0.04 .. 1.00 A | 0.04 A | Pole Open Current Threshold End 5 |
5A | 0.20 .. 5.00 A | 0.20 A | |||
0.1A | 0.004 .. 0.100 A | 0.004 A | |||
1136 | PoleOpenCurr I6 | 1A | 0.04 .. 1.00 A | 0.04 A | Pole Open Current Threshold End 6 |
5A | 0.20 .. 5.00 A | 0.20 A | |||
0.1A | 0.004 .. 0.100 A | 0.004 A | |||
1137 | PoleOpenCurr I7 | 1A | 0.04 .. 1.00 A | 0.04 A | Pole Open Current Threshold End 7 |
5A | 0.20 .. 5.00 A | 0.20 A | |||
0.1A | 0.004 .. 0.100 A | 0.004 A | |||
1138 | PoleOpenCurr I8 | 1A | 0.04 .. 1.00 A | 0.04 A | Pole Open Current Threshold End 8 |
5A | 0.20 .. 5.00 A | 0.20 A | |||
0.1A | 0.004 .. 0.100 A | 0.004 A | |||
1139 | PoleOpenCurr I9 | 1A | 0.04 .. 1.00 A | 0.04 A | Pole Open Current Threshold End 9 |
5A | 0.20 .. 5.00 A | 0.20 A | |||
0.1A | 0.004 .. 0.100 A | 0.004 A | |||
1140 | PoleOpenCurrI10 | 1A | 0.04 .. 1.00 A | 0.04 A | Pole Open Current Threshold End 10 |
5A | 0.20 .. 5.00 A | 0.20 A | |||
0.1A | 0.004 .. 0.100 A | 0.004 A | |||
1141 | PoleOpenCurrI11 | 1A | 0.04 .. 1.00 A | 0.04 A | Pole Open Current Threshold End 11 |
5A | 0.20 .. 5.00 A | 0.20 A | |||
0.1A | 0.004 .. 0.100 A | 0.004 A | |||
1142 | PoleOpenCurrI12 | 1A | 0.04 .. 1.00 A | 0.04 A | Pole Open Current Threshold End 12 |
5A | 0.20 .. 5.00 A | 0.20 A | |||
0.1A | 0.004 .. 0.100 A | 0.004 A | |||
1151 | PoleOpenCurrIX1 | 1A | 0.04 .. 1.00 A | 0.04 A | Pole Open Current Threshold AuxiliaryCT1 |
5A | 0.20 .. 5.00 A | 0.20 A | |||
1152 | PoleOpenCurrIX2 | 1A | 0.04 .. 1.00 A | 0.04 A | Pole Open Current Threshold AuxiliaryCT2 |
5A | 0.20 .. 5.00 A | 0.20 A | |||
1153 | PoleOpenCurrIX3 | 1A | 0.04 .. 1.00 A | 0.04 A | Pole Open Current Threshold AuxiliaryCT3 |
5A | 0.20 .. 5.00 A | 0.20 A | |||
1154 | PoleOpenCurrIX4 | 1A | 0.04 .. 1.00 A | 0.04 A | Pole Open Current Threshold AuxiliaryCT4 |
5A | 0.20 .. 5.00 A | 0.20 A | |||
Differential Protection
Addr. | Parameter | C | Setting Options | Default Setting | Comments |
1201 | DIFF. PROT. | OFF ON Block relay |
OFF | Differential Protection | |
1205 | INC.CHAR.START | OFF ON |
OFF | Increase of Trip Char. During Start | |
1206 | INRUSH 2.HARM. | OFF ON |
ON | Inrush with 2. Harmonic Restraint | |
1207 | RESTR. n.HARM. | OFF 3. Harmonic 5. Harmonic |
OFF | n-th Harmonic Restraint | |
1208 | I-DIFF> MON. | OFF ON |
ON | Differential Current monitoring | |
1210 | I> CURR. GUARD | 0.20 .. 2.00 I/InS; 0 | 0.00 I/InS | I> for Current Guard | |
1211A | DIFFw.IE1-MEAS | NO YES |
NO | Diff-Prot. with meas. Earth Current S1 | |
1212A | DIFFw.IE2-MEAS | NO YES |
NO | Diff-Prot. with meas. Earth Current S2 | |
1213A | DIFFw.IE3-MEAS | NO YES |
NO | Diff-Prot. with meas. Earth Current S3 | |
1214A | DIFFw.IE4-MEAS | NO YES |
NO | Diff-Prot. with meas. Earth Current S4 | |
1215A | DIFFw.IE5-MEAS | NO YES |
NO | Diff-Prot. with meas. Earth Current S5 | |
1216A | DIFFw.IE3phMEAS | NO YES |
NO | Diff-Prot.with meas.current earth.electr | |
1221 | I-DIFF> | 0.05 .. 2.00 I/InO | 0.20 I/InO | Pickup Value of Differential Curr. | |
1226A | T I-DIFF> | 0.00 .. 60.00 sec; ∞ | 0.00 sec | T I-DIFF> Time Delay | |
1231 | I-DIFF>> | 0.5 .. 35.0 I/InO; ∞ | 7.5 I/InO | Pickup Value of High Set Trip | |
1236A | T I-DIFF>> | 0.00 .. 60.00 sec; ∞ | 0.00 sec | T I-DIFF>> Time Delay | |
1241A | SLOPE 1 | 0.10 .. 0.50 | 0.25 | Slope 1 of Tripping Characteristic | |
1242A | BASE POINT 1 | 0.00 .. 2.00 I/InO | 0.00 I/InO | Base Point for Slope 1 of Charac. | |
1243A | SLOPE 2 | 0.25 .. 0.95 | 0.50 | Slope 2 of Tripping Characteristic | |
1244A | BASE POINT 2 | 0.00 .. 10.00 I/InO | 2.50 I/InO | Base Point for Slope 2 of Charac. | |
1251A | I-REST. STARTUP | 0.00 .. 2.00 I/InO | 0.10 I/InO | I-RESTRAINT for Start Detection | |
1252A | START-FACTOR | 1.0 .. 2.0 | 1.0 | Factor for Increasing of Char. at Start | |
1253 | T START MAX | 0.0 .. 180.0 sec | 5.0 sec | Maximum Permissible Starting Time | |
1261A | I-ADD ON STAB. | 2.00 .. 15.00 I/InO | 4.00 I/InO | Pickup for Add-on Stabilization | |
1262A | T ADD ON-STAB. | 2 .. 250 Cycle; ∞ | 15 Cycle | Duration of Add-on Stabilization | |
1263A | CROSSB. ADD ON | 2 .. 1000 Cycle; 0; ∞ | 15 Cycle | Time for Cross-blocking Add-on Stabiliz. | |
1271 | 2. HARMONIC | 10 .. 80 % | 15 % | 2nd Harmonic Content in I-DIFF | |
1272A | CROSSB. 2. HARM | 2 .. 1000 Cycle; 0; ∞ | 3 Cycle | Time for Cross-blocking 2nd Harm. | |
1276 | n. HARMONIC | 10 .. 80 % | 30 % | n-th Harmonic Content in I-DIFF | |
1277A | CROSSB. n.HARM | 2 .. 1000 Cycle; 0; ∞ | 0 Cycle | Time for Cross-blocking n-th Harm. | |
1278A | IDIFFmax n.HM | 0.5 .. 20.0 I/InO | 1.5 I/InO | Limit IDIFFmax of n-th Harm.Restraint | |
1281 | I-DIFF> MON. | 0.15 .. 0.80 I/InO | 0.20 I/InO | Pickup Value of diff. Current Moni- toring | |
1282 | T I-DIFF> MON. | 1 .. 10 sec | 2 sec | T I-DIFF> Monitoring Time Delay | |
1283A | Inst. Idiff Rec | NO YES |
NO | Fault record with inst. diff current | |
1300 | Blocked w. CWA | ON OFF |
ON | Blocking with CWA | |
Restricted Earth Fault Protection
Addr. | Parameter | C | Setting Options | Default Setting | Comments |
1301 | REF PROT. | OFF ON Block relay |
OFF | Restricted Earth Fault Protection | |
1311 | I-REF> | 0.05 .. 2.00 I/InS | 0.15 I/InS | Pick up value I REF> | |
1312A | T I-REF> | 0.00 .. 60.00 sec; ∞ | 0.00 sec | T I-REF> Time Delay | |
1313A | SLOPE | 0.00 .. 0.95 | 0.00 | Slope of Charac. I-REF> = f(I-SUM) | |
Time Overcurrent Protection for Phase Currents
Addr. | Parameter | C | Setting Options | Default Setting | Comments |
2001 | PHASE O/C | ON OFF Block relay |
OFF | Phase Time Overcurrent | |
2002 | InRushRest. Ph | ON OFF |
OFF | InRush Restrained O/C Phase | |
2008A | MANUAL CLOSE | I>> instant. I> instant. Ip instant. Inactive |
I>> instant. | O/C Manual Close Mode | |
2011 | I>> | 1A | 0.10 .. 35.00 A; ∞ | 4.00 A | I>> Pickup |
5A | 0.50 .. 175.00 A; ∞ | 20.00 A | |||
2012 | I>> | 0.10 .. 35.00 I/InS; ∞ | 4.00 I/InS | I>> Pickup | |
2013 | T I>> | 0.00 .. 60.00 sec; ∞ | 0.10 sec | T I>> Time Delay | |
2014 | I> | 1A | 0.10 .. 35.00 A; ∞ | 2.00 A | I> Pickup |
5A | 0.50 .. 175.00 A; ∞ | 10.00 A | |||
2015 | I> | 0.10 .. 35.00 I/InS; ∞ | 2.00 I/InS | I> Pickup | |
2016 | T I> | 0.00 .. 60.00 sec; ∞ | 0.30 sec | T I> Time Delay | |
2021 | Ip | 1A | 0.10 .. 4.00 A | 2.00 A | Ip Pickup |
5A | 0.50 .. 20.00 A | 10.00 A | |||
2022 | Ip | 0.10 .. 4.00 I/InS | 2.00 I/InS | Ip Pickup | |
2023 | T Ip | 0.05 .. 3.20 sec; ∞ | 0.50 sec | T Ip Time Dial | |
2024 | D Ip | 0.50 .. 15.00 ; ∞ | 5.00 | D Ip Time Dial | |
2025 | TOC DROP-OUT | Instantaneous Disk Emulation |
Disk Emulation | TOC Drop-out characteristic | |
2026 | IEC CURVE | Normal Inverse Very Inverse Extremely Inv. Long Inverse |
Normal Inverse | IEC Curve | |
2027 | ANSI CURVE | Very Inverse Inverse Short Inverse Long Inverse Moderately Inv. Extremely Inv. Definite Inv. |
Very Inverse | ANSI Curve | |
2031 | I/Ip PU T/Tp | 1.00 .. 20.00 I/Ip; ∞ 0.01 .. 999.00 TD |
Pickup Curve I/Ip – TI/TIp | ||
2032 | MofPU Res T/Tp | 0.05 .. 0.95 I/Ip; ∞ 0.01 .. 999.00 TD |
Multiple of Pickup <-> TI/TIp | ||
2041 | 2.HARM. Phase | 10 .. 45 % | 15 % | 2nd harmonic O/C Ph. in % of fundamental | |
2042 | I Max InRr. Ph. | 1A | 0.30 .. 25.00 A | 7.50 A | Maximum Current for Inr. Rest. O/C Phase |
5A | 1.50 .. 125.00 A | 37.50 A | |||
2043 | I Max InRr. Ph. | 0.30 .. 25.00 I/InS | 7.50 I/InS | Maximum Current for Inr. Rest. O/C Phase | |
2044 | CROSS BLK.Phase | NO YES |
NO | CROSS BLOCK O/C Phase | |
2045 | T CROSS BLK.Ph | 0.00 .. 180.00 sec | 0.00 sec | CROSS BLOCK Time O/C Phase |
|
2111 | I>> | 1A | 0.10 .. 35.00 A; ∞ | 10.00 A | I>> Pickup |
5A | 0.50 .. 175.00 A; ∞ | 50.00 A | |||
2112 | I>> | 0.10 .. 35.00 I/InS; ∞ | 10.00 I/InS | I>> Pickup | |
2113 | T I>> | 0.00 .. 60.00 sec; ∞ | 0.10 sec | T I>> Time Delay | |
2114 | I> | 1A | 0.10 .. 35.00 A; ∞ | 4.00 A | I> Pickup |
5A | 0.50 .. 175.00 A; ∞ | 20.00 A | |||
2115 | I> | 0.10 .. 35.00 I/InS; ∞ | 4.00 I/InS | I> Pickup | |
2116 | T I> | 0.00 .. 60.00 sec; ∞ | 0.30 sec | T I> Time Delay | |
2121 | Ip | 1A | 0.10 .. 4.00 A | 4.00 A | Ip Pickup |
5A | 0.50 .. 20.00 A | 20.00 A | |||
2122 | Ip | 0.10 .. 4.00 I/InS | 4.00 I/InS | Ip Pickup | |
2123 | T Ip | 0.05 .. 3.20 sec; ∞ | 0.50 sec | T Ip Time Dial | |
2124 | D Ip | 0.50 .. 15.00 ; ∞ | 5.00 | D Ip Time Dial | |
Time Overcurrent Protection for Residual Current
Addr. | Parameter | C | Setting Options | Default Setting | Comments |
2201 | 3I0 O/C | ON OFF Block relay |
OFF | 3I0 Time Overcurrent | |
2202 | InRushRest. 3I0 | ON OFF | OFF | InRush Restrained O/C 3I0 | |
2208A | 3I0 MAN. CLOSE | 3I0>> instant. 3I0> instant. 3I0p instant. Inactive |
3I0>> instant. | O/C 3I0 Manual Close Mode | |
2211 | 3I0>> | 1A | 0.05 .. 35.00 A; ∞ | 1.00 A | 3I0>> Pickup |
5A | 0.25 .. 175.00 A; ∞ | 5.00 A | |||
2212 | 3I0>> | 0.05 .. 35.00 I/InS; ∞ | 1.00 I/InS | 3I0>> Pickup | |
2213 | T 3I0>> | 0.00 .. 60.00 sec; ∞ | 1.50 sec | T 3I0>> Time Delay | |
2214 | 3I0> | 1A | 0.05 .. 35.00 A; ∞ | 0.40 A | 3I0> Pickup |
5A | 0.25 .. 175.00 A; ∞ | 2.00 A | |||
2215 | 3I0> | 0.05 .. 35.00 I/InS; ∞ | 0.40 I/InS | 3I0> Pickup | |
2216 | T 3I0> | 0.00 .. 60.00 sec; ∞ | 2.00 sec | T 3I0> Time Delay | |
2221 | 3I0p | 1A | 0.05 .. 4.00 A | 0.40 A | 3I0p Pickup |
5A | 0.25 .. 20.00 A | 2.00 A | |||
2222 | 3I0p | 0.05 .. 4.00 I/InS | 0.40 I/InS | 3I0p Pickup | |
2223 | T 3I0p | 0.05 .. 3.20 sec; ∞ | 0.50 sec | T 3I0p Time Dial | |
2224 | D 3I0p | 0.50 .. 15.00 ; ∞ | 5.00 | D 3I0p Time Dial | |
2225 | TOC DROP-OUT | Instantaneous Disk Emulation |
Disk Emulation | TOC Drop-out Character- istic | |
2226 | IEC CURVE | Normal Inverse Very Inverse Extremely Inv. Long Inverse |
Normal Inverse | IEC Curve | |
2227 | ANSI CURVE | Very Inverse Inverse Short Inverse Long Inverse Moderately Inv. Extremely Inv. Definite Inv. |
Very Inverse | ANSI Curve | |
2231 | I/I0p PU T/TI0p | 1.00 .. 20.00 I/Ip; ∞ 0.01 .. 999.00 TD |
Pickup Curve 3I0/3I0p – T3I0/T3I0p | ||
2232 | MofPU ResT/TI0p | 0.05 .. 0.95 I/Ip; ∞ 0.01 .. 999.00 TD |
Multiple of Pickup <-> T3I0/ T3I0p | ||
2241 | 2.HARM. 3I0 | 10 .. 45 % | 15 % | 2nd harmonic O/C 3I0 in % of fundamental | |
2242 | I Max InRr. 3I0 | 1A | 0.30 .. 25.00 A | 7.50 A | Maximum Current for Inr. Rest. O/C 3I0 |
5A | 1.50 .. 125.00 A | 37.50 A | |||
2243 | I Max InRr. 3I0 | 0.30 .. 25.00 I/InS | 7.50 I/InS | Maximum Current for Inr. Rest. O/C 3I0 | |
2311 | 3I0>> | 1A | 0.05 .. 35.00 A; ∞ | 7.00 A | 3I0>> Pickup |
5A | 0.25 .. 175.00 A; ∞ | 35.00 A | |||
2312 | 3I0>> | 0.05 .. 35.00 I/InS; ∞ | 7.00 I/InS | 3I0>> Pickup | |
2313 | T 3I0>> | 0.00 .. 60.00 sec; ∞ | 1.50 sec | T 3I0>> Time Delay | |
2314 | 3I0> | 1A | 0.05 .. 35.00 A; ∞ | 1.50 A | 3I0> Pickup |
5A | 0.25 .. 175.00 A; ∞ | 7.50 A | |||
2315 | 3I0> | 0.05 .. 35.00 I/InS; ∞ | 1.50 I/InS | 3I0> Pickup | |
2316 | T 3I0> | 0.00 .. 60.00 sec; ∞ | 2.00 sec | T 3I0> Time Delay | |
2321 | 3I0p | 1A | 0.05 .. 4.00 A | 1.00 A | 3I0p Pickup |
5A | 0.25 .. 20.00 A | 5.00 A | |||
2322 | 3I0p | 0.05 .. 4.00 I/InS | 1.00 I/InS | 3I0p Pickup | |
2323 | T 3I0p | 0.05 .. 3.20 sec; ∞ | 0.50 sec | T 3I0p Time Dial | |
2324 | D 3I0p | 0.50 .. 15.00 ; ∞ | 5.00 | D 3I0p Time Dial | |
Time Overcurrent Protection for Earth Current
Addr. | Parameter | C | Setting Options | Default Setting | Comments |
2401 | EARTH O/C | ON OFF Block relay |
OFF | Earth Time Overcurrent | |
2402 | InRushRestEarth | ON OFF |
OFF | InRush Restrained O/C Earth | |
2408A | IE MAN. CLOSE | IE>> instant. IE> instant. IEp instant. Inactive |
IE>> instant. | O/C IE Manual Close Mode | |
2411 | IE>> | 1A | 0.05 .. 35.00 A; ∞ | 1.00 A | IE>> Pickup |
5A | 0.25 .. 175.00 A; ∞ | 5.00 A | |||
2412 | T IE>> | 0.00 .. 60.00 sec; ∞ | 1.50 sec | T IE>> Time Delay | |
2413 | IE> | 1A | 0.05 .. 35.00 A; ∞ | 0.40 A | IE> Pickup |
5A | 0.25 .. 175.00 A; ∞ | 2.00 A | |||
2414 | T IE> | 0.00 .. 60.00 sec; ∞ | 2.00 sec | T IE> Time Delay | |
2421 | IEp | 1A | 0.05 .. 4.00 A | 0.40 A | IEp Pickup |
5A | 0.25 .. 20.00 A | 2.00 A | |||
2422 | T IEp | 0.05 .. 3.20 sec; ∞ | 0.50 sec | T IEp Time Dial | |
2423 | D IEp | 0.50 .. 15.00 ; ∞ | 5.00 | D IEp Time Dial | |
2424 | TOC DROP-OUT | Instantaneous Disk Emulation |
Disk Emulation | TOC Drop-out Character- istic | |
2425 | IEC CURVE | Normal Inverse Very Inverse Extremely Inv. Long Inverse |
Normal Inverse | IEC Curve | |
2426 | ANSI CURVE | Very Inverse Inverse Short Inverse Long Inverse Moderately Inv. Extremely Inv. Definite Inv. |
Very Inverse | ANSI Curve | |
2431 | I/IEp PU T/TEp | 1.00 .. 20.00 I/Ip; ∞ 0.01 .. 999.00 TD |
Pickup Curve IE/IEp – TIE/ TIEp | ||
2432 | MofPU Res T/TEp | 0.05 .. 0.95 I/Ip; ∞ 0.01 .. 999.00 TD |
Multiple of Pickup <-> TI/ TIEp | ||
2441 | 2.HARM. Earth | 10 .. 45 % | 15 % | 2nd harmonic O/C E in % of fundamental | |
2442 | I Max InRr. E | 1A | 0.30 .. 25.00 A | 7.50 A | Maximum Current for Inr. Rest. O/C Earth |
5A | 1.50 .. 125.00 A | 37.50 A | |||
2511 | IE>> | 1A | 0.05 .. 35.00 A; ∞ | 7.00 A | IE>> Pickup |
5A | 0.25 .. 175.00 A; ∞ | 35.00 A | |||
2512 | T IE>> | 0.00 .. 60.00 sec; ∞ | 1.50 sec | T IE>> Time Delay | |
2513 | IE> | 1A | 0.05 .. 35.00 A; ∞ | 1.50 A | IE> Pickup |
5A | 0.25 .. 175.00 A; ∞ | 7.50 A | |||
2514 | T IE> | 0.00 .. 60.00 sec; ∞ | 2.00 sec | T IE> Time Delay | |
2521 | IEp | 1A | 0.05 .. 4.00 A | 1.00 A | IEp Pickup |
5A | 0.25 .. 20.00 A | 5.00 A | |||
2522 | T IEp | 0.05 .. 3.20 sec; ∞ | 0.50 sec | T IEp Time Dial | |
2523 | D IEp | 0.50 .. 15.00 ; ∞ | 5.00 | D IEp Time Dial | |
Dynamic Cold Load Pickup for Time Overcurrent Protection
Addr. | Parameter | C | Setting Options | Default Setting | Comments |
1701 | COLDLOAD PICKUP | OFF ON |
OFF | Cold-Load-Pickup Function | |
1702 | Start CLP Phase | No Current Breaker Contact |
No Current | Start Condition CLP for O/C Phase | |
1703 | Start CLP 3I0 | No Current Breaker Contact |
No Current | Start Condition CLP for O/C 3I0 | |
1704 | Start CLP Earth | No Current Breaker Contact |
No Current | Start Condition CLP for O/C Earth | |
1705 | Start CLP Ph 2 | No Current Breaker Contact |
No Current | Start Condition CLP for O/C Phase 2 | |
1706 | Start CLP Ph 3 | No Current Breaker Contact |
No Current | Start Condition CLP for O/C Phase 3 | |
1707 | Start CLP 3I0 2 | No Current Breaker Contact |
No Current | Start Condition CLP for O/C 3I0 2 | |
1708 | Start CLP 3I0 3 | No Current Breaker Contact |
No Current | Start Condition CLP for O/C 3I0 3 | |
1709 | Start CLP E 2 | No Current Breaker Contact |
No Current | Start Condition CLP for O/C Earth 2 | |
1711 | CB Open Time | 0 .. 21600 sec | 3600 sec | Circuit Breaker OPEN Time | |
1712 | Active Time | 1 .. 21600 sec | 3600 sec | Active Time | |
1713 | Stop Time | 1 .. 600 sec; ∞ | 600 sec | Stop Time | |
Single-Phase Time Overcurrent Protection
Addr. | Parameter | C | Setting Options | Default Setting | Comments |
2701 | 1Phase O/C | OFF ON Block relay |
OFF | 1Phase Time Overcurrent | |
2702 | 1Phase I>> | 1A | 0.05 .. 35.00 A; ∞ | 0.50 A | 1Phase O/C I>> Pickup |
5A | 0.25 .. 175.00 A; ∞ | 2.50 A | |||
2703 | 1Phase I>> | 0.003 .. 1.500 A; ∞ | 0.300 A | 1Phase O/C I>> Pickup | |
2704 | T 1Phase I>> | 0.00 .. 60.00 sec; ∞ | 0.10 sec | T 1Phase O/C I>> Time Delay | |
2705 | 1Phase I> | 1A | 0.05 .. 35.00 A; ∞ | 0.20 A | 1Phase O/C I> Pickup |
5A | 0.25 .. 175.00 A; ∞ | 1.00 A | |||
2706 | 1Phase I> | 0.003 .. 1.500 A; ∞ | 0.100 A | 1Phase O/C I> Pickup | |
2707 | T 1Phase I> | 0.00 .. 60.00 sec; ∞ | 0.50 sec | T 1Phase O/C I> Time Delay | |
Unbalanced Load Protection
Addr. | Parameter | C | Setting Options | Default Setting | Comments |
4001 | UNBALANCE LOAD | OFF ON Block relay |
OFF | Unbalance Load (Negative Sequence) | |
4011 | I2>> | 1A | 0.10 .. 3.00 A; ∞ | 0.50 A | I2>> Pickup |
5A | 0.50 .. 15.00 A; ∞ | 2.50 A | |||
4012 | I2>> | 0.10 .. 3.00 I/InS; ∞ | 0.50 I/InS | I2>> Pickup | |
4013 | T I2>> | 0.00 .. 60.00 sec; ∞ | 1.50 sec | T I2>> Time Delay | |
4014 | I2> | 1A | 0.10 .. 3.00 A; ∞ | 0.10 A | I2> Pickup |
5A | 0.50 .. 15.00 A; ∞ | 0.50 A | |||
4015 | I2> | 0.10 .. 3.00 I/InS; ∞ | 0.10 I/InS | I2> Pickup | |
4016 | T I2> | 0.00 .. 60.00 sec; ∞ | 1.50 sec | T I2> Time Delay | |
4021 | I2p | 1A | 0.10 .. 2.00 A | 0.90 A | I2p Pickup |
5A | 0.50 .. 10.00 A | 4.50 A | |||
4022 | I2p | 0.10 .. 2.00 I/InS | 0.90 I/InS | I2p Pickup | |
4023 | T I2p | 0.05 .. 3.20 sec; ∞ | 0.50 sec | T I2p Time Dial | |
4024 | D I2p | 0.50 .. 15.00 ; ∞ | 5.00 | D I2p Time Dial | |
4025 | I2p DROP-OUT | Instantaneous Disk Emulation |
Instantaneous | I2p Drop-out Characteristic | |
4026 | IEC CURVE | Normal Inverse Very Inverse Extremely Inv. |
Extremely Inv. | IEC Curve | |
4027 | ANSI CURVE | Extremely Inv. Inverse Moderately Inv. Very Inverse |
Extremely Inv. | ANSI Curve | |
4031 | I2> | 1A | 0.01 .. 4.00 A; ∞ | 0.10 A | Continously Permissible Current I2 |
5A | 0.05 .. 20.00 A; ∞ | 0.50 A | |||
4032 | I2 tolerance | 0.01 .. 0.80 I/InS; ∞ | 0.16 I/InS | Permissable quiescent unbalanced load | |
4033 | T WARN | 0.00 .. 60.00 sec; ∞ | 20.00 sec | Warning Stage Time Delay | |
4034 | FACTOR K | 1.0 .. 100.0 sec; ∞ | 18.7 sec | Negativ Sequence Factor K | |
4035 | T COOL DOWN | 0 .. 50000 sec | 1650 sec | Time for Cooling Down | |
Thermal Overload Protection
Addr. | Parameter | C | Setting Options | Default Setting | Comments |
4201 | THERM. OVERLOAD | OFF ON Block relay Alarm Only |
OFF | Thermal Overload Protection | |
4202 | K-FACTOR | 0.10 .. 4.00 | 1.10 | K-Factor | |
4203 | TIME CONSTANT | 1.0 .. 999.9 min | 100.0 min | Thermal Time Constant | |
4204 | Θ ALARM | 50 .. 100 % | 90 % | Thermal Alarm Stage | |
4205 | I ALARM | 0.10 .. 4.00 I/InS | 1.00 I/InS | Current Overload Alarm Setpoint | |
4207A | Kτ-FACTOR | 1.0 .. 10.0 | 1.0 | Kt-FACTOR when motor stops | |
4208A | T EMERGENCY | 10 .. 15000 sec | 100 sec | Emergency Time | |
4209A | I MOTOR START | 0.60 .. 10.00 I/InS; ∞ | ∞ I/InS | Current Pickup Value of Motor Starting | |
4210 | TEMPSENSOR RTD | 1 .. 6 | 1 | Temperature sensor connected to RTD | |
4211 | TEMPSENSOR RTD | 1 .. 12 | 1 | Temperature sensor connected to RTD | |
4212 | TEMP. RISE I | 40 .. 200 °C | 100 °C | Temperature Rise at Rated Sec. Curr. | |
4213 | TEMP. RISE I | 104 .. 392 °F | 212 °F | Temperature Rise at Rated Sec. Curr. | |
4220 | OIL-DET. RTD | 1 .. 6 | 1 | Oil-Detector conected at RTD | |
4221 | OIL Sensor RTD | 1 .. 12 | 1 | Oil sensor connected to RTD | |
4222 | HOT SPOT ST. 1 | 98 .. 140 °C | 98 °C | Hot Spot Temperature Stage 1 Pickup | |
4223 | HOT SPOT ST. 1 | 208 .. 284 °F | 208 °F | Hot Spot Temperature Stage 1 Pickup | |
4224 | HOT SPOT ST. 2 | 98 .. 140 °C | 108 °C | Hot Spot Temperature Stage 2 Pickup | |
4225 | HOT SPOT ST. 2 | 208 .. 284 °F | 226 °F | Hot Spot Temperature Stage 2 Pickup | |
4226 | AG. RATE ST. 1 | 0.200 .. 128.000 | 1.000 | Aging Rate STAGE 1 Pickup | |
4227 | AG. RATE ST. 2 | 0.200 .. 128.000 | 2.000 | Aging Rate STAGE 2 Pickup | |
4231 | METH. COOLING | ON OF OD |
ON | Method of Cooling | |
4232 | Y-WIND.EXPONENT | 1.6 .. 2.0 | 1.6 | Y-Winding Exponent | |
4233 | HOT-SPOT GR | 22 .. 29 | 22 | Hot-spot to top-oil gradient | |
RTD-Boxes for Overload Detection
Addr. | Parameter | C | Setting Options | Default Setting | Comments |
9011A | RTD 1 TYPE | Not connected Pt 100 Ω Ni 120 Ω Ni 100 Ω |
Pt 100 Ω | RTD 1: Type | |
9012A | RTD 1 LOCATION | Oil Ambient Winding Bearing Other |
Oil | RTD 1: Location | |
9013 | RTD 1 STAGE 1 | -50 .. 250 °C; ∞ | 100 °C | RTD 1: Temperature Stage 1 Pickup | |
9014 | RTD 1 STAGE 1 | -58 .. 482 °F; ∞ | 212 °F | RTD 1: Temperature Stage 1 Pickup | |
9015 | RTD 1 STAGE 2 | -50 .. 250 °C; ∞ | 120 °C | RTD 1: Temperature Stage 2 Pickup | |
9016 | RTD 1 STAGE 2 | -58 .. 482 °F; ∞ | 248 °F | RTD 1: Temperature Stage 2 Pickup | |
9021A | RTD 2 TYPE | Not connected Pt 100 Ω Ni 120 Ω Ni 100 Ω |
Not connected | RTD 2: Type | |
9022A | RTD 2 LOCATION | Oil Ambient Winding Bearing Other |
Other | RTD 2: Location | |
9023 | RTD 2 STAGE 1 | -50 .. 250 °C; ∞ | 100 °C | RTD 2: Temperature Stage 1 Pickup | |
9024 | RTD 2 STAGE 1 | -58 .. 482 °F; ∞ | 212 °F | RTD 2: Temperature Stage 1 Pickup | |
9025 | RTD 2 STAGE 2 | -50 .. 250 °C; ∞ | 120 °C | RTD 2: Temperature Stage 2 Pickup | |
9026 | RTD 2 STAGE 2 | -58 .. 482 °F; ∞ | 248 °F | RTD 2: Temperature Stage 2 Pickup | |
9031A | RTD 3 TYPE | Not connected Pt 100 Ω Ni 120 Ω Ni 100 Ω |
Not connected | RTD 3: Type | |
9032A | RTD 3 LOCATION | Oil Ambient Winding Bearing Other |
Other | RTD 3: Location | |
9033 | RTD 3 STAGE 1 | -50 .. 250 °C; ∞ | 100 °C | RTD 3: Temperature Stage 1 Pickup | |
9034 | RTD 3 STAGE 1 | -58 .. 482 °F; ∞ | 212 °F | RTD 3: Temperature Stage 1 Pickup | |
9035 | RTD 3 STAGE 2 | -50 .. 250 °C; ∞ | 120 °C | RTD 3: Temperature Stage 2 Pickup | |
9036 | RTD 3 STAGE 2 | -58 .. 482 °F; ∞ | 248 °F | RTD 3: Temperature Stage 2 Pickup | |
9041A | RTD 4 TYPE | Not connected Pt 100 Ω Ni 120 Ω Ni 100 Ω |
Not connected | RTD 4: Type | |
9042A | RTD 4 LOCATION | Oil Ambient Winding Bearing Other |
Other | RTD 4: Location | |
9043 | RTD 4 STAGE 1 | -50 .. 250 °C; ∞ | 100 °C | RTD 4: Temperature Stage 1 Pickup | |
9044 | RTD 4 STAGE 1 | -58 .. 482 °F; ∞ | 212 °F | RTD 4: Temperature Stage 1 Pickup | |
9045 | RTD 4 STAGE 2 | -50 .. 250 °C; ∞ | 120 °C | RTD 4: Temperature Stage 2 Pickup | |
9046 | RTD 4 STAGE 2 | -58 .. 482 °F; ∞ | 248 °F | RTD 4: Temperature Stage 2 Pickup | |
9051A | RTD 5 TYPE | Not connected Pt 100 Ω Ni 120 Ω Ni 100 Ω |
Not connected | RTD 5: Type | |
9052A | RTD 5 LOCATION | Oil Ambient Winding Bearing Other |
Other | RTD 5: Location | |
9053 | RTD 5 STAGE 1 | -50 .. 250 °C; ∞ | 100 °C | RTD 5: Temperature Stage 1 Pickup | |
9054 | RTD 5 STAGE 1 | -58 .. 482 °F; ∞ | 212 °F | RTD 5: Temperature Stage 1 Pickup | |
9055 | RTD 5 STAGE 2 | -50 .. 250 °C; ∞ | 120 °C | RTD 5: Temperature Stage 2 Pickup | |
9056 | RTD 5 STAGE 2 | -58 .. 482 °F; ∞ | 248 °F | RTD 5: Temperature Stage 2 Pickup | |
9061A | RTD 6 TYPE | Not connected Pt 100 Ω Ni 120 Ω Ni 100 Ω |
Not connected | RTD 6: Type | |
9062A | RTD 6 LOCATION | Oil Ambient Winding Bearing Other |
Other | RTD 6: Location | |
9063 | RTD 6 STAGE 1 | -50 .. 250 °C; ∞ | 100 °C | RTD 6: Temperature Stage 1 Pickup | |
9064 | RTD 6 STAGE 1 | -58 .. 482 °F; ∞ | 212 °F | RTD 6: Temperature Stage 1 Pickup | |
9065 | RTD 6 STAGE 2 | -50 .. 250 °C; ∞ | 120 °C | RTD 6: Temperature Stage 2 Pickup | |
9066 | RTD 6 STAGE 2 | -58 .. 482 °F; ∞ | 248 °F | RTD 6: Temperature Stage 2 Pickup | |
9071A | RTD 7 TYPE | Not connected Pt 100 Ω Ni 120 Ω Ni 100 Ω |
Not connected | RTD 7: Type | |
9072A | RTD 7 LOCATION | Oil Ambient Winding Bearing Other |
Other | RTD 7: Location | |
9073 | RTD 7 STAGE 1 | -50 .. 250 °C; ∞ | 100 °C | RTD 7: Temperature Stage 1 Pickup | |
9074 | RTD 7 STAGE 1 | -58 .. 482 °F; ∞ | 212 °F | RTD 7: Temperature Stage 1 Pickup | |
9075 | RTD 7 STAGE 2 | -50 .. 250 °C; ∞ | 120 °C | RTD 7: Temperature Stage 2 Pickup | |
9076 | RTD 7 STAGE 2 | -58 .. 482 °F; ∞ | 248 °F | RTD 7: Temperature Stage 2 Pickup | |
9081A | RTD 8 TYPE | Not connected Pt 100 Ω Ni 120 Ω Ni 100 Ω |
Not connected | RTD 8: Type | |
9082A | RTD 8 LOCATION | Oil Ambient Winding Bearing Other |
Other | RTD 8: Location | |
9083 | RTD 8 STAGE 1 | -50 .. 250 °C; ∞ | 100 °C | RTD 8: Temperature Stage 1 Pickup | |
9084 | RTD 8 STAGE 1 | -58 .. 482 °F; ∞ | 212 °F | RTD 8: Temperature Stage 1 Pickup | |
9085 | RTD 8 STAGE 2 | -50 .. 250 °C; ∞ | 120 °C | RTD 8: Temperature Stage 2 Pickup | |
9086 | RTD 8 STAGE 2 | -58 .. 482 °F; ∞ | 248 °F | RTD 8: Temperature Stage 2 Pickup | |
9091A | RTD 9 TYPE | Not connected Pt 100 Ω Ni 120 Ω Ni 100 Ω |
Not connected | RTD 9: Type | |
9092A | RTD 9 LOCATION | Oil Ambient Winding Bearing Other |
Other | RTD 9: Location | |
9093 | RTD 9 STAGE 1 | -50 .. 250 °C; ∞ | 100 °C | RTD 9: Temperature Stage 1 Pickup | |
9094 | RTD 9 STAGE 1 | -58 .. 482 °F; ∞ | 212 °F | RTD 9: Temperature Stage 1 Pickup | |
9095 | RTD 9 STAGE 2 | -50 .. 250 °C; ∞ | 120 °C | RTD 9: Temperature Stage 2 Pickup | |
9096 | RTD 9 STAGE 2 | -58 .. 482 °F; ∞ | 248 °F | RTD 9: Temperature Stage 2 Pickup | |
9101A | RTD10 TYPE | Not connected Pt 100 Ω Ni 120 Ω Ni 100 Ω |
Not connected | RTD10: Type | |
9102A | RTD10 LOCATION | Oil Ambient Winding Bearing Other |
Other | RTD10: Location | |
9103 | RTD10 STAGE 1 | -50 .. 250 °C; ∞ | 100 °C | RTD10: Temperature Stage 1 Pickup | |
9104 | RTD10 STAGE 1 | -58 .. 482 °F; ∞ | 212 °F | RTD10: Temperature Stage 1 Pickup | |
9105 | RTD10 STAGE 2 | -50 .. 250 °C; ∞ | 120 °C | RTD10: Temperature Stage 2 Pickup | |
9106 | RTD10 STAGE 2 | -58 .. 482 °F; ∞ | 248 °F | RTD10: Temperature Stage 2 Pickup | |
9111A | RTD11 TYPE | Not connected Pt 100 Ω Ni 120 Ω Ni 100 Ω |
Not connected | RTD11: Type | |
9112A | RTD11 LOCATION | Oil Ambient Winding Bearing Other |
Other | RTD11: Location | |
9113 | RTD11 STAGE 1 | -50 .. 250 °C; ∞ | 100 °C | RTD11: Temperature Stage 1 Pickup | |
9114 | RTD11 STAGE 1 | -58 .. 482 °F; ∞ | 212 °F | RTD11: Temperature Stage 1 Pickup | |
9115 | RTD11 STAGE 2 | -50 .. 250 °C; ∞ | 120 °C | RTD11: Temperature Stage 2 Pickup | |
9116 | RTD11 STAGE 2 | -58 .. 482 °F; ∞ | 248 °F | RTD11: Temperature Stage 2 Pickup | |
9121A | RTD12 TYPE | Not connected Pt 100 Ω Ni 120 Ω Ni 100 Ω |
Not connected | RTD12: Type | |
9122A | RTD12 LOCATION | Oil Ambient Winding Bearing Other |
Other | RTD12: Location | |
9123 | RTD12 STAGE 1 | -50 .. 250 °C; ∞ | 100 °C | RTD12: Temperature Stage 1 Pickup | |
9124 | RTD12 STAGE 1 | -58 .. 482 °F; ∞ | 212 °F | RTD12: Temperature Stage 1 Pickup | |
9125 | RTD12 STAGE 2 | -50 .. 250 °C; ∞ | 120 °C | RTD12: Temperature Stage 2 Pickup | |
9126 | RTD12 STAGE 2 | -58 .. 482 °F; ∞ | 248 °F | RTD12: Temperature Stage 2 Pickup | |
Overexcitation Protection
Addr. | Parameter | C | Setting Options | Default Setting | Comments |
4301 | OVEREXC. PROT. | OFF ON Block relay |
OFF | Overexcitation Protection (U/f) | |
4302 | U/f > | 1.00 .. 1.20 | 1.10 | U/f > Pickup | |
4303 | T U/f > | 0.00 .. 60.00 sec; ∞ | 10.00 sec | T U/f > Time Delay | |
4304 | U/f >> | 1.00 .. 1.40 | 1.40 | U/f >> Pickup | |
4305 | T U/f >> | 0.00 .. 60.00 sec; ∞ | 1.00 sec | T U/f >> Time Delay | |
4306 | t(U/f=1.05) | 0 .. 20000 sec | 20000 sec | U/f = 1.05 Time Delay | |
4307 | t(U/f=1.10) | 0 .. 20000 sec | 6000 sec | U/f = 1.10 Time Delay | |
4308 | t(U/f=1.15) | 0 .. 20000 sec | 240 sec | U/f = 1.15 Time Delay | |
4309 | t(U/f=1.20) | 0 .. 20000 sec | 60 sec | U/f = 1.20 Time Delay | |
4310 | t(U/f=1.25) | 0 .. 20000 sec | 30 sec | U/f = 1.25 Time Delay | |
4311 | t(U/f=1.30) | 0 .. 20000 sec | 19 sec | U/f = 1.30 Time Delay | |
4312 | t(U/f=1.35) | 0 .. 20000 sec | 13 sec | U/f = 1.35 Time Delay | |
4313 | t(U/f=1.40) | 0 .. 20000 sec | 10 sec | U/f = 1.40 Time Delay | |
4314 | T COOL DOWN | 0 .. 20000 sec | 3600 sec | Time for cool down | |
Reverse Power Protection
Addr. | Parameter | C | Setting Options | Default Setting | Comments |
5001 | REVERSE POWER | OFF ON Block relay |
OFF | Reverse Power Protection | |
5011 | P> REVERSE | 1A | -3000.00 .. -0.85 W | -8.70 W | P> Reverse Pickup |
5A | -15000.00 .. -4.25 W | -43.50 W | |||
5012 | Pr pick-up | -17.000 .. -0.005 P/SnS | -0.050 P/SnS | Pick-up threshold reverse power | |
5013 | T-SV-OPEN | 0.00 .. 60.00 sec; ∞ | 10.00 sec | Time Delay Long (without Stop Valve) | |
5014 | T-SV-CLOSED | 0.00 .. 60.00 sec; ∞ | 1.00 sec | Time Delay Short (with Stop Valve) | |
5015A | T-HOLD | 0.00 .. 60.00 sec; ∞ | 0.00 sec | Pickup Holding Time | |
5016A | Type of meas. | accurate fast |
accurate | Type of measurement | |
Forward Power Supervision
Addr. | Parameter | C | Setting Options | Default Setting | Comments |
5101 | FORWARD POWER | OFF ON Block relay |
OFF | Forward Power Supervision | |
5111 | Pf< | 1A | 1.7 .. 3000.0 W | 17.3 W | P-forw.< Supervision Pickup |
5A | 8.5 .. 15000.0 W | 86.5 W | |||
5112 | P< fwd | 0.01 .. 17.00 P/SnS | 0.10 P/SnS | Pick-up threshold P< | |
5113 | T-Pf< | 0.00 .. 60.00 sec; ∞ | 10.00 sec | T-P-forw.< Time Delay | |
5114 | Pf> | 1A | 1.7 .. 3000.0 W | 164.5 W | P-forw.> Supervision Pickup |
5A | 8.5 .. 15000.0 W | 822.5 W | |||
5115 | P> fwd | 0.01 .. 17.00 P/SnS | 0.95 P/SnS | Pick-up threshold P> | |
5116 | T-Pf> | 0.00 .. 60.00 sec; ∞ | 10.00 sec | T-P-forw.> Time Delay | |
5117A | MEAS. METHOD | accurate fast |
accurate | Method of Operation | |
Undervoltage Protection
Addr. | Parameter | C | Setting Options | Default Setting | Comments |
5201 | UNDERVOLTAGE | OFF ON Block relay |
OFF | Undervoltage Protection | |
5211 | U< | 10.0 .. 125.0 V | 75.0 V | U< Pickup | |
5212 | U< | 0.10 .. 1.25 U/UnS | 0.75 U/UnS | Pick-up voltage U< | |
5213 | T U< | 0.00 .. 60.00 sec; ∞ | 3.00 sec | T U< Time Delay | |
5214 | U<< | 10.0 .. 125.0 V | 65.0 V | U<< Pickup | |
5215 | U<< | 0.10 .. 1.25 U/UnS | 0.65 U/UnS | Pick-up voltage U<< | |
5216 | T U<< | 0.00 .. 60.00 sec; ∞ | 0.50 sec | T U<< Time Delay | |
5217A | DOUT RATIO | 1.01 .. 1.20 | 1.05 | U<, U<< Drop Out Ratio | |
Overvoltage Protection
Addr. | Parameter | C | Setting Options | Default Setting | Comments |
5301 | OVERVOLTAGE | OFF ON Block relay |
OFF | Overvoltage Protection | |
5311 | U> | 30.0 .. 170.0 V | 115.0 V | U> Pickup | |
5312 | U> | 0.30 .. 1.70 U/UnS | 1.15 U/UnS | Pick-up voltage U> | |
5313 | T U> | 0.00 .. 60.00 sec; ∞ | 3.00 sec | T U> Time Delay | |
5314 | U>> | 30.0 .. 170.0 V | 130.0 V | U>> Pickup | |
5315 | U>> | 0.30 .. 1.70 U/UnS | 1.30 U/UnS | Pick-up voltage U>> | |
5316 | T U>> | 0.00 .. 60.00 sec; ∞ | 0.50 sec | T U>> Time Delay | |
5317A | DOUT RATIO | 0.90 .. 0.99 | 0.98 | U>, U>> Drop Out Ratio | |
5318A | VALUES | U-ph-ph U-ph-e |
U-ph-ph | Measurement Values | |
Frequency Protection
Addr. | Parameter | C | Setting Options | Default Setting | Comments |
5601 | O/U FREQUENCY | OFF ON Block relay |
OFF | Over / Under Frequency Protection | |
5611 | f< | 40.00 .. 49.99 Hz; 0 | 49.50 Hz | Pick-up frequency f< | |
5612 | f<< | 40.00 .. 49.99 Hz; 0 | 48.00 Hz | Pick-up frequency f<< | |
5613 | f<<< | 40.00 .. 49.99 Hz; 0 | 47.00 Hz | Pick-up frequency f<<< | |
5614 | f> | 50.01 .. 66.00 Hz; ∞ | 52.00 Hz | Pick-up frequency f> | |
5621 | f< | 50.00 .. 59.99 Hz; 0 | 59.50 Hz | Pick-up frequency f< | |
5622 | f<< | 50.00 .. 59.99 Hz; 0 | 58.00 Hz | Pick-up frequency f<< | |
5623 | f<<< | 50.00 .. 59.99 Hz; 0 | 57.00 Hz | Pick-up frequency f<<< | |
5624 | f> | 60.01 .. 66.00 Hz; ∞ | 62.00 Hz | Pick-up frequency f> | |
5631 | f< | 10.00 .. 16.69 Hz; 0 | 16.50 Hz | Pick-up frequency f< | |
5632 | f<< | 10.00 .. 16.69 Hz; 0 | 16.00 Hz | Pick-up frequency f<< | |
5633 | f<<< | 10.00 .. 16.69 Hz; 0 | 15.70 Hz | Pick-up frequency f<<< | |
5634 | f> | 16.67 .. 22.00 Hz; ∞ | 17.40 Hz | Pick-up frequency f> | |
5641 | T f< | 0.00 .. 100.00 sec; ∞ | 20.00 sec | Delay time T f< | |
5642 | T f<< | 0.00 .. 600.00 sec; ∞ | 1.00 sec | Delay time T f<< | |
5643 | T f<<< | 0.00 .. 100.00 sec; ∞ | 6.00 sec | Delay time T f<<< | |
5644 | T f> | 0.00 .. 100.00 sec; ∞ | 10.00 sec | Delay time T f> | |
5651 | Umin | 10.0 .. 125.0 V; 0 | 65.0 V | Minimum Required Voltage for Operation | |
5652 | U MIN | 0.10 .. 1.25 U/UnS; 0 | 0.65 U/UnS | Minimum voltage | |
Circuit Breaker Failure Protection
Addr. | Parameter | C | Setting Options | Default Setting | Comments |
7001 | BREAKER FAILURE | OFF ON Block relay |
OFF | Breaker Failure Protection | |
7011 | START WITH REL. | 0 .. 8 | 0 | Start with Relay (intern) | |
7012 | START WITH REL. | 0 .. 24 | 0 | Start with Relay (intern) | |
7015 | T1 | 0.00 .. 60.00 sec; ∞ | 0.15 sec | T1, Delay of 1st stage (local trip) | |
7016 | T2 | 0.00 .. 60.00 sec; ∞ | 0.30 sec | T2, Delay of 2nd stage (busbar trip) | |
External Trip Commands
Addr. | Parameter | C | Setting Options | Default Setting | Comments |
8601 | EXTERN TRIP 1 | OFF ON Block relay |
OFF | External Trip Function 1 | |
8602 | T DELAY | 0.00 .. 60.00 sec; ∞ | 1.00 sec | Ext. Trip 1 Time Delay | |
8701 | EXTERN TRIP 2 | OFF ON Block relay |
OFF | External Trip Function 2 | |
8702 | T DELAY | 0.00 .. 60.00 sec; ∞ | 1.00 sec | Ext. Trip 2 Time Delay | |
Measurement Supervision
Addr. | Parameter | C | Setting Options | Default Setting | Comments |
8101 | BALANCE I | ON OFF |
OFF | Current Balance Supervi- sion | |
8102 | BALANCE U | ON OFF |
OFF | Voltage Balance Supervi- sion | |
8104 | SUMMATION U | ON OFF |
OFF | Voltage Summation Super- vision | |
8105 | PHASE ROTAT. I | ON OFF |
OFF | Current Phase Rotation Supervision | |
8106 | PHASE ROTAT. U | ON OFF |
OFF | Voltage Phase Rotation Supervision | |
8111 | BAL. I LIMIT M1 | 1A | 0.10 .. 1.00 A | 0.50 A | Current Balance Monitor Meas. Loc. 1 |
5A | 0.50 .. 5.00 A | 2.50 A | |||
8112 | BAL. FACT. I M1 | 0.10 .. 0.90 | 0.50 | Bal. Factor for Curr. Monitor Meas.Loc.1 | |
8113A | T Sym. I th. M1 | 5 .. 100 sec | 5 sec | Symmetry Iph: Pick-up delay | |
8121 | BAL. I LIMIT M2 | 1A | 0.10 .. 1.00 A | 0.50 A | Current Balance Monitor Meas. Loc. 2 |
5A | 0.50 .. 5.00 A | 2.50 A | |||
8122 | BAL. FACT. I M2 | 0.10 .. 0.90 | 0.50 | Bal. Factor for Curr. Monitor Meas.Loc.2 | |
8123A | T Sym. I th. M2 | 5 .. 100 sec | 5 sec | Symmetry Iph: Pick-up delay | |
8131 | BAL. I LIMIT M3 | 1A | 0.10 .. 1.00 A | 0.50 A | Current Balance Monitor Meas. Loc. 3 |
5A | 0.50 .. 5.00 A | 2.50 A | |||
8132 | BAL. FACT. I M3 | 0.10 .. 0.90 | 0.50 | Bal. Factor for Curr. Monitor Meas.Loc.3 | |
8133A | T Sym. I th. M3 | 5 .. 100 sec | 5 sec | Symmetry Iph: Pick-up delay | |
8141 | BAL. I LIMIT M4 | 1A | 0.10 .. 1.00 A | 0.50 A | Current Balance Monitor Meas. Loc. 4 |
5A | 0.50 .. 5.00 A | 2.50 A | |||
8142 | BAL. FACT. I M4 | 0.10 .. 0.90 | 0.50 | Bal. Factor for Curr. Monitor Meas.Loc.4 | |
8143A | T Sym. I th. M4 | 5 .. 100 sec | 5 sec | Symmetry Iph: Pick-up delay | |
8151 | BAL. I LIMIT M5 | 1A | 0.10 .. 1.00 A | 0.50 A | Current Balance Monitor Meas. Loc. 5 |
5A | 0.50 .. 5.00 A | 2.50 A | |||
8152 | BAL. FACT. I M5 | 0.10 .. 0.90 | 0.50 | Bal. Factor for Curr. Monitor Meas.Loc.5 | |
8153A | T Sym. I th. M5 | 5 .. 100 sec | 5 sec | Symmetry Iph: Pick-up delay | |
8161 | BALANCE U-LIMIT | 10 .. 100 V | 50 V | Voltage Threshold for Balance Monitoring | |
8162 | BAL. FACTOR U | 0.58 .. 0.90 | 0.75 | Balance Factor for Voltage Monitor | |
8163A | T BAL. U LIMIT | 5 .. 100 sec | 5 sec | T Balance Factor for Voltage Monitor | |
Trip Circuit Supervision
Addr. | Parameter | C | Setting Options | Default Setting | Comments |
8201 | TRIP Cir. SUP. | ON OFF |
OFF | TRIP Circuit Supervision | |
Broken Wire Detection, Fuse Failure Monitoring
Addr. | Parameter | C | Setting Options | Default Setting | Comments |
2911A | FFM U>(min) | 10 .. 100 V | 20 V | Minimum Voltage Threshold U> | |
8401 | BROKEN WIRE | OFF BWD Al and Blk BWD Al and ABlk BWD Al only |
OFF | Fast broken current-wire supervision | |
8403 | FUSE FAIL MON. | OFF ON |
OFF | Fuse Failure Monitor | |
8414 | T BWD delay | 0.0 .. 180.0 sec | 1.0 sec | Delay time for BWD super- vision | |
8415 | ΔI< BWD | 0.05 .. 5.00 I/InO | 1.00 I/InO | min differential current for BWD | |
8422A | FFM I< M1 | 1A | 0.04 .. 2.00 A | 0.10 A | I< for FFM detection M1 |
5A | 0.20 .. 10.00 A | 0.50 A | |||
8423A | FFM I< M2 | 1A | 0.04 .. 2.00 A | 0.10 A | I< for FFM detection M2 |
5A | 0.20 .. 10.00 A | 0.50 A | |||
8424A | FFM I< M3 | 1A | 0.04 .. 2.00 A | 0.10 A | I< for FFM detection M3 |
5A | 0.20 .. 10.00 A | 0.50 A | |||
8426A | FFM U<max (3ph) | 2 .. 100 V | 5 V | Maximum Voltage Threshold U< (3phase) | |
Measurement
Addr. | Parameter | C | Setting Options | Default Setting | Comments |
7601 | POWER CALCUL. | with V setting with V measur. |
with V setting | Calculation of Power | |
Flexible Function
Addr. | Parameter | C | Setting Options | Default Setting | Comments |
0 | FLEXIBLE FUNC. | OFF ON Alarm Only Block relay |
OFF | Flexible Function | |
0 | Pick-up thresh. | 1A | 0.05 .. 35.00 A | 2.00 A | Pick-up threshold I meas. location 1 |
5A | 0.25 .. 175.00 A | 10.00 A | |||
0 | Pick-up thresh. | 1A | 0.05 .. 35.00 A | 2.00 A | Pick-up threshold I meas. location 2 |
5A | 0.25 .. 175.00 A | 10.00 A | |||
0 | Pick-up thresh. | 1A | 0.05 .. 35.00 A | 2.00 A | Pick-up threshold I meas. location 3 |
5A | 0.25 .. 175.00 A | 10.00 A | |||
0 | Pick-up thresh. | 1A | 0.05 .. 35.00 A | 2.00 A | Pick-up threshold I meas. location 4 |
5A | 0.25 .. 175.00 A | 10.00 A | |||
0 | Pick-up thresh. | 1A | 0.05 .. 35.00 A | 2.00 A | Pick-up threshold I meas. location 5 |
5A | 0.25 .. 175.00 A | 10.00 A | |||
0 | Pick-up thresh. | 1A | 0.05 .. 35.00 A | 2.00 A | Pick-up threshold I1 |
5A | 0.25 .. 175.00 A | 10.00 A | |||
0.1A | 0.005 .. 3.500 A | 0.200 A | |||
0 | Pick-up thresh. | 1A | 0.05 .. 35.00 A | 2.00 A | Pick-up threshold I2 |
5A | 0.25 .. 175.00 A | 10.00 A | |||
0.1A | 0.005 .. 3.500 A | 0.200 A | |||
0 | Pick-up thresh. | 1A | 0.05 .. 35.00 A | 2.00 A | Pick-up threshold I3 |
5A | 0.25 .. 175.00 A | 10.00 A | |||
0.1A | 0.005 .. 3.500 A | 0.200 A | |||
0 | Pick-up thresh. | 1A | 0.05 .. 35.00 A | 2.00 A | Pick-up threshold I4 |
5A | 0.25 .. 175.00 A | 10.00 A | |||
0.1A | 0.005 .. 3.500 A | 0.200 A | |||
0 | Pick-up thresh. | 1A | 0.05 .. 35.00 A | 2.00 A | Pick-up threshold I5 |
5A | 0.25 .. 175.00 A | 10.00 A | |||
0.1A | 0.005 .. 3.500 A | 0.200 A | |||
0 | Pick-up thresh. | 1A | 0.05 .. 35.00 A | 2.00 A | Pick-up threshold I6 |
5A | 0.25 .. 175.00 A | 10.00 A | |||
0.1A | 0.005 .. 3.500 A | 0.200 A | |||
0 | Pick-up thresh. | 1A | 0.05 .. 35.00 A | 2.00 A | Pick-up threshold I7 |
5A | 0.25 .. 175.00 A | 10.00 A | |||
0.1A | 0.005 .. 3.500 A | 0.200 A | |||
0 | Pick-up thresh. | 1A | 0.05 .. 35.00 A | 2.00 A | Pick-up threshold I8 |
5A | 0.25 .. 175.00 A | 10.00 A | |||
0.1A | 0.005 .. 3.500 A | 0.200 A | |||
0 | Pick-up thresh. | 1A | 0.05 .. 35.00 A | 2.00 A | Pick-up threshold I9 |
5A | 0.25 .. 175.00 A | 10.00 A | |||
0.1A | 0.005 .. 3.500 A | 0.200 A | |||
0 | Pick-up thresh. | 1A | 0.05 .. 35.00 A | 2.00 A | Pick-up threshold I10 |
5A | 0.25 .. 175.00 A | 10.00 A | |||
0.1A | 0.005 .. 3.500 A | 0.200 A | |||
0 | Pick-up thresh. | 1A | 0.05 .. 35.00 A | 2.00 A | Pick-up threshold I11 |
5A | 0.25 .. 175.00 A | 10.00 A | |||
0.1A | 0.005 .. 3.500 A | 0.200 A | |||
0 | Pick-up thresh. | 1A | 0.05 .. 35.00 A | 2.00 A | Pick-up threshold I12 |
5A | 0.25 .. 175.00 A | 10.00 A | |||
0.1A | 0.005 .. 3.500 A | 0.200 A | |||
0 | Pick-up thresh. | 1A | 0.05 .. 35.00 A | 2.00 A | Pick-up threshold IX1 |
5A | 0.25 .. 175.00 A | 10.00 A | |||
0 | Pick-up thresh. | 1A | 0.05 .. 35.00 A | 2.00 A | Pick-up threshold IX2 |
5A | 0.25 .. 175.00 A | 10.00 A | |||
0 | Pick-up thresh. | 1A | 0.05 .. 35.00 A | 2.00 A | Pick-up threshold IX3 |
5A | 0.25 .. 175.00 A | 10.00 A | |||
0 | Pick-up thresh. | 1A | 0.05 .. 35.00 A | 2.00 A | Pick-up threshold IX4 |
5A | 0.25 .. 175.00 A | 10.00 A | |||
0 | Pick-up thresh. | 0.001 .. 1.500 A | 0.100 A | Pick-up threshold IX3 sens. | |
0 | Pick-up thresh. | 0.001 .. 1.500 A | 0.100 A | Pick-up threshold IX4 sens. | |
0 | Pick-up thresh. | 0.05 .. 35.00 I/InS | 2.00 I/InS | Pick-up threshold I-side | |
0 | P.U. THRESHOLD | 1.0 .. 170.0 V | 110.0 V | Pickup Threshold | |
0 | P.U. THRESHOLD | 1.0 .. 170.0 V | 110.0 V | Pickup Threshold | |
0 | P.U. THRESHOLD | 40.00 .. 66.00 Hz | 51.00 Hz | Pickup Threshold | |
0 | P.U. THRESHOLD | 10.00 .. 22.00 Hz | 18.00 Hz | Pickup Threshold | |
0 | P.U. THRESHOLD | 1A | 1.7 .. 3000.0 W | 200.0 W | Pickup Threshold |
5A | 8.5 .. 15000.0 W | 1000.0 W | |||
0 | Pick-up thresh. | 0.01 .. 17.00 P/SnS | 1.10 P/SnS | Pick-up threshold P-side | |
0 | Pick-up thresh. | 1A | 1.7 .. 3000.0 VAR | 200.0 VAR | Pick-up threshold Q meas. location |
5A | 8.5 .. 15000.0 VAR | 1000.0 VAR | |||
0 | Pick-up thresh. | 0.01 .. 17.00 Q/SnS | 1.10 Q/SnS | Pick-up threshold Q-side | |
0 | P.U. THRESHOLD | -0.99 .. 0.99 | 0.50 | Pickup Threshold | |
0 | T TRIP DELAY | 0.00 .. 3600.00 sec | 1.00 sec | Trip Time Delay | |
0A | T PICKUP DELAY | 0.00 .. 60.00 sec | 0.00 sec | Pickup Time Delay | |
0A | T DROPOUT DELAY | 0.00 .. 60.00 sec | 0.00 sec | Dropout Time Delay | |
0A | BLOCKED BY FFM | YES NO |
YES | Block in case of Meas.- Voltage Loss | |
0A | Blk I brkn cond | YES NO |
YES | Block for broken conductor in CT path | |
0A | DROPOUT RATIO | 0.70 .. 0.99 | 0.95 | Dropout Ratio | |
0A | DROPOUT RATIO | 1.01 .. 3.00 | 1.05 | Dropout Ratio | |
0 | MEAS. QUANTITY | Please select I-Meas Loc/side Curr. I1..I12 Curr. IX1..IX4 Voltage P forward P reverse Q forward Q reverse Power factor Frequency |
|||
0 | Func. assigned | Please select Side 1 Side 2 Side 3 Side 4 Side 5 Measuring loc.1 Measuring loc.2 Measuring loc.3 Measuring loc.4 Measuring loc.5 |
|||
0 | Func. per phase | IL1..IL3 IL1 IL2 IL3 3I0 (Zero seq.) I1 (Pos. seq.) I2 (Neg. seq.) |
|||
0 | Func. assigned | Please select I-CT 1 I-CT 2 I-CT 3 I-CT 4 I-CT 5 I-CT 6 I-CT 7 I-CT 8 I-CT 9 I-CT 10 I-CT 11 I-CT 12 |
|||
0 | Func. assigned | Please select AuxiliaryCT IX1 AuxiliaryCT IX2 AuxiliaryCT IX3 AuxiliaryCT IX4 |
|||
0 | Func. per phase | Please select UL1E..UL3E UL1E UL2E UL3E UL12..UL31 UL12 UL23 UL31 U0 (Zero seq.) U1 (Pos. seq.) U2 (Neg. seq.) U4/Uen |
|||
0 | PICKUP WITH | Exceeding Dropping below |
|||
0A | Type of meas. | accurate fast |
|||
Oscillographic Fault Recording
Addr. | Parameter | C | Setting Options | Default Setting | Comments |
901 | WAVEFORMTRIGGER | Save w. Pickup Save w. TRIP Start w. TRIP |
Save w. Pickup | Waveform Capture | |
903 | MAX. LENGTH | 0.30 .. 5.00 sec | 1.00 sec | Max. length of a Waveform Capture Record | |
904 | PRE. TRIG. TIME | 0.05 .. 0.50 sec | 0.20 sec | Captured Waveform Prior to Trigger | |
905 | POST REC. TIME | 0.05 .. 0.50 sec | 0.10 sec | Captured Waveform after Event | |
906 | BinIn CAPT.TIME | 0.10 .. 5.00 sec; ∞ | 0.50 sec | Capture Time via Binary Input | |
Demand Measurement Setup
Addr. | Parameter | C | Setting Options | Default Setting | Comments |
7611 | DMD Interval | 15 Min., 1 Sub 15 Min., 3 Subs 15 Min.,15 Subs 30 Min., 1 Sub 60 Min., 1 Sub 60 Min.,10 Subs 5 Min., 5 Subs |
60 Min., 1 Sub | Demand Calculation Intervals | |
7612 | DMD Sync.Time | On The Hour 15 After Hour 30 After Hour 45 After Hour |
On The Hour | Demand Synchronization Time | |
Min/Max Measurement Setup
Addr. | Parameter | C | Setting Options | Default Setting | Comments |
7621 | MinMax cycRESET | NO YES |
YES | Automatic Cyclic Reset Function | |
7622 | MiMa RESET TIME | 0 .. 1439 min | 0 min | MinMax Reset Timer | |
7623 | MiMa RESETCYCLE | 1 .. 365 Days | 7 Days | MinMax Reset Cycle Period | |
7624 | MinMaxRES.START | 1 .. 365 Days | 1 Days | MinMax Start Reset Cycle in | |