Table of Contents

Siemens / SIPROTEC 7UT6 V4.67 setting parameters & highlights (SI4016)

Table of Contents

Overview

The SIPROTEC 7UT6 differential protection relays are used for fast and selective fault clearing of short-circuits in transformers of all voltage levels and in rotating electric machines like motors and generators, for short lines and busbars.

For more detailed information on “SIPROTEC 7UT6x V4.67” relays, refer to SIPROTEC 4 devices manuals.

To see other supported devices, click here.


Analog measuring inputs

  for 3-phase protected objects1) for busbar 1-phase Voltage 3-phase Voltage 1-phase
Current 3-phase1) Current (auxiliary) Strom 1-phase Current (auxiliary)
1-phase sensitive2) 1-phase sensitive2)
7UT612 2 2 1 7 2 1
7UT613 3 3 1 9 3 1 1 1
7UT633 3 3 1 9 3 1 1 1
7UT635 5 1 1
4 4 2 12 4 2
1) also applicable for single-phase power transformers
2) selectable, contained in the number of 1-phase inputs

Device

Addr. Parameter C Setting Options Default Setting Comments
201 FltDisp.LED/LCD   Target on PU
Target on TRIP
Target on PU Fault Display on LED / LCD
202 Spont. FltDisp.   NO
YES
NO Spontaneous display of flt.annun- ciations
204 Start image DD   image 1
image 2
image 3
image 4
image 5
image 6
image 7
image 1 Start image Default Display

Functional Scope

Addr. Parameter C Setting Options Default Setting Comments
103 Grp Chge OPTION   Disabled
Enabled
Disabled Setting Group Change Option
105 PROT. OBJECT   3 phase transf.
1 phase transf.
Autotransf.
Autotr. node
Generator/Motor
3ph Busbar
1ph Busbar
3 phase transf. Protection Object
112 DIFF. PROT.   Disabled
Enabled
Enabled Differential Protection
113 REF PROT.   Disabled
Enabled
Disabled Restricted earth fault protection
114 REF PROT. 2   Disabled
Enabled
Disabled Restricted earth fault protection 2
117 COLDLOAD PICKUP   Disabled
Enabled
Disabled Cold Load Pickup
120 DMT/IDMT Phase   Disabled
Definite Time
TOC IEC
TOC ANSI
User Defined PU
User def. Reset
Disabled DMT / IDMT Phase
122 DMT/IDMT 3I0   Disabled
Definite Time
TOC IEC
TOC ANSI
User Defined PU
User def. Reset
Disabled DMT / IDMT 3I0
124 DMT/IDMT Earth   Disabled
Definite Time
TOC IEC
TOC ANSI
User Defined PU
User def. Reset
Disabled DMT / IDMT Earth
127 DMT 1PHASE   Disabled
Enabled
Disabled DMT 1Phase
130 DMT/IDMT Phase2   Disabled
Definite Time
TOC IEC
TOC ANSI
User Defined PU
User def. Reset
Disabled DMT / IDMT Phase 2
132 DMT/IDMT Phase3   Disabled
Definite Time
TOC IEC
TOC ANSI
User Defined PU
User def. Reset
Disabled DMT / IDMT Phase 3
134 DMT/IDMT 3I0 2   Disabled
Definite Time
TOC IEC
TOC ANSI
User Defined PU
User def. Reset
Disabled DMT / IDMT 3I0 2
136 DMT/IDMT 3I0 3   Disabled
Definite Time
TOC IEC
TOC ANSI
User Defined PU
User def. Reset
Disabled DMT / IDMT 3I0 3
138 DMT/IDMT Earth2   Disabled
Definite Time
TOC IEC
TOC ANSI
User Defined PU
User def. Reset
Disabled DMT / IDMT Earth 2
140 UNBALANCE LOAD   Disabled
Definite Time
TOC IEC
TOC ANSI
DT/thermal
Disabled Unbalance Load (Negative Sequence)
142 THERM. OVERLOAD   Disabled
th rep w.o. sen
th repl w. sens
IEC354
Disabled Thermal Overload Protection
143 OVEREXC. PROT.   Disabled
Enabled
Disabled Overexcitation Protection (U/f)
144 THERM.OVERLOAD2   Disabled
th rep w.o. sen
th repl w. sens
IEC354
Disabled Thermal Overload Protection 2
150 REVERSE POWER   Disabled
Enabled
Disabled Reverse Power Protection
151 FORWARD POWER   Disabled
Enabled
Disabled Forward Power Supervision
152 UNDERVOLTAGE   Disabled
Enabled
Disabled Undervoltage Protection
153 OVERVOLTAGE   Disabled
Enabled
Disabled Overvoltage Protection
156 FREQUENCY Prot.   Disabled
Enabled
Disabled Over / Underfrequency Protection
170 BREAKER FAILURE   Disabled
Enabled
Disabled Breaker Failure Protection
171 BREAKER FAIL. 2   Disabled
Enabled
Disabled Breaker Failure Protection 2
180 DISCON.MEAS.LOC   Disabled
Enabled
Disabled Disconnect measurment location
181 M.V. SUPERV   Disabled
Enabled
Enabled Measured Values Supervision
182 Trip Cir. Sup.   Disabled
2 Binary Inputs
1 Binary Input
Disabled Trip Circuit Supervision
186 EXT. TRIP 1   Disabled
Enabled
Disabled External Trip Function 1
187 EXT. TRIP 2   Disabled
Enabled
Disabled External Trip Function 2
190 RTD-BOX INPUT   Disabled
Port C
Port D
Disabled External Temperature Input
191 RTD CONNECTION   6 RTD simplex
6 RTD HDX
12 RTD HDX
6 RTD simplex Ext. Temperature Input Connec- tion Type
FLEXIBLE FcT. 1…12   Flexible Function 01
Flexible Function 02
Flexible Function 03
Flexible Function 04
Flexible Function 05
Flexible Function 06
Flexible Function 07
Flexible Function 08
Flexible Function 09
Flexible Function 10
Flexible Function 11
Flexible Function 12
Please select Flexible Functions 1…12
ADD MV 1…20   Add. MV 01
Add. MV 02
Add. MV 03
Add. MV 04
Add. MV 05
Add. MV 06
Add. MV 07
Add. MV 08
Add. MV 09
Add. MV 10
Add. MV 11
Add. MV 12
Add. MV 13
Add. MV 14
Add. MV 15
Add. MV 16
Add. MV 17
Add. MV 18
Add. MV 19
Add. MV 20
Please select Additional Measured Value 1…20

Power System Data 1

Addr. Parameter C Setting Options Default Setting Comments
211 No Conn.MeasLoc   2
3
4
5
3 Number of connected Measuring Locations
212 No AssigMeasLoc   2
3
4
5
3 Number of assigned Measuring Locations
213 NUMBER OF SIDES   2
3
4
5
3 Number of Sides
216 NUMBER OF ENDS   3
4
5
6
7
8
9
10
11
12
6 Number of Ends for 1 Phase Busbar
220 ASSIGNM. 2M,2S   M1,M2 M1,M2 Assignment at 2 assig.Meas.Loc./ 2 Sides
221 ASSIGNM. 3M,2S   M1+M2,M3
M1,M2+M3
M1+M2,M3 Assignment at 3 assig.Meas.Loc./ 2 Sides
222 ASSIGNM. 3M,3S   M1,M2,M3 M1,M2,M3 Assignment at 3 assig.Meas.Loc./ 3 Sides
223 ASSIGNM. 4M,2S   M1+M2,M3+M4
M1+M2+M3,M4
M1,M2+M3+M4
M1+M2,M3+M4 Assignment at 4 assig.Meas.Loc./ 2 Sides
224 ASSIGNM. 4M,3S   M1+M2,M3,M4
M1,M2+M3,M4
M1,M2,M3+M4
M1+M2,M3,M4 Assignment at 4 assig.Meas.Loc./ 3 Sides
225 ASSIGNM. 4M,4S   M1,M2,M3,M4 M1,M2,M3,M4 Assignment at 4 assig.Meas.Loc./ 4 Sides
226 ASSIGNM. 5M,2S   M1+M2+M3,M4+M5 M1+M2,M3+M4+M5 M1+M2+M3+M4,M5 M1,M2+M3+M4+M5 M1+M2+M3,M4+M5 Assignment at 5 assig.Meas.Loc./ 2 Sides
227 ASSIGNM. 5M,3S   M1+M2,M3+M4,M5 M1+M2,M3,M4+M5 M1,M2+M3,M4+M5 M1+M2+M3,M4,M5 M1,M2+M3+M4,M5 M1,M2,M3+M4+M5 M1+M2,M3+M4,M5 Assignment at 5 assig.Meas.Loc./ 3 Sides
228 ASSIGNM. 5M,4S   M1+M2,M3,M4,M5 M1,M2+M3,M4,M5 M1,M2,M3+M4,M5 M1,M2,M3,M4+M5 M1+M2,M3,M4,M5 Assignment at 5 assig.Meas.Loc./ 4 Sides
229 ASSIGNM. 5M,5S   M1,M2,M3,M4,M5 M1,M2,M3,M4,M5 Assignment at 5 assig.Meas.Loc./ 5 Sides
230 ASSIGNM. ERROR   No AssigMeasLoc
No of sides
without Assignment Error
241 SIDE 1   auto-connected auto-connected Side 1 is assigned to
242 SIDE 2   auto-connected auto-connected Side 2 is assigned to
243 SIDE 3   auto-connected
compensation
earth.electrode
auto-connected Side 3 is assigned to
244 SIDE 4   auto-connected
compensation
earth.electrode
compensation Side 4 is assigned to
251 AUX. CT IX1   Not connected
conn/not assig.
Side 1 earth
Side 2 earth
Side 3 earth
Side 4 earth
MeasLoc.1 earth
MeasLoc.2 earth
MeasLoc.3 earth
MeasLoc.4 earth
Not connected Auxiliary CT IX1 is used as
252 AUX. CT IX2   Not connected
conn/not assig.
Side 1 earth
Side 2 earth
Side 3 earth
Side 4 earth
MeasLoc.1 earth
MeasLoc.2 earth
MeasLoc.3 earth
MeasLoc.4 earth
Not connected Auxiliary CT IX2 is used as
253 AUX. CT IX3   Not connected
conn/not assig.
Side 1 earth
Side 2 earth
Side 3 earth
Side 4 earth
MeasLoc.1 earth
MeasLoc.2 earth
MeasLoc.3 earth
MeasLoc.4 earth
Not connected Auxiliary CT IX3 is used as
254 AUX. CT IX4   Not connected conn/not assig. Side 1 earth
Side 2 earth
Side 3 earth
Side 4 earth
Side 5 earth MeasLoc.1 earth MeasLoc.2 earth MeasLoc.3 earth MeasLoc.4 earth MeasLoc.5 earth
Not connected Auxiliary CT IX4 is used as
255 AUX CT IX3 TYPE   1A/5A input
sensitiv input
1A/5A input Type of auxiliary CT IX3
256 AUX CT IX4 TYPE   1A/5A input
sensitiv input
1A/5A input Type of auxiliary CT IX4
261 VT SET   Not connected
Side 1
Side 2
Side 3
Measuring loc.1
Measuring loc.2
Measuring loc.3
Busbar
Measuring loc.1 VT set UL1, UL2, UL3 is assigned
262 VT U4   Not connected
Side 1
Side 2
Side 3
Measuring loc.1
Measuring loc.2
Measuring loc.3
Busbar
Measuring loc.1 VT U4 is assigned
263 VT U4 TYPE   Udelta transf.
UL1E transform.
UL2E transform.
UL3E transform.
UL12 transform.
UL23 transform.
UL31 transform.
Ux transformer
Udelta transf. VT U4 is used as
270 Rated Frequency   50 Hz
60 Hz
16,7 Hz
50 Hz Rated Frequency
271 PHASE SEQ.   L1 L2 L3
L1 L3 L2
L1 L2 L3 Phase Sequence
276 TEMP. UNIT   Celsius
Fahrenheit
Celsius Unit of temperature measurement
311 UN-PRI SIDE 1   0.4 .. 800.0 kV 110.0 kV Rated Primary Voltage Side 1
312 SN SIDE 1   0.20 .. 5000.00 MVA 38.10 MVA Rated Apparent Power of Transf. Side 1
313 STARPNT SIDE 1   Earthed
Isolated
Earthed Starpoint of Side 1 is
314 CONNECTION S1   Y
D
Z
Y Transf. Winding Connection Side 1
321 UN-PRI SIDE 2   0.4 .. 800.0 kV 11.0 kV Rated Primary Voltage Side 2
322 SN SIDE 2   0.20 .. 5000.00 MVA 38.10 MVA Rated Apparent Power of Transf. Side 2
323 STARPNT SIDE 2   Earthed
Isolated
Earthed Starpoint of Side 2 is
324 CONNECTION S2   Y
D
Z
Y Transf. Winding Connection Side 2
325 VECTOR GRP S2   0
1
2
3
4
5
6
7
8
9
10
11
0 Vector Group Numeral of Side 2
331 UN-PRI SIDE 3   0.4 .. 800.0 kV 11.0 kV Rated Primary Voltage Side 3
332 SN SIDE 3   0.20 .. 5000.00 MVA 10.00 MVA Rated Apparent Power of Transf. Side 3
333 STARPNT SIDE 3   Earthed
Isolated
Earthed Starpoint of Side 3 is
334 CONNECTION S3   Y
D
Z
Y Transf. Winding Connection Side 3
335 VECTOR GRP S3   0
1
2
3
4
5
6
7
8
9
10
11
0 Vector Group Numeral of Side 3
341 UN-PRI SIDE 4   0.4 .. 800.0 kV 11.0 kV Rated Primary Voltage Side 4
342 SN SIDE 4   0.20 .. 5000.00 MVA 10.00 MVA Rated Apparent Power of Transf. Side 4
343 STARPNT SIDE 4   Earthed
Isolated
Earthed Starpoint of Side 4 is
344 CONNECTION S4   Y
D
Z
Y Transf. Winding Connection Side 4
345 VECTOR GRP S4   0
1
2
3
4
5
6
7
8
9
10
11
0 Vector Group Numeral of Side 4
351 UN-PRI SIDE 5   0.4 .. 800.0 kV 11.0 kV Rated Primary Voltage Side 5
352 SN SIDE 5   0.20 .. 5000.00 MVA 10.00 MVA Rated Apparent Power of Transf. Side 5
353 STARPNT SIDE 5   Earthed
Isolated
Earthed Starpoint of Side 5 is
354 CONNECTION S5   Y
D
Z
Y Transf. Winding Connection Side 5
355 VECTOR GRP S5   0
1
2
3
4
5
6
7
8
9
10
11
0 Vector Group Numeral of Side 5
361 UN GEN/MOTOR   0.4 .. 800.0 kV 21.0 kV Rated Primary Voltage Generator/ Motor
362 SN GEN/MOTOR   0.20 .. 5000.00 MVA 70.00 MVA Rated Apparent Power of the Generator
370 UN BUSBAR   0.4 .. 800.0 kV 110.0 kV Rated Primary Voltage Busbar
371 I PRIMARY OP.   1 .. 100000 A 200 A Primary Operating Current of Busbar
372 I PRIMARY OP S1   1 .. 100000 A 200 A Primary Operating Current Side 1
373 I PRIMARY OP S2   1 .. 100000 A 200 A Primary Operating Current Side 2
374 I PRIMARY OP S3   1 .. 100000 A 200 A Primary Operating Current Side 3
375 I PRIMARY OP S4   1 .. 100000 A 200 A Primary Operating Current Side 4
376 I PRIMARY OP S5   1 .. 100000 A 200 A Primary Operating Current Side 5
381 I PRIMARY OP 1   1 .. 100000 A 200 A Primary Operating Current End 1
382 I PRIMARY OP 2   1 .. 100000 A 200 A Primary Operating Current End 2
383 I PRIMARY OP 3   1 .. 100000 A 200 A Primary Operating Current End 3
384 I PRIMARY OP 4   1 .. 100000 A 200 A Primary Operating Current End 4
385 I PRIMARY OP 5   1 .. 100000 A 200 A Primary Operating Current End 5
386 I PRIMARY OP 6   1 .. 100000 A 200 A Primary Operating Current End 6
387 I PRIMARY OP 7   1 .. 100000 A 200 A Primary Operating Current End 7
388 I PRIMARY OP 8   1 .. 100000 A 200 A Primary Operating Current End 8
389 I PRIMARY OP 9   1 .. 100000 A 200 A Primary Operating Current End 9
390 I PRIMARY OP 10   1 .. 100000 A 200 A Primary Operating Current End 10
391 I PRIMARY OP 11   1 .. 100000 A 200 A Primary Operating Current End 11
392 I PRIMARY OP 12   1 .. 100000 A 200 A Primary Operating Current End 12
396 PHASE SELECTION   Phase 1
Phase 2
Phase 3
Phase 1 Phase selection
403 I PRIMARY OP M3   1 .. 100000 A 200 A Primary Operating Current Meas. Loc. 3
404 I PRIMARY OP M4   1 .. 100000 A 200 A Primary Operating Current Meas. Loc. 4
405 I PRIMARY OP M5   1 .. 100000 A 200 A Primary Operating Current Meas. Loc. 5
408 UN-PRI M3   0.4 .. 800.0 kV 110.0 kV Rated Primary Voltage Measuring Loc. 3
409 UN-PRI U4   0.4 .. 800.0 kV 110.0 kV Rated Primary Voltage U4
413 REF PROT. AT   Side 1
Side 2
Side 3
Side 4
Side 5
auto-connected
n.assigMeasLoc3
n.assigMeasLoc4
n.assigMeasLoc5
Side 1 Restricted earth fault prot. assigned to
414 REF PROT. 2 AT   Side 1
Side 2
Side 3
Side 4
Side 5
auto-connected
n.assigMeasLoc3
n.assigMeasLoc4
n.assigMeasLoc5
Side 1 Restricted earth fault prot2 assigned to
420 DMT/IDMT Ph AT   Side 1
Side 2
Side 3
Side 4
Side 5
Measuring loc.1
Measuring loc.2
Measuring loc.3
Measuring loc.4
Measuring loc.5
Side 1 DMT / IDMT Phase assigned to
422 DMT/IDMT 3I0 AT   Side 1
Side 2
Side 3
Side 4
Side 5
Measuring loc.1
Measuring loc.2
Measuring loc.3
Measuring loc.4
Measuring loc.5
Side 1 DMT / IDMT 3I0 assigned to
424 DMT/IDMT E AT   no assig. poss.
AuxiliaryCT IX1
AuxiliaryCT IX2
AuxiliaryCT IX3
AuxiliaryCT IX4
AuxiliaryCT IX1 DMT / IDMT Earth assigned to
427 DMT 1PHASE AT   no assig. poss.
AuxiliaryCT IX1
AuxiliaryCT IX2
AuxiliaryCT IX3
AuxiliaryCT IX4
AuxiliaryCT IX1 DMT 1Phase assigned to
430 DMT/IDMT Ph2 AT   Side 1
Side 2
Side 3
Side 4
Side 5
Measuring loc.1
Measuring loc.2
Measuring loc.3
Measuring loc.4
Measuring loc.5
Side 1 DMT / IDMT Phase 2 assigned to
432 DMT/IDMT Ph3 AT   Side 1
Side 2
Side 3
Side 4
Side 5
Measuring loc.1
Measuring loc.2
Measuring loc.3
Measuring loc.4
Measuring loc.5
Side 1 DMT / IDMT Phase 3 assigned to
434 DMT/IDMT3I0-2AT   Side 1
Side 2
Side 3
Side 4
Side 5
Measuring loc.1
Measuring loc.2
Measuring loc.3
Measuring loc.4
Measuring loc.5
Side 1 DMT / IDMT 3I0 2 assigned to
436 DMT/IDMT3I0-3AT   Side 1
Side 2
Side 3
Side 4
Side 5
Measuring loc.1
Measuring loc.2
Measuring loc.3
Measuring loc.4
Measuring loc.5
Side 1 DMT / IDMT 3I0 3 assigned to
438 DMT/IDMT E2 AT   no assig. poss.
AuxiliaryCT IX1
AuxiliaryCT IX2
AuxiliaryCT IX3
AuxiliaryCT IX4
AuxiliaryCT IX1 DMT / IDMT Earth 2 assigned to
440 UNBAL. LOAD AT   Side 1
Side 2
Side 3
Side 4
Side 5
Measuring loc.1
Measuring loc.2
Measuring loc.3
Measuring loc.4
Measuring loc.5
Side 1 Unbalance Load (Neg. Seq.) assigned to
442 THERM. O/L AT   Side 1
Side 2
Side 3
Side 4
Side 5
Side 1 Thermal Overload Protection assigned to
444 THERM. O/L 2 AT   Side 1
Side 2
Side 3
Side 4
Side 5
Side 1 Thermal Overload Protection2 assigned to
470 BREAKER FAIL.AT   Side 1
Side 2
Side 3
Side 4
Side 5
Measuring loc.1
Measuring loc.2
Measuring loc.3
Measuring loc.4
Measuring loc.5
Ext. switchg. 1
Side 1 Breaker Failure Protection assigned to
471 BREAKER FAIL2AT   Side 1
Side 2
Side 3
Side 4
Side 5 Measuring loc.1 Measuring loc.2 Measuring loc.3 Measuring loc.4 Measuring loc.5 Ext. switchg. 1
Side 1 Breaker Failure Protection 2 assigned to
511 STRPNT->OBJ M1   YES
NO
YES CT-Strpnt. Meas. Loc.1 in Dir. of Object
512 IN-PRI CT M1   1 .. 100000 A 200 A CT Rated Primary Current Meas. Loc. 1
513 IN-SEC CT M1   1A
5A
1A CT Rated Secondary Current Meas. Loc. 1
521 STRPNT->OBJ M2   YES
NO
YES CT-Strpnt. Meas. Loc.2 in Dir. of Object
522 IN-PRI CT M2   1 .. 100000 A 2000 A CT Rated Primary Current Meas. Loc. 2
523 IN-SEC CT M2   1A
5A
1A CT Rated Secondary Current Meas. Loc. 2
531 STRPNT->OBJ M3   YES
NO
YES CT-Strpnt. Meas. Loc.3 in Dir. of Object
532 IN-PRI CT M3   1 .. 100000 A 2000 A CT Rated Primary Current Meas. Loc. 3
533 IN-SEC CT M3   1A
5A
1A CT Rated Secondary Current Meas. Loc. 3
541 STRPNT->OBJ M4   YES
NO
YES CT-Strpnt. Meas. Loc.4 in Dir. of Object
542 IN-PRI CT M4   1 .. 100000 A 2000 A CT Rated Primary Current Meas. Loc. 4
543 IN-SEC CT M4   1A
5A
1A CT Rated Secondary Current Meas. Loc. 4
551 STRPNT->OBJ M5   YES
NO
YES CT-Strpnt. Meas. Loc.5 in Dir. of Object
552 IN-PRI CT M5   1 .. 100000 A 2000 A CT Rated Primary Current Meas. Loc. 5
553 IN-SEC CT M5   1A
5A
1A CT Rated Secondary Current Meas. Loc. 5
561 STRPNT->BUS I1   YES
NO
YES CT-Starpoint I1 in Direction of Busbar
562 IN-PRI CT I1   1 .. 100000 A 200 A CT Rated Primary Current I1
563 IN-SEC CT I1   1A
5A
0.1A
1A CT Rated Secondary Current I1
571 STRPNT->BUS I2   YES
NO
YES CT-Starpoint I2 in Direction of Busbar
572 IN-PRI CT I2   1 .. 100000 A 200 A CT Rated Primary Current I2
573 IN-SEC CT I2   1A
5A
0.1A
1A CT Rated Secondary Current I2
581 STRPNT->BUS I3   YES
NO
YES CT-Starpoint I3 in Direction of Busbar
582 IN-PRI CT I3   1 .. 100000 A 200 A CT Rated Primary Current I3
583 IN-SEC CT I3   1A
5A
0.1A
1A CT Rated Secondary Current I3
591 STRPNT->BUS I4   YES
NO
YES CT-Starpoint I4 in Direction of Busbar
592 IN-PRI CT I4   1 .. 100000 A 200 A CT Rated Primary Current I4
593 IN-SEC CT I4   1A
5A
0.1A
1A CT Rated Secondary Current I4
601 STRPNT->BUS I5   YES
NO
YES CT-Starpoint I5 in Direction of Busbar
602 IN-PRI CT I5   1 .. 100000 A 200 A CT Rated Primary Current I5
603 IN-SEC CT I5   1A
5A
0.1A
1A CT Rated Secondary Current I5
611 STRPNT->BUS I6   YES
NO
YES CT-Starpoint I6 in Direction of Busbar
612 IN-PRI CT I6   1 .. 100000 A 200 A CT Rated Primary Current I6
613 IN-SEC CT I6   1A
5A
0.1A
1A CT Rated Secondary Current I6
621 STRPNT->BUS I7   YES
NO
YES CT-Starpoint I7 in Direction of Busbar
622 IN-PRI CT I7   1 .. 100000 A 200 A CT Rated Primary Current I7
623 IN-SEC CT I7   1A
5A
0.1A
1A CT Rated Secondary Current I7
631 STRPNT->BUS I8   YES
NO
YES CT-Starpoint I8 in Direction of Busbar
632 IN-PRI CT I8   1 .. 100000 A 200 A CT Rated Primary Current I8
633 IN-SEC CT I8   1A
5A
0.1A
1A CT Rated Secondary Current I8
641 STRPNT->BUS I9   YES
NO
YES CT-Starpoint I9 in Direction of Busbar
642 IN-PRI CT I9   1 .. 100000 A 200 A CT Rated Primary Current I9
643 IN-SEC CT I9   1A
5A
0.1A
1A CT Rated Secondary Current I9
651 STRPNT->BUS I10   YES
NO
YES CT-Starpoint I10 in Direction of Busbar
652 IN-PRI CT I10   1 .. 100000 A 200 A CT Rated Primary Current I10
653 IN-SEC CT I10   1A
5A
0.1A
1A CT Rated Secondary Current I10
661 STRPNT->BUS I11   YES
NO
YES CT-Starpoint I11 in Direction of Busbar
662 IN-PRI CT I11   1 .. 100000 A 200 A CT Rated Primary Current I11
663 IN-SEC CT I11   1A
5A
0.1A
1A CT Rated Secondary Current I11
671 STRPNT->BUS I12   YES
NO
YES CT-Starpoint I12 in Direction of Busbar
672 IN-PRI CT I12   1 .. 100000 A 200 A CT Rated Primary Current I12
673 IN-SEC CT I12   1A
5A
0.1A
1A CT Rated Secondary Current I12
711 EARTH IX1 AT   Terminal Q7
Terminal Q8
Terminal Q7 Earthing electrod IX1 connected to
712 IN-PRI CT IX1   1 .. 100000 A 200 A CT rated primary current IX1
713 IN-SEC CT IX1   1A
5A
1A CT rated secondary current IX1
721 EARTH IX2 AT   Terminal N7
Terminal N8
Terminal N7 Earthing electrod IX2 connected to
722 IN-PRI CT IX2   1 .. 100000 A 200 A CT rated primary current IX2
723 IN-SEC CT IX2   1A
5A
1A CT rated secondary current IX2
731 EARTH IX3 AT   Terminal R7
Terminal R8
Terminal R7 Earthing electrod IX3 connected to
732 IN-PRI CT IX3   1 .. 100000 A 200 A CT rated primary current IX3
733 IN-SEC CT IX3   1A
5A
1A CT rated secondary current IX3
734 FACTOR CT IX3   1.0 .. 300.0 60.0 Factor: prim. over sek. current IX3
741 EARTH IX4 AT   Terminal P7
Terminal P8
Terminal P7 Earthing electrod IX4 connected to
742 IN-PRI CT IX4   1 .. 100000 A 200 A CT rated primary current IX4
743 IN-SEC CT IX4   1A
5A
1A CT rated secondary current IX4
744 FACTOR CT IX4   1.0 .. 300.0 60.0 Factor: prim. over sek. current IX4
801 UN-PRI VT SET   0.1 .. 1200.0 kV 110.0 kV VT Rated Prim. Voltage Set UL1, UL2, UL3
802 UN-SEC VT SET   80 .. 125 V 100 V VT Rated Sec. Voltage Set UL1, UL2, UL3
803 CORRECT. U Ang   -5.00 .. 5.00 ° 0.00 ° Angle correction UL1, UL2, UL3 – VT
811 UN-PRI VT U4   0.1 .. 1200.0 kV 110.0 kV VT Rated Primary Voltage U4
812 UN-SEC VT U4   80 .. 125 V 100 V VT Rated Secondary Voltage U4
816 Uph / Udelta   0.10 .. 9.99 1.73 Matching ratio Phase-VT to Open- Delta-VT
817 Uph(U4)/Udelta   0.10 .. 9.99 1.73 Matching ratio Ph-VT(U4) to Open- DeltaVT
831 SwitchgCBaux S1   (Einstellmoglichkeiten anwendungsabhangig)   Switchgear / CBaux at Side 1
832 SwitchgCBaux S2   (Einstellmoglichkeiten anwendungsabhangig) none Switchgear / CBaux at Side 2
833 SwitchgCBaux S3   (Einstellmoglichkeiten anwendungsabhangig) none Switchgear / CBaux at Side 3
834 SwitchgCBaux S4   (Einstellmoglichkeiten anwendungsabhangig) none Switchgear / CBaux at Side 4
835 SwitchgCBaux S5   (Einstellmoglichkeiten anwendungsabhangig) none Switchgear / CBaux at Side 5
836 SwitchgCBaux M1   (Einstellmoglichkeiten anwendungsabhangig) none Switchgear / CBaux at Measuring Loc. M1
837 SwitchgCBaux M2   (Einstellmoglichkeiten anwendungsabhangig) none Switchgear / CBaux at Measuring Loc. M2
838 SwitchgCBaux M3   (Einstellmoglichkeiten anwendungsabhangig) none Switchgear / CBaux at Measuring Loc. M3
839 SwitchgCBaux M4   (Einstellmoglichkeiten anwendungsabhangig) none Switchgear / CBaux at Measuring Loc. M4
840 SwitchgCBaux M5   (Einstellmoglichkeiten anwendungsabhangig) none Switchgear / CBaux at Measuring Loc. M5
841 SwitchgCBaux E1   (Einstellmoglichkeiten anwendungsabhangig) none Switchgear / CBaux at ext. location 1
851A TMin TRIP CMD   0.01 .. 32.00 sec 0.15 sec Minimum TRIP Command Duration

Setting Groups

Addr. Parameter C Setting Options Default Setting Comments
302 CHANGE   Group A
Group B
Group C
Group D
Binary Input
Protocol
Group A Change to Another Setting Group

Power System Data 2

Addr. Parameter C Setting Options Default Setting Comments
1107 P,Q sign   not reversed
reversed
not reversed sign of P,Q
1111 PoleOpenCurr.S1   0.04 .. 1.00 I/InS 0.10 I/InS Pole Open Current Threshold Side 1
1112 PoleOpenCurr.S2   0.04 .. 1.00 I/InS 0.10 I/InS Pole Open Current Threshold Side 2
1113 PoleOpenCurr.S3   0.04 .. 1.00 I/InS 0.16 I/InS Pole Open Current Threshold Side 3
1114 PoleOpenCurr.S4   0.04 .. 1.00 I/InS 0.16 I/InS Pole Open Current Threshold Side 4
1115 PoleOpenCurr.S5   0.04 .. 1.00 I/InS 0.16 I/InS Pole Open Current Threshold Side 5
1121 PoleOpenCurr.M1 1A 0.04 .. 1.00 A 0.04 A Pole Open Current Threshold Meas.Loc. M1
5A 0.20 .. 5.00 A 0.20 A  
1122 PoleOpenCurr.M2 1A 0.04 .. 1.00 A 0.04 A Pole Open Current Threshold Meas.Loc. M2
5A 0.20 .. 5.00 A 0.20 A  
1123 PoleOpenCurr.M3 1A 0.04 .. 1.00 A 0.04 A Pole Open Current Threshold Meas.Loc. M3
5A 0.20 .. 5.00 A 0.20 A  
1124 PoleOpenCurr.M4 1A 0.04 .. 1.00 A 0.04 A Pole Open Current Threshold Meas.Loc. M4
5A 0.20 .. 5.00 A 0.20 A  
1125 PoleOpenCurr.M5 1A 0.04 .. 1.00 A 0.04 A Pole Open Current Threshold Meas.Loc. M5
5A 0.20 .. 5.00 A 0.20 A  
1131 PoleOpenCurr I1 1A 0.04 .. 1.00 A 0.04 A Pole Open Current Threshold End 1
5A 0.20 .. 5.00 A 0.20 A  
0.1A 0.004 .. 0.100 A 0.004 A  
1132 PoleOpenCurr I2 1A 0.04 .. 1.00 A 0.04 A Pole Open Current Threshold End 2
5A 0.20 .. 5.00 A 0.20 A  
0.1A 0.004 .. 0.100 A 0.004 A  
1133 PoleOpenCurr I3 1A 0.04 .. 1.00 A 0.04 A Pole Open Current Threshold End 3
5A 0.20 .. 5.00 A 0.20 A  
0.1A 0.004 .. 0.100 A 0.004 A  
1134 PoleOpenCurr I4 1A 0.04 .. 1.00 A 0.04 A Pole Open Current Threshold End 4
5A 0.20 .. 5.00 A 0.20 A  
0.1A 0.004 .. 0.100 A 0.004 A  
1135 PoleOpenCurr I5 1A 0.04 .. 1.00 A 0.04 A Pole Open Current Threshold End 5
5A 0.20 .. 5.00 A 0.20 A  
0.1A 0.004 .. 0.100 A 0.004 A  
1136 PoleOpenCurr I6 1A 0.04 .. 1.00 A 0.04 A Pole Open Current Threshold End 6
5A 0.20 .. 5.00 A 0.20 A
0.1A 0.004 .. 0.100 A 0.004 A
1137 PoleOpenCurr I7 1A 0.04 .. 1.00 A 0.04 A Pole Open Current Threshold End 7
5A 0.20 .. 5.00 A 0.20 A
0.1A 0.004 .. 0.100 A 0.004 A
1138 PoleOpenCurr I8 1A 0.04 .. 1.00 A 0.04 A Pole Open Current Threshold End 8
5A 0.20 .. 5.00 A 0.20 A
0.1A 0.004 .. 0.100 A 0.004 A
1139 PoleOpenCurr I9 1A 0.04 .. 1.00 A 0.04 A Pole Open Current Threshold End 9
5A 0.20 .. 5.00 A 0.20 A
0.1A 0.004 .. 0.100 A 0.004 A
1140 PoleOpenCurrI10 1A 0.04 .. 1.00 A 0.04 A Pole Open Current Threshold End 10
5A 0.20 .. 5.00 A 0.20 A
0.1A 0.004 .. 0.100 A 0.004 A
1141 PoleOpenCurrI11 1A 0.04 .. 1.00 A 0.04 A Pole Open Current Threshold End 11
5A 0.20 .. 5.00 A 0.20 A
0.1A 0.004 .. 0.100 A 0.004 A
1142 PoleOpenCurrI12 1A 0.04 .. 1.00 A 0.04 A Pole Open Current Threshold End 12
5A 0.20 .. 5.00 A 0.20 A
0.1A 0.004 .. 0.100 A 0.004 A
1151 PoleOpenCurrIX1 1A 0.04 .. 1.00 A 0.04 A Pole Open Current Threshold AuxiliaryCT1
5A 0.20 .. 5.00 A 0.20 A
1152 PoleOpenCurrIX2 1A 0.04 .. 1.00 A 0.04 A Pole Open Current Threshold AuxiliaryCT2
5A 0.20 .. 5.00 A 0.20 A
1153 PoleOpenCurrIX3 1A 0.04 .. 1.00 A 0.04 A Pole Open Current Threshold AuxiliaryCT3
5A 0.20 .. 5.00 A 0.20 A
1154 PoleOpenCurrIX4 1A 0.04 .. 1.00 A 0.04 A Pole Open Current Threshold AuxiliaryCT4
5A 0.20 .. 5.00 A 0.20 A

Differential Protection

Addr. Parameter C Setting Options Default Setting Comments
1201 DIFF. PROT.   OFF
ON
Block relay
OFF Differential Protection
1205 INC.CHAR.START   OFF
ON
OFF Increase of Trip Char. During Start
1206 INRUSH 2.HARM.   OFF
ON
ON Inrush with 2. Harmonic Restraint
1207 RESTR. n.HARM.   OFF
3. Harmonic
5. Harmonic
OFF n-th Harmonic Restraint
1208 I-DIFF> MON.   OFF
ON
ON Differential Current monitoring
1210 I> CURR. GUARD   0.20 .. 2.00 I/InS; 0 0.00 I/InS I> for Current Guard
1211A DIFFw.IE1-MEAS   NO
YES
NO Diff-Prot. with meas. Earth Current S1
1212A DIFFw.IE2-MEAS   NO
YES
NO Diff-Prot. with meas. Earth Current S2
1213A DIFFw.IE3-MEAS   NO
YES
NO Diff-Prot. with meas. Earth Current S3
1214A DIFFw.IE4-MEAS   NO
YES
NO Diff-Prot. with meas. Earth Current S4
1215A DIFFw.IE5-MEAS   NO
YES
NO Diff-Prot. with meas. Earth Current S5
1216A DIFFw.IE3phMEAS   NO
YES
NO Diff-Prot.with meas.current earth.electr
1221 I-DIFF>   0.05 .. 2.00 I/InO 0.20 I/InO Pickup Value of Differential Curr.
1226A T I-DIFF>   0.00 .. 60.00 sec; ∞ 0.00 sec T I-DIFF> Time Delay
1231 I-DIFF>>   0.5 .. 35.0 I/InO; ∞ 7.5 I/InO Pickup Value of High Set Trip
1236A T I-DIFF>>   0.00 .. 60.00 sec; ∞ 0.00 sec T I-DIFF>> Time Delay
1241A SLOPE 1   0.10 .. 0.50 0.25 Slope 1 of Tripping Characteristic
1242A BASE POINT 1   0.00 .. 2.00 I/InO 0.00 I/InO Base Point for Slope 1 of Charac.
1243A SLOPE 2   0.25 .. 0.95 0.50 Slope 2 of Tripping Characteristic
1244A BASE POINT 2   0.00 .. 10.00 I/InO 2.50 I/InO Base Point for Slope 2 of Charac.
1251A I-REST. STARTUP   0.00 .. 2.00 I/InO 0.10 I/InO I-RESTRAINT for Start Detection
1252A START-FACTOR   1.0 .. 2.0 1.0 Factor for Increasing of Char. at Start
1253 T START MAX   0.0 .. 180.0 sec 5.0 sec Maximum Permissible Starting Time
1261A I-ADD ON STAB.   2.00 .. 15.00 I/InO 4.00 I/InO Pickup for Add-on Stabilization
1262A T ADD ON-STAB.   2 .. 250 Cycle; ∞ 15 Cycle Duration of Add-on Stabilization
1263A CROSSB. ADD ON   2 .. 1000 Cycle; 0; ∞ 15 Cycle Time for Cross-blocking Add-on Stabiliz.
1271 2. HARMONIC   10 .. 80 % 15 % 2nd Harmonic Content in I-DIFF
1272A CROSSB. 2. HARM   2 .. 1000 Cycle; 0; ∞ 3 Cycle Time for Cross-blocking 2nd Harm.
1276 n. HARMONIC   10 .. 80 % 30 % n-th Harmonic Content in I-DIFF
1277A CROSSB. n.HARM   2 .. 1000 Cycle; 0; ∞ 0 Cycle Time for Cross-blocking n-th Harm.
1278A IDIFFmax n.HM   0.5 .. 20.0 I/InO 1.5 I/InO Limit IDIFFmax of n-th Harm.Restraint
1281 I-DIFF> MON.   0.15 .. 0.80 I/InO 0.20 I/InO Pickup Value of diff. Current Moni- toring
1282 T I-DIFF> MON.   1 .. 10 sec 2 sec T I-DIFF> Monitoring Time Delay
1283A Inst. Idiff Rec   NO
YES
NO Fault record with inst. diff current
1300 Blocked w. CWA   ON
OFF
ON Blocking with CWA

Restricted Earth Fault Protection

Addr. Parameter C Setting Options Default Setting Comments
1301 REF PROT.   OFF
ON
Block relay
OFF Restricted Earth Fault Protection
1311 I-REF>   0.05 .. 2.00 I/InS 0.15 I/InS Pick up value I REF>
1312A T I-REF>   0.00 .. 60.00 sec; ∞ 0.00 sec T I-REF> Time Delay
1313A SLOPE   0.00 .. 0.95 0.00 Slope of Charac. I-REF> = f(I-SUM)

Time Overcurrent Protection for Phase Currents

Addr. Parameter C Setting Options Default Setting Comments
2001 PHASE O/C   ON
OFF
Block relay
OFF Phase Time Overcurrent
2002 InRushRest. Ph   ON
OFF
OFF InRush Restrained O/C Phase
2008A MANUAL CLOSE   I>> instant.
I> instant.
Ip instant.
Inactive
I>> instant. O/C Manual Close Mode
2011 I>> 1A 0.10 .. 35.00 A; ∞ 4.00 A I>> Pickup
5A 0.50 .. 175.00 A; ∞ 20.00 A
2012 I>>   0.10 .. 35.00 I/InS; ∞ 4.00 I/InS I>> Pickup
2013 T I>>   0.00 .. 60.00 sec; ∞ 0.10 sec T I>> Time Delay
2014 I> 1A 0.10 .. 35.00 A; ∞ 2.00 A I> Pickup
5A 0.50 .. 175.00 A; ∞ 10.00 A
2015 I>   0.10 .. 35.00 I/InS; ∞ 2.00 I/InS I> Pickup
2016 T I>   0.00 .. 60.00 sec; ∞ 0.30 sec T I> Time Delay
2021 Ip 1A 0.10 .. 4.00 A 2.00 A Ip Pickup
5A 0.50 .. 20.00 A 10.00 A
2022 Ip   0.10 .. 4.00 I/InS 2.00 I/InS Ip Pickup
2023 T Ip   0.05 .. 3.20 sec; ∞ 0.50 sec T Ip Time Dial
2024 D Ip   0.50 .. 15.00 ; ∞ 5.00 D Ip Time Dial
2025 TOC DROP-OUT   Instantaneous
Disk Emulation
Disk Emulation TOC Drop-out characteristic
2026 IEC CURVE   Normal Inverse
Very Inverse
Extremely Inv.
Long Inverse
Normal Inverse IEC Curve
2027 ANSI CURVE   Very Inverse
Inverse
Short Inverse
Long Inverse
Moderately Inv.
Extremely Inv.
Definite Inv.
Very Inverse ANSI Curve
2031 I/Ip PU T/Tp   1.00 .. 20.00 I/Ip; ∞
0.01 .. 999.00 TD
  Pickup Curve I/Ip – TI/TIp
2032 MofPU Res T/Tp   0.05 .. 0.95 I/Ip; ∞
0.01 .. 999.00 TD
  Multiple of Pickup <-> TI/TIp
2041 2.HARM. Phase   10 .. 45 % 15 % 2nd harmonic O/C Ph. in % of fundamental
2042 I Max InRr. Ph. 1A 0.30 .. 25.00 A 7.50 A Maximum Current for Inr. Rest. O/C Phase
5A 1.50 .. 125.00 A 37.50 A
2043 I Max InRr. Ph.   0.30 .. 25.00 I/InS 7.50 I/InS Maximum Current for Inr. Rest. O/C Phase
2044 CROSS BLK.Phase   NO
YES
NO CROSS BLOCK O/C Phase
2045 T CROSS BLK.Ph   0.00 .. 180.00 sec 0.00 sec CROSS BLOCK Time O/C
Phase
2111 I>> 1A 0.10 .. 35.00 A; ∞ 10.00 A I>> Pickup
5A 0.50 .. 175.00 A; ∞ 50.00 A
2112 I>>   0.10 .. 35.00 I/InS; ∞ 10.00 I/InS I>> Pickup
2113 T I>>   0.00 .. 60.00 sec; ∞ 0.10 sec T I>> Time Delay
2114 I> 1A 0.10 .. 35.00 A; ∞ 4.00 A I> Pickup
5A 0.50 .. 175.00 A; ∞ 20.00 A
2115 I>   0.10 .. 35.00 I/InS; ∞ 4.00 I/InS I> Pickup
2116 T I>   0.00 .. 60.00 sec; ∞ 0.30 sec T I> Time Delay
2121 Ip 1A 0.10 .. 4.00 A 4.00 A Ip Pickup
5A 0.50 .. 20.00 A 20.00 A
2122 Ip   0.10 .. 4.00 I/InS 4.00 I/InS Ip Pickup
2123 T Ip   0.05 .. 3.20 sec; ∞ 0.50 sec T Ip Time Dial
2124 D Ip   0.50 .. 15.00 ; ∞ 5.00 D Ip Time Dial

Time Overcurrent Protection for Residual Current

Addr. Parameter C Setting Options Default Setting Comments
2201 3I0 O/C   ON
OFF
Block relay
OFF 3I0 Time Overcurrent
2202 InRushRest. 3I0   ON OFF OFF InRush Restrained O/C 3I0
2208A 3I0 MAN. CLOSE   3I0>> instant.
3I0> instant.
3I0p instant.
Inactive
3I0>> instant. O/C 3I0 Manual Close Mode
2211 3I0>> 1A 0.05 .. 35.00 A; ∞ 1.00 A 3I0>> Pickup
5A 0.25 .. 175.00 A; ∞ 5.00 A
2212 3I0>>   0.05 .. 35.00 I/InS; ∞ 1.00 I/InS 3I0>> Pickup
2213 T 3I0>>   0.00 .. 60.00 sec; ∞ 1.50 sec T 3I0>> Time Delay
2214 3I0> 1A 0.05 .. 35.00 A; ∞ 0.40 A 3I0> Pickup
5A 0.25 .. 175.00 A; ∞ 2.00 A
2215 3I0>   0.05 .. 35.00 I/InS; ∞ 0.40 I/InS 3I0> Pickup
2216 T 3I0>   0.00 .. 60.00 sec; ∞ 2.00 sec T 3I0> Time Delay
2221 3I0p 1A 0.05 .. 4.00 A 0.40 A 3I0p Pickup
5A 0.25 .. 20.00 A 2.00 A
2222 3I0p   0.05 .. 4.00 I/InS 0.40 I/InS 3I0p Pickup
2223 T 3I0p   0.05 .. 3.20 sec; ∞ 0.50 sec T 3I0p Time Dial
2224 D 3I0p   0.50 .. 15.00 ; ∞ 5.00 D 3I0p Time Dial
2225 TOC DROP-OUT   Instantaneous
Disk Emulation
Disk Emulation TOC Drop-out Character- istic
2226 IEC CURVE   Normal Inverse
Very Inverse
Extremely Inv.
Long Inverse
Normal Inverse IEC Curve
2227 ANSI CURVE   Very Inverse
Inverse
Short Inverse
Long Inverse
Moderately Inv.
Extremely Inv.
Definite Inv.
Very Inverse ANSI Curve
2231 I/I0p PU T/TI0p   1.00 .. 20.00 I/Ip; ∞
0.01 .. 999.00 TD
  Pickup Curve 3I0/3I0p – T3I0/T3I0p
2232 MofPU ResT/TI0p   0.05 .. 0.95 I/Ip; ∞
0.01 .. 999.00 TD
  Multiple of Pickup <-> T3I0/ T3I0p
2241 2.HARM. 3I0   10 .. 45 % 15 % 2nd harmonic O/C 3I0 in % of fundamental
2242 I Max InRr. 3I0 1A 0.30 .. 25.00 A 7.50 A Maximum Current for Inr. Rest. O/C 3I0
5A 1.50 .. 125.00 A 37.50 A
2243 I Max InRr. 3I0   0.30 .. 25.00 I/InS 7.50 I/InS Maximum Current for Inr. Rest. O/C 3I0
2311 3I0>> 1A 0.05 .. 35.00 A; ∞ 7.00 A 3I0>> Pickup
5A 0.25 .. 175.00 A; ∞ 35.00 A
2312 3I0>>   0.05 .. 35.00 I/InS; ∞ 7.00 I/InS 3I0>> Pickup
2313 T 3I0>>   0.00 .. 60.00 sec; ∞ 1.50 sec T 3I0>> Time Delay
2314 3I0> 1A 0.05 .. 35.00 A; ∞ 1.50 A 3I0> Pickup
5A 0.25 .. 175.00 A; ∞ 7.50 A
2315 3I0>   0.05 .. 35.00 I/InS; ∞ 1.50 I/InS 3I0> Pickup
2316 T 3I0>   0.00 .. 60.00 sec; ∞ 2.00 sec T 3I0> Time Delay
2321 3I0p 1A 0.05 .. 4.00 A 1.00 A 3I0p Pickup
5A 0.25 .. 20.00 A 5.00 A
2322 3I0p   0.05 .. 4.00 I/InS 1.00 I/InS 3I0p Pickup
2323 T 3I0p   0.05 .. 3.20 sec; ∞ 0.50 sec T 3I0p Time Dial
2324 D 3I0p   0.50 .. 15.00 ; ∞ 5.00 D 3I0p Time Dial

Time Overcurrent Protection for Earth Current

Addr. Parameter C Setting Options Default Setting Comments
2401 EARTH O/C   ON
OFF
Block relay
OFF Earth Time Overcurrent
2402 InRushRestEarth   ON
OFF
OFF InRush Restrained O/C Earth
2408A IE MAN. CLOSE   IE>> instant.
IE> instant.
IEp instant.
Inactive
IE>> instant. O/C IE Manual Close Mode
2411 IE>> 1A 0.05 .. 35.00 A; ∞ 1.00 A IE>> Pickup
5A 0.25 .. 175.00 A; ∞ 5.00 A
2412 T IE>>   0.00 .. 60.00 sec; ∞ 1.50 sec T IE>> Time Delay
2413 IE> 1A 0.05 .. 35.00 A; ∞ 0.40 A IE> Pickup
5A 0.25 .. 175.00 A; ∞ 2.00 A
2414 T IE>   0.00 .. 60.00 sec; ∞ 2.00 sec T IE> Time Delay
2421 IEp 1A 0.05 .. 4.00 A 0.40 A IEp Pickup
5A 0.25 .. 20.00 A 2.00 A
2422 T IEp   0.05 .. 3.20 sec; ∞ 0.50 sec T IEp Time Dial
2423 D IEp   0.50 .. 15.00 ; ∞ 5.00 D IEp Time Dial
2424 TOC DROP-OUT   Instantaneous
Disk Emulation
Disk Emulation TOC Drop-out Character- istic
2425 IEC CURVE   Normal Inverse
Very Inverse
Extremely Inv.
Long Inverse
Normal Inverse IEC Curve
2426 ANSI CURVE   Very Inverse
Inverse
Short Inverse
Long Inverse
Moderately Inv.
Extremely Inv.
Definite Inv.
Very Inverse ANSI Curve
2431 I/IEp PU T/TEp   1.00 .. 20.00 I/Ip; ∞
0.01 .. 999.00 TD
  Pickup Curve IE/IEp – TIE/ TIEp
2432 MofPU Res T/TEp   0.05 .. 0.95 I/Ip; ∞
0.01 .. 999.00 TD
  Multiple of Pickup <-> TI/ TIEp
2441 2.HARM. Earth   10 .. 45 % 15 % 2nd harmonic O/C E in % of fundamental
2442 I Max InRr. E 1A 0.30 .. 25.00 A 7.50 A Maximum Current for Inr. Rest. O/C Earth
5A 1.50 .. 125.00 A 37.50 A
2511 IE>> 1A 0.05 .. 35.00 A; ∞ 7.00 A IE>> Pickup
5A 0.25 .. 175.00 A; ∞ 35.00 A
2512 T IE>>   0.00 .. 60.00 sec; ∞ 1.50 sec T IE>> Time Delay
2513 IE> 1A 0.05 .. 35.00 A; ∞ 1.50 A IE> Pickup
5A 0.25 .. 175.00 A; ∞ 7.50 A
2514 T IE>   0.00 .. 60.00 sec; ∞ 2.00 sec T IE> Time Delay
2521 IEp 1A 0.05 .. 4.00 A 1.00 A IEp Pickup
5A 0.25 .. 20.00 A 5.00 A
2522 T IEp   0.05 .. 3.20 sec; ∞ 0.50 sec T IEp Time Dial
2523 D IEp   0.50 .. 15.00 ; ∞ 5.00 D IEp Time Dial

Dynamic Cold Load Pickup for Time Overcurrent Protection

Addr. Parameter C Setting Options Default Setting Comments
1701 COLDLOAD PICKUP   OFF
ON
OFF Cold-Load-Pickup Function
1702 Start CLP Phase   No Current
Breaker Contact
No Current Start Condition CLP for O/C Phase
1703 Start CLP 3I0   No Current
Breaker Contact
No Current Start Condition CLP for O/C 3I0
1704 Start CLP Earth   No Current
Breaker Contact
No Current Start Condition CLP for O/C Earth
1705 Start CLP Ph 2   No Current
Breaker Contact
No Current Start Condition CLP for O/C Phase 2
1706 Start CLP Ph 3   No Current
Breaker Contact
No Current Start Condition CLP for O/C Phase 3
1707 Start CLP 3I0 2   No Current
Breaker Contact
No Current Start Condition CLP for O/C 3I0 2
1708 Start CLP 3I0 3   No Current
Breaker Contact
No Current Start Condition CLP for O/C 3I0 3
1709 Start CLP E 2   No Current
Breaker Contact
No Current Start Condition CLP for O/C Earth 2
1711 CB Open Time   0 .. 21600 sec 3600 sec Circuit Breaker OPEN Time
1712 Active Time   1 .. 21600 sec 3600 sec Active Time
1713 Stop Time   1 .. 600 sec; ∞ 600 sec Stop Time

Single-Phase Time Overcurrent Protection

Addr. Parameter C Setting Options Default Setting Comments
2701 1Phase O/C   OFF
ON
Block relay
OFF 1Phase Time Overcurrent
2702 1Phase I>> 1A 0.05 .. 35.00 A; ∞ 0.50 A 1Phase O/C I>> Pickup
5A 0.25 .. 175.00 A; ∞ 2.50 A
2703 1Phase I>>   0.003 .. 1.500 A; ∞ 0.300 A 1Phase O/C I>> Pickup
2704 T 1Phase I>>   0.00 .. 60.00 sec; ∞ 0.10 sec T 1Phase O/C I>> Time Delay
2705 1Phase I> 1A 0.05 .. 35.00 A; ∞ 0.20 A 1Phase O/C I> Pickup
5A 0.25 .. 175.00 A; ∞ 1.00 A
2706 1Phase I>   0.003 .. 1.500 A; ∞ 0.100 A 1Phase O/C I> Pickup
2707 T 1Phase I>   0.00 .. 60.00 sec; ∞ 0.50 sec T 1Phase O/C I> Time Delay

Unbalanced Load Protection

Addr. Parameter C Setting Options Default Setting Comments
4001 UNBALANCE LOAD   OFF
ON
Block relay
OFF Unbalance Load (Negative Sequence)
4011 I2>> 1A 0.10 .. 3.00 A; ∞ 0.50 A I2>> Pickup
5A 0.50 .. 15.00 A; ∞ 2.50 A
4012 I2>>   0.10 .. 3.00 I/InS; ∞ 0.50 I/InS I2>> Pickup
4013 T I2>>   0.00 .. 60.00 sec; ∞ 1.50 sec T I2>> Time Delay
4014 I2> 1A 0.10 .. 3.00 A; ∞ 0.10 A I2> Pickup
5A 0.50 .. 15.00 A; ∞ 0.50 A
4015 I2>   0.10 .. 3.00 I/InS; ∞ 0.10 I/InS I2> Pickup
4016 T I2>   0.00 .. 60.00 sec; ∞ 1.50 sec T I2> Time Delay
4021 I2p 1A 0.10 .. 2.00 A 0.90 A I2p Pickup
5A 0.50 .. 10.00 A 4.50 A
4022 I2p   0.10 .. 2.00 I/InS 0.90 I/InS I2p Pickup
4023 T I2p   0.05 .. 3.20 sec; ∞ 0.50 sec T I2p Time Dial
4024 D I2p   0.50 .. 15.00 ; ∞ 5.00 D I2p Time Dial
4025 I2p DROP-OUT   Instantaneous
Disk Emulation
Instantaneous I2p Drop-out Characteristic
4026 IEC CURVE   Normal Inverse
Very Inverse
Extremely Inv.
Extremely Inv. IEC Curve
4027 ANSI CURVE   Extremely Inv.
Inverse
Moderately Inv.
Very Inverse
Extremely Inv. ANSI Curve
4031 I2> 1A 0.01 .. 4.00 A; ∞ 0.10 A Continously Permissible Current I2
5A 0.05 .. 20.00 A; ∞ 0.50 A
4032 I2 tolerance   0.01 .. 0.80 I/InS; ∞ 0.16 I/InS Permissable quiescent unbalanced load
4033 T WARN   0.00 .. 60.00 sec; ∞ 20.00 sec Warning Stage Time Delay
4034 FACTOR K   1.0 .. 100.0 sec; ∞ 18.7 sec Negativ Sequence Factor K
4035 T COOL DOWN   0 .. 50000 sec 1650 sec Time for Cooling Down

Thermal Overload Protection

Addr. Parameter C Setting Options Default Setting Comments
4201 THERM. OVERLOAD   OFF
ON
Block relay
Alarm Only
OFF Thermal Overload Protection
4202 K-FACTOR   0.10 .. 4.00 1.10 K-Factor
4203 TIME CONSTANT   1.0 .. 999.9 min 100.0 min Thermal Time Constant
4204 Θ ALARM   50 .. 100 % 90 % Thermal Alarm Stage
4205 I ALARM   0.10 .. 4.00 I/InS 1.00 I/InS Current Overload Alarm Setpoint
4207A Kτ-FACTOR   1.0 .. 10.0 1.0 Kt-FACTOR when motor stops
4208A T EMERGENCY   10 .. 15000 sec 100 sec Emergency Time
4209A I MOTOR START   0.60 .. 10.00 I/InS; ∞ ∞ I/InS Current Pickup Value of Motor Starting
4210 TEMPSENSOR RTD   1 .. 6 1 Temperature sensor connected to RTD
4211 TEMPSENSOR RTD   1 .. 12 1 Temperature sensor connected to RTD
4212 TEMP. RISE I   40 .. 200 °C 100 °C Temperature Rise at Rated Sec. Curr.
4213 TEMP. RISE I   104 .. 392 °F 212 °F Temperature Rise at Rated Sec. Curr.
4220 OIL-DET. RTD   1 .. 6 1 Oil-Detector conected at RTD
4221 OIL Sensor RTD   1 .. 12 1 Oil sensor connected to RTD
4222 HOT SPOT ST. 1   98 .. 140 °C 98 °C Hot Spot Temperature Stage 1 Pickup
4223 HOT SPOT ST. 1   208 .. 284 °F 208 °F Hot Spot Temperature Stage 1 Pickup
4224 HOT SPOT ST. 2   98 .. 140 °C 108 °C Hot Spot Temperature Stage 2 Pickup
4225 HOT SPOT ST. 2   208 .. 284 °F 226 °F Hot Spot Temperature Stage 2 Pickup
4226 AG. RATE ST. 1   0.200 .. 128.000 1.000 Aging Rate STAGE 1 Pickup
4227 AG. RATE ST. 2   0.200 .. 128.000 2.000 Aging Rate STAGE 2 Pickup
4231 METH. COOLING   ON
OF
OD
ON Method of Cooling
4232 Y-WIND.EXPONENT   1.6 .. 2.0 1.6 Y-Winding Exponent
4233 HOT-SPOT GR   22 .. 29 22 Hot-spot to top-oil gradient

RTD-Boxes for Overload Detection

Addr. Parameter C Setting Options Default Setting Comments
9011A RTD 1 TYPE   Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
Pt 100 Ω RTD 1: Type
9012A RTD 1 LOCATION   Oil
Ambient
Winding
Bearing
Other
Oil RTD 1: Location
9013 RTD 1 STAGE 1   -50 .. 250 °C; ∞ 100 °C RTD 1: Temperature Stage 1 Pickup
9014 RTD 1 STAGE 1   -58 .. 482 °F; ∞ 212 °F RTD 1: Temperature Stage 1 Pickup
9015 RTD 1 STAGE 2   -50 .. 250 °C; ∞ 120 °C RTD 1: Temperature Stage 2 Pickup
9016 RTD 1 STAGE 2   -58 .. 482 °F; ∞ 248 °F RTD 1: Temperature Stage 2 Pickup
9021A RTD 2 TYPE   Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
Not connected RTD 2: Type
9022A RTD 2 LOCATION   Oil
Ambient
Winding
Bearing
Other
Other RTD 2: Location
9023 RTD 2 STAGE 1   -50 .. 250 °C; ∞ 100 °C RTD 2: Temperature Stage 1 Pickup
9024 RTD 2 STAGE 1   -58 .. 482 °F; ∞ 212 °F RTD 2: Temperature Stage 1 Pickup
9025 RTD 2 STAGE 2   -50 .. 250 °C; ∞ 120 °C RTD 2: Temperature Stage 2 Pickup
9026 RTD 2 STAGE 2   -58 .. 482 °F; ∞ 248 °F RTD 2: Temperature Stage 2 Pickup
9031A RTD 3 TYPE   Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
Not connected RTD 3: Type
9032A RTD 3 LOCATION   Oil
Ambient
Winding
Bearing
Other
Other RTD 3: Location
9033 RTD 3 STAGE 1   -50 .. 250 °C; ∞ 100 °C RTD 3: Temperature Stage 1 Pickup
9034 RTD 3 STAGE 1   -58 .. 482 °F; ∞ 212 °F RTD 3: Temperature Stage 1 Pickup
9035 RTD 3 STAGE 2   -50 .. 250 °C; ∞ 120 °C RTD 3: Temperature Stage 2 Pickup
9036 RTD 3 STAGE 2   -58 .. 482 °F; ∞ 248 °F RTD 3: Temperature Stage 2 Pickup
9041A RTD 4 TYPE   Not connected Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
Not connected RTD 4: Type
9042A RTD 4 LOCATION   Oil
Ambient
Winding
Bearing
Other
Other RTD 4: Location
9043 RTD 4 STAGE 1   -50 .. 250 °C; ∞ 100 °C RTD 4: Temperature Stage 1 Pickup
9044 RTD 4 STAGE 1   -58 .. 482 °F; ∞ 212 °F RTD 4: Temperature Stage 1 Pickup
9045 RTD 4 STAGE 2   -50 .. 250 °C; ∞ 120 °C RTD 4: Temperature Stage 2 Pickup
9046 RTD 4 STAGE 2   -58 .. 482 °F; ∞ 248 °F RTD 4: Temperature Stage 2 Pickup
9051A RTD 5 TYPE   Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
Not connected RTD 5: Type
9052A RTD 5 LOCATION   Oil
Ambient
Winding
Bearing
Other
Other RTD 5: Location
9053 RTD 5 STAGE 1   -50 .. 250 °C; ∞ 100 °C RTD 5: Temperature Stage 1 Pickup
9054 RTD 5 STAGE 1   -58 .. 482 °F; ∞ 212 °F RTD 5: Temperature Stage 1 Pickup
9055 RTD 5 STAGE 2   -50 .. 250 °C; ∞ 120 °C RTD 5: Temperature Stage 2 Pickup
9056 RTD 5 STAGE 2   -58 .. 482 °F; ∞ 248 °F RTD 5: Temperature Stage 2 Pickup
9061A RTD 6 TYPE   Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
Not connected RTD 6: Type
9062A RTD 6 LOCATION   Oil
Ambient
Winding
Bearing
Other
Other RTD 6: Location
9063 RTD 6 STAGE 1   -50 .. 250 °C; ∞ 100 °C RTD 6: Temperature Stage 1 Pickup
9064 RTD 6 STAGE 1   -58 .. 482 °F; ∞ 212 °F RTD 6: Temperature Stage 1 Pickup
9065 RTD 6 STAGE 2   -50 .. 250 °C; ∞ 120 °C RTD 6: Temperature Stage 2 Pickup
9066 RTD 6 STAGE 2   -58 .. 482 °F; ∞ 248 °F RTD 6: Temperature Stage 2 Pickup
9071A RTD 7 TYPE   Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
Not connected RTD 7: Type
9072A RTD 7 LOCATION   Oil
Ambient
Winding
Bearing
Other
Other RTD 7: Location
9073 RTD 7 STAGE 1   -50 .. 250 °C; ∞ 100 °C RTD 7: Temperature Stage 1 Pickup
9074 RTD 7 STAGE 1   -58 .. 482 °F; ∞ 212 °F RTD 7: Temperature Stage 1 Pickup
9075 RTD 7 STAGE 2   -50 .. 250 °C; ∞ 120 °C RTD 7: Temperature Stage 2 Pickup
9076 RTD 7 STAGE 2   -58 .. 482 °F; ∞ 248 °F RTD 7: Temperature Stage 2 Pickup
9081A RTD 8 TYPE   Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
Not connected RTD 8: Type
9082A RTD 8 LOCATION   Oil
Ambient
Winding
Bearing
Other
Other RTD 8: Location
9083 RTD 8 STAGE 1   -50 .. 250 °C; ∞ 100 °C RTD 8: Temperature Stage 1 Pickup
9084 RTD 8 STAGE 1   -58 .. 482 °F; ∞ 212 °F RTD 8: Temperature Stage 1 Pickup
9085 RTD 8 STAGE 2   -50 .. 250 °C; ∞ 120 °C RTD 8: Temperature Stage 2 Pickup
9086 RTD 8 STAGE 2   -58 .. 482 °F; ∞ 248 °F RTD 8: Temperature Stage 2 Pickup
9091A RTD 9 TYPE   Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
Not connected RTD 9: Type
9092A RTD 9 LOCATION   Oil
Ambient
Winding
Bearing
Other
Other RTD 9: Location
9093 RTD 9 STAGE 1   -50 .. 250 °C; ∞ 100 °C RTD 9: Temperature Stage 1 Pickup
9094 RTD 9 STAGE 1   -58 .. 482 °F; ∞ 212 °F RTD 9: Temperature Stage 1 Pickup
9095 RTD 9 STAGE 2   -50 .. 250 °C; ∞ 120 °C RTD 9: Temperature Stage 2 Pickup
9096 RTD 9 STAGE 2   -58 .. 482 °F; ∞ 248 °F RTD 9: Temperature Stage 2 Pickup
9101A RTD10 TYPE   Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
Not connected RTD10: Type
9102A RTD10 LOCATION   Oil
Ambient
Winding
Bearing
Other
Other RTD10: Location
9103 RTD10 STAGE 1   -50 .. 250 °C; ∞ 100 °C RTD10: Temperature Stage 1 Pickup
9104 RTD10 STAGE 1   -58 .. 482 °F; ∞ 212 °F RTD10: Temperature Stage 1 Pickup
9105 RTD10 STAGE 2   -50 .. 250 °C; ∞ 120 °C RTD10: Temperature Stage 2 Pickup
9106 RTD10 STAGE 2   -58 .. 482 °F; ∞ 248 °F RTD10: Temperature Stage 2 Pickup
9111A RTD11 TYPE   Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
Not connected RTD11: Type
9112A RTD11 LOCATION   Oil
Ambient
Winding
Bearing
Other
Other RTD11: Location
9113 RTD11 STAGE 1   -50 .. 250 °C; ∞ 100 °C RTD11: Temperature Stage 1 Pickup
9114 RTD11 STAGE 1   -58 .. 482 °F; ∞ 212 °F RTD11: Temperature Stage 1 Pickup
9115 RTD11 STAGE 2   -50 .. 250 °C; ∞ 120 °C RTD11: Temperature Stage 2 Pickup
9116 RTD11 STAGE 2   -58 .. 482 °F; ∞ 248 °F RTD11: Temperature Stage 2 Pickup
9121A RTD12 TYPE   Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
Not connected RTD12: Type
9122A RTD12 LOCATION   Oil
Ambient
Winding
Bearing
Other
Other RTD12: Location
9123 RTD12 STAGE 1   -50 .. 250 °C; ∞ 100 °C RTD12: Temperature Stage 1 Pickup
9124 RTD12 STAGE 1   -58 .. 482 °F; ∞ 212 °F RTD12: Temperature Stage 1 Pickup
9125 RTD12 STAGE 2   -50 .. 250 °C; ∞ 120 °C RTD12: Temperature Stage 2 Pickup
9126 RTD12 STAGE 2   -58 .. 482 °F; ∞ 248 °F RTD12: Temperature Stage 2 Pickup

Overexcitation Protection

Addr. Parameter C Setting Options Default Setting Comments
4301 OVEREXC. PROT.   OFF
ON
Block relay
OFF Overexcitation Protection (U/f)
4302 U/f >   1.00 .. 1.20 1.10 U/f > Pickup
4303 T U/f >   0.00 .. 60.00 sec; ∞ 10.00 sec T U/f > Time Delay
4304 U/f >>   1.00 .. 1.40 1.40 U/f >> Pickup
4305 T U/f >>   0.00 .. 60.00 sec; ∞ 1.00 sec T U/f >> Time Delay
4306 t(U/f=1.05)   0 .. 20000 sec 20000 sec U/f = 1.05 Time Delay
4307 t(U/f=1.10)   0 .. 20000 sec 6000 sec U/f = 1.10 Time Delay
4308 t(U/f=1.15)   0 .. 20000 sec 240 sec U/f = 1.15 Time Delay
4309 t(U/f=1.20)   0 .. 20000 sec 60 sec U/f = 1.20 Time Delay
4310 t(U/f=1.25)   0 .. 20000 sec 30 sec U/f = 1.25 Time Delay
4311 t(U/f=1.30)   0 .. 20000 sec 19 sec U/f = 1.30 Time Delay
4312 t(U/f=1.35)   0 .. 20000 sec 13 sec U/f = 1.35 Time Delay
4313 t(U/f=1.40)   0 .. 20000 sec 10 sec U/f = 1.40 Time Delay
4314 T COOL DOWN   0 .. 20000 sec 3600 sec Time for cool down

Reverse Power Protection

Addr. Parameter C Setting Options Default Setting Comments
5001 REVERSE POWER   OFF
ON
Block relay
OFF Reverse Power Protection
5011 P> REVERSE 1A -3000.00 .. -0.85 W -8.70 W P> Reverse Pickup
5A -15000.00 .. -4.25 W -43.50 W
5012 Pr pick-up   -17.000 .. -0.005 P/SnS -0.050 P/SnS Pick-up threshold reverse power
5013 T-SV-OPEN   0.00 .. 60.00 sec; ∞ 10.00 sec Time Delay Long (without Stop Valve)
5014 T-SV-CLOSED   0.00 .. 60.00 sec; ∞ 1.00 sec Time Delay Short (with Stop Valve)
5015A T-HOLD   0.00 .. 60.00 sec; ∞ 0.00 sec Pickup Holding Time
5016A Type of meas.   accurate
fast
accurate Type of measurement

Forward Power Supervision

Addr. Parameter C Setting Options Default Setting Comments
5101 FORWARD POWER   OFF
ON
Block relay
OFF Forward Power Supervision
5111 Pf< 1A 1.7 .. 3000.0 W 17.3 W P-forw.< Supervision Pickup
5A 8.5 .. 15000.0 W 86.5 W
5112 P< fwd   0.01 .. 17.00 P/SnS 0.10 P/SnS Pick-up threshold P<
5113 T-Pf<   0.00 .. 60.00 sec; ∞ 10.00 sec T-P-forw.< Time Delay
5114 Pf> 1A 1.7 .. 3000.0 W 164.5 W P-forw.> Supervision Pickup
5A 8.5 .. 15000.0 W 822.5 W
5115 P> fwd   0.01 .. 17.00 P/SnS 0.95 P/SnS Pick-up threshold P>
5116 T-Pf>   0.00 .. 60.00 sec; ∞ 10.00 sec T-P-forw.> Time Delay
5117A MEAS. METHOD   accurate
fast
accurate Method of Operation

Undervoltage Protection

Addr. Parameter C Setting Options Default Setting Comments
5201 UNDERVOLTAGE   OFF
ON
Block relay
OFF Undervoltage Protection
5211 U<   10.0 .. 125.0 V 75.0 V U< Pickup
5212 U<   0.10 .. 1.25 U/UnS 0.75 U/UnS Pick-up voltage U<
5213 T U<   0.00 .. 60.00 sec; ∞ 3.00 sec T U< Time Delay
5214 U<<   10.0 .. 125.0 V 65.0 V U<< Pickup
5215 U<<   0.10 .. 1.25 U/UnS 0.65 U/UnS Pick-up voltage U<<
5216 T U<<   0.00 .. 60.00 sec; ∞ 0.50 sec T U<< Time Delay
5217A DOUT RATIO   1.01 .. 1.20 1.05 U<, U<< Drop Out Ratio

Overvoltage Protection

Addr. Parameter C Setting Options Default Setting Comments
5301 OVERVOLTAGE   OFF
ON
Block relay
OFF Overvoltage Protection
5311 U>   30.0 .. 170.0 V 115.0 V U> Pickup
5312 U>   0.30 .. 1.70 U/UnS 1.15 U/UnS Pick-up voltage U>
5313 T U>   0.00 .. 60.00 sec; ∞ 3.00 sec T U> Time Delay
5314 U>>   30.0 .. 170.0 V 130.0 V U>> Pickup
5315 U>>   0.30 .. 1.70 U/UnS 1.30 U/UnS Pick-up voltage U>>
5316 T U>>   0.00 .. 60.00 sec; ∞ 0.50 sec T U>> Time Delay
5317A DOUT RATIO   0.90 .. 0.99 0.98 U>, U>> Drop Out Ratio
5318A VALUES   U-ph-ph
U-ph-e
U-ph-ph Measurement Values

Frequency Protection

Addr. Parameter C Setting Options Default Setting Comments
5601 O/U FREQUENCY   OFF
ON
Block relay
OFF Over / Under Frequency Protection
5611 f<   40.00 .. 49.99 Hz; 0 49.50 Hz Pick-up frequency f<
5612 f<<   40.00 .. 49.99 Hz; 0 48.00 Hz Pick-up frequency f<<
5613 f<<<   40.00 .. 49.99 Hz; 0 47.00 Hz Pick-up frequency f<<<
5614 f>   50.01 .. 66.00 Hz; ∞ 52.00 Hz Pick-up frequency f>
5621 f<   50.00 .. 59.99 Hz; 0 59.50 Hz Pick-up frequency f<
5622 f<<   50.00 .. 59.99 Hz; 0 58.00 Hz Pick-up frequency f<<
5623 f<<<   50.00 .. 59.99 Hz; 0 57.00 Hz Pick-up frequency f<<<
5624 f>   60.01 .. 66.00 Hz; ∞ 62.00 Hz Pick-up frequency f>
5631 f<   10.00 .. 16.69 Hz; 0 16.50 Hz Pick-up frequency f<
5632 f<<   10.00 .. 16.69 Hz; 0 16.00 Hz Pick-up frequency f<<
5633 f<<<   10.00 .. 16.69 Hz; 0 15.70 Hz Pick-up frequency f<<<
5634 f>   16.67 .. 22.00 Hz; ∞ 17.40 Hz Pick-up frequency f>
5641 T f<   0.00 .. 100.00 sec; ∞ 20.00 sec Delay time T f<
5642 T f<<   0.00 .. 600.00 sec; ∞ 1.00 sec Delay time T f<<
5643 T f<<<   0.00 .. 100.00 sec; ∞ 6.00 sec Delay time T f<<<
5644 T f>   0.00 .. 100.00 sec; ∞ 10.00 sec Delay time T f>
5651 Umin   10.0 .. 125.0 V; 0 65.0 V Minimum Required Voltage for Operation
5652 U MIN   0.10 .. 1.25 U/UnS; 0 0.65 U/UnS Minimum voltage

Circuit Breaker Failure Protection

Addr. Parameter C Setting Options Default Setting Comments
7001 BREAKER FAILURE   OFF
ON
Block relay
OFF Breaker Failure Protection
7011 START WITH REL.   0 .. 8 0 Start with Relay (intern)
7012 START WITH REL.   0 .. 24 0 Start with Relay (intern)
7015 T1   0.00 .. 60.00 sec; ∞ 0.15 sec T1, Delay of 1st stage (local trip)
7016 T2   0.00 .. 60.00 sec; ∞ 0.30 sec T2, Delay of 2nd stage (busbar trip)

External Trip Commands

Addr. Parameter C Setting Options Default Setting Comments
8601 EXTERN TRIP 1   OFF
ON
Block relay
OFF External Trip Function 1
8602 T DELAY   0.00 .. 60.00 sec; ∞ 1.00 sec Ext. Trip 1 Time Delay
8701 EXTERN TRIP 2   OFF
ON
Block relay
OFF External Trip Function 2
8702 T DELAY   0.00 .. 60.00 sec; ∞ 1.00 sec Ext. Trip 2 Time Delay

Measurement Supervision

Addr. Parameter C Setting Options Default Setting Comments
8101 BALANCE I   ON
OFF
OFF Current Balance Supervi- sion
8102 BALANCE U   ON
OFF
OFF Voltage Balance Supervi- sion
8104 SUMMATION U   ON
OFF
OFF Voltage Summation Super- vision
8105 PHASE ROTAT. I   ON
OFF
OFF Current Phase Rotation Supervision
8106 PHASE ROTAT. U   ON
OFF
OFF Voltage Phase Rotation Supervision
8111 BAL. I LIMIT M1 1A 0.10 .. 1.00 A 0.50 A Current Balance Monitor Meas. Loc. 1
5A 0.50 .. 5.00 A 2.50 A
8112 BAL. FACT. I M1   0.10 .. 0.90 0.50 Bal. Factor for Curr. Monitor Meas.Loc.1
8113A T Sym. I th. M1   5 .. 100 sec 5 sec Symmetry Iph: Pick-up delay
8121 BAL. I LIMIT M2 1A 0.10 .. 1.00 A 0.50 A Current Balance Monitor Meas. Loc. 2
5A 0.50 .. 5.00 A 2.50 A
8122 BAL. FACT. I M2   0.10 .. 0.90 0.50 Bal. Factor for Curr. Monitor Meas.Loc.2
8123A T Sym. I th. M2   5 .. 100 sec 5 sec Symmetry Iph: Pick-up delay
8131 BAL. I LIMIT M3 1A 0.10 .. 1.00 A 0.50 A Current Balance Monitor Meas. Loc. 3
5A 0.50 .. 5.00 A 2.50 A
8132 BAL. FACT. I M3   0.10 .. 0.90 0.50 Bal. Factor for Curr. Monitor Meas.Loc.3
8133A T Sym. I th. M3   5 .. 100 sec 5 sec Symmetry Iph: Pick-up delay
8141 BAL. I LIMIT M4 1A 0.10 .. 1.00 A 0.50 A Current Balance Monitor Meas. Loc. 4
5A 0.50 .. 5.00 A 2.50 A
8142 BAL. FACT. I M4   0.10 .. 0.90 0.50 Bal. Factor for Curr. Monitor Meas.Loc.4
8143A T Sym. I th. M4   5 .. 100 sec 5 sec Symmetry Iph: Pick-up delay
8151 BAL. I LIMIT M5 1A 0.10 .. 1.00 A 0.50 A Current Balance Monitor Meas. Loc. 5
5A 0.50 .. 5.00 A 2.50 A
8152 BAL. FACT. I M5   0.10 .. 0.90 0.50 Bal. Factor for Curr. Monitor Meas.Loc.5
8153A T Sym. I th. M5   5 .. 100 sec 5 sec Symmetry Iph: Pick-up delay
8161 BALANCE U-LIMIT   10 .. 100 V 50 V Voltage Threshold for Balance Monitoring
8162 BAL. FACTOR U   0.58 .. 0.90 0.75 Balance Factor for Voltage Monitor
8163A T BAL. U LIMIT   5 .. 100 sec 5 sec T Balance Factor for Voltage Monitor

Trip Circuit Supervision

Addr. Parameter C Setting Options Default Setting Comments
8201 TRIP Cir. SUP.   ON
OFF
OFF TRIP Circuit Supervision

Broken Wire Detection, Fuse Failure Monitoring

Addr. Parameter C Setting Options Default Setting Comments
2911A FFM U>(min)   10 .. 100 V 20 V Minimum Voltage Threshold U>
8401 BROKEN WIRE   OFF
BWD Al and Blk
BWD Al and ABlk
BWD Al only
OFF Fast broken current-wire supervision
8403 FUSE FAIL MON.   OFF
ON
OFF Fuse Failure Monitor
8414 T BWD delay   0.0 .. 180.0 sec 1.0 sec Delay time for BWD super- vision
8415 ΔI< BWD   0.05 .. 5.00 I/InO 1.00 I/InO min differential current for BWD
8422A FFM I< M1 1A 0.04 .. 2.00 A 0.10 A I< for FFM detection M1
5A 0.20 .. 10.00 A 0.50 A
8423A FFM I< M2 1A 0.04 .. 2.00 A 0.10 A I< for FFM detection M2
5A 0.20 .. 10.00 A 0.50 A
8424A FFM I< M3 1A 0.04 .. 2.00 A 0.10 A I< for FFM detection M3
5A 0.20 .. 10.00 A 0.50 A
8426A FFM U<max (3ph)   2 .. 100 V 5 V Maximum Voltage Threshold U< (3phase)

Measurement

Addr. Parameter C Setting Options Default Setting Comments
7601 POWER CALCUL.   with V setting
with V measur.
with V setting Calculation of Power

Flexible Function

Addr. Parameter C Setting Options Default Setting Comments
0 FLEXIBLE FUNC.   OFF
ON
Alarm Only
Block relay
OFF Flexible Function
0 Pick-up thresh. 1A 0.05 .. 35.00 A 2.00 A Pick-up threshold I meas. location 1
5A 0.25 .. 175.00 A 10.00 A
0 Pick-up thresh. 1A 0.05 .. 35.00 A 2.00 A Pick-up threshold I meas. location 2
5A 0.25 .. 175.00 A 10.00 A
0 Pick-up thresh. 1A 0.05 .. 35.00 A 2.00 A Pick-up threshold I meas. location 3
5A 0.25 .. 175.00 A 10.00 A
0 Pick-up thresh. 1A 0.05 .. 35.00 A 2.00 A Pick-up threshold I meas. location 4
5A 0.25 .. 175.00 A 10.00 A
0 Pick-up thresh. 1A 0.05 .. 35.00 A 2.00 A Pick-up threshold I meas. location 5
5A 0.25 .. 175.00 A 10.00 A
0 Pick-up thresh. 1A 0.05 .. 35.00 A 2.00 A Pick-up threshold I1
5A 0.25 .. 175.00 A 10.00 A
0.1A 0.005 .. 3.500 A 0.200 A
0 Pick-up thresh. 1A 0.05 .. 35.00 A 2.00 A Pick-up threshold I2
5A 0.25 .. 175.00 A 10.00 A
0.1A 0.005 .. 3.500 A 0.200 A
0 Pick-up thresh. 1A 0.05 .. 35.00 A 2.00 A Pick-up threshold I3
5A 0.25 .. 175.00 A 10.00 A
0.1A 0.005 .. 3.500 A 0.200 A
0 Pick-up thresh. 1A 0.05 .. 35.00 A 2.00 A Pick-up threshold I4
5A 0.25 .. 175.00 A 10.00 A
0.1A 0.005 .. 3.500 A 0.200 A
0 Pick-up thresh. 1A 0.05 .. 35.00 A 2.00 A Pick-up threshold I5
5A 0.25 .. 175.00 A 10.00 A
0.1A 0.005 .. 3.500 A 0.200 A
0 Pick-up thresh. 1A 0.05 .. 35.00 A 2.00 A Pick-up threshold I6
5A 0.25 .. 175.00 A 10.00 A
0.1A 0.005 .. 3.500 A 0.200 A
0 Pick-up thresh. 1A 0.05 .. 35.00 A 2.00 A Pick-up threshold I7
5A 0.25 .. 175.00 A 10.00 A
0.1A 0.005 .. 3.500 A 0.200 A
0 Pick-up thresh. 1A 0.05 .. 35.00 A 2.00 A Pick-up threshold I8
5A 0.25 .. 175.00 A 10.00 A
0.1A 0.005 .. 3.500 A 0.200 A
0 Pick-up thresh. 1A 0.05 .. 35.00 A 2.00 A Pick-up threshold I9
5A 0.25 .. 175.00 A 10.00 A
0.1A 0.005 .. 3.500 A 0.200 A
0 Pick-up thresh. 1A 0.05 .. 35.00 A 2.00 A Pick-up threshold I10
5A 0.25 .. 175.00 A 10.00 A
0.1A 0.005 .. 3.500 A 0.200 A
0 Pick-up thresh. 1A 0.05 .. 35.00 A 2.00 A Pick-up threshold I11
5A 0.25 .. 175.00 A 10.00 A
0.1A 0.005 .. 3.500 A 0.200 A
0 Pick-up thresh. 1A 0.05 .. 35.00 A 2.00 A Pick-up threshold I12
5A 0.25 .. 175.00 A 10.00 A
0.1A 0.005 .. 3.500 A 0.200 A
0 Pick-up thresh. 1A 0.05 .. 35.00 A 2.00 A Pick-up threshold IX1
5A 0.25 .. 175.00 A 10.00 A
0 Pick-up thresh. 1A 0.05 .. 35.00 A 2.00 A Pick-up threshold IX2
5A 0.25 .. 175.00 A 10.00 A
0 Pick-up thresh. 1A 0.05 .. 35.00 A 2.00 A Pick-up threshold IX3
5A 0.25 .. 175.00 A 10.00 A
0 Pick-up thresh. 1A 0.05 .. 35.00 A 2.00 A Pick-up threshold IX4
5A 0.25 .. 175.00 A 10.00 A
0 Pick-up thresh.   0.001 .. 1.500 A 0.100 A Pick-up threshold IX3 sens.
0 Pick-up thresh.   0.001 .. 1.500 A 0.100 A Pick-up threshold IX4 sens.
0 Pick-up thresh.   0.05 .. 35.00 I/InS 2.00 I/InS Pick-up threshold I-side
0 P.U. THRESHOLD   1.0 .. 170.0 V 110.0 V Pickup Threshold
0 P.U. THRESHOLD   1.0 .. 170.0 V 110.0 V Pickup Threshold
0 P.U. THRESHOLD   40.00 .. 66.00 Hz 51.00 Hz Pickup Threshold
0 P.U. THRESHOLD   10.00 .. 22.00 Hz 18.00 Hz Pickup Threshold
0 P.U. THRESHOLD 1A 1.7 .. 3000.0 W 200.0 W Pickup Threshold
5A 8.5 .. 15000.0 W 1000.0 W
0 Pick-up thresh.   0.01 .. 17.00 P/SnS 1.10 P/SnS Pick-up threshold P-side
0 Pick-up thresh. 1A 1.7 .. 3000.0 VAR 200.0 VAR Pick-up threshold Q meas. location
5A 8.5 .. 15000.0 VAR 1000.0 VAR
0 Pick-up thresh.   0.01 .. 17.00 Q/SnS 1.10 Q/SnS Pick-up threshold Q-side
0 P.U. THRESHOLD   -0.99 .. 0.99 0.50 Pickup Threshold
0 T TRIP DELAY   0.00 .. 3600.00 sec 1.00 sec Trip Time Delay
0A T PICKUP DELAY   0.00 .. 60.00 sec 0.00 sec Pickup Time Delay
0A T DROPOUT DELAY   0.00 .. 60.00 sec 0.00 sec Dropout Time Delay
0A BLOCKED BY FFM   YES
NO
YES Block in case of Meas.- Voltage Loss
0A Blk I brkn cond   YES
NO
YES Block for broken conductor in CT path
0A DROPOUT RATIO   0.70 .. 0.99 0.95 Dropout Ratio
0A DROPOUT RATIO   1.01 .. 3.00 1.05 Dropout Ratio
0 MEAS. QUANTITY   Please select
I-Meas Loc/side
Curr. I1..I12
Curr. IX1..IX4
Voltage
P forward
P reverse
Q forward
Q reverse
Power factor
Frequency
   
0 Func. assigned   Please select
Side 1
Side 2
Side 3
Side 4
Side 5
Measuring loc.1
Measuring loc.2
Measuring loc.3
Measuring loc.4
Measuring loc.5
   
0 Func. per phase   IL1..IL3
IL1
IL2
IL3
3I0 (Zero seq.)
I1 (Pos. seq.)
I2 (Neg. seq.)
   
0 Func. assigned   Please select
I-CT 1
I-CT 2
I-CT 3
I-CT 4
I-CT 5
I-CT 6
I-CT 7
I-CT 8
I-CT 9
I-CT 10
I-CT 11
I-CT 12
   
0 Func. assigned   Please select
AuxiliaryCT IX1
AuxiliaryCT IX2
AuxiliaryCT IX3
AuxiliaryCT IX4
   
0 Func. per phase   Please select
UL1E..UL3E
UL1E
UL2E
UL3E
UL12..UL31
UL12
UL23
UL31
U0 (Zero seq.)
U1 (Pos. seq.)
U2 (Neg. seq.)
U4/Uen
   
0 PICKUP WITH   Exceeding
Dropping below
   
0A Type of meas.   accurate
fast
   

Oscillographic Fault Recording

Addr. Parameter C Setting Options Default Setting Comments
901 WAVEFORMTRIGGER   Save w. Pickup
Save w. TRIP
Start w. TRIP
Save w. Pickup Waveform Capture
903 MAX. LENGTH   0.30 .. 5.00 sec 1.00 sec Max. length of a Waveform Capture Record
904 PRE. TRIG. TIME   0.05 .. 0.50 sec 0.20 sec Captured Waveform Prior to Trigger
905 POST REC. TIME   0.05 .. 0.50 sec 0.10 sec Captured Waveform after Event
906 BinIn CAPT.TIME   0.10 .. 5.00 sec; ∞ 0.50 sec Capture Time via Binary Input

Demand Measurement Setup

Addr. Parameter C Setting Options Default Setting Comments
7611 DMD Interval   15 Min., 1 Sub
15 Min., 3 Subs
15 Min.,15 Subs
30 Min., 1 Sub
60 Min., 1 Sub
60 Min.,10 Subs
5 Min., 5 Subs
60 Min., 1 Sub Demand Calculation Intervals
7612 DMD Sync.Time   On The Hour
15 After Hour
30 After Hour
45 After Hour
On The Hour Demand Synchronization Time

Min/Max Measurement Setup

Addr. Parameter C Setting Options Default Setting Comments
7621 MinMax cycRESET   NO
YES
YES Automatic Cyclic Reset Function
7622 MiMa RESET TIME   0 .. 1439 min 0 min MinMax Reset Timer
7623 MiMa RESETCYCLE   1 .. 365 Days 7 Days MinMax Reset Cycle Period
7624 MinMaxRES.START   1 .. 365 Days 1 Days MinMax Start Reset Cycle in