Overview

The SIPROTEC 7SD610 relay is a differential protection relay suitable for all types of applications and incorporating all those functions required for differential protection of lines, cables and transformers.

For more detailed information on “SIPROTEC 7SD610 V4.7” relays, refer to SIPROTEC 4 devices manuals.

To see other supported devices, click here.


Functional Scope

Addr. Parameter C Setting Options Default Setting Comments
103 Grp Chge OPTION   Disabled
Enabled
Disabled Setting Group Change Option
110 Trip mode   3pole only
1-/3pole
3pole only Trip mode
112 DIFF.PROTECTION   Disabled
Enabled
Enabled Differential protection
122 DTT Direct Trip   Disabled
Enabled
Disabled DTT Direct Transfer Trip
124 HS/SOTF-O/C   Disabled
Enabled
Disabled Instantaneous HighSpeed/SOTF Overcurrent
126 Back-Up O/C   Disabled
TOC IEC
TOC ANSI
TOC IEC Backup overcurrent
133 Auto Reclose   1 AR-cycle
2 AR-cycles
3 AR-cycles
4 AR-cycles
5 AR-cycles
6 AR-cycles
7 AR-cycles
8 AR-cycles
ADT
Disabled
Disabled Auto-Reclose Function
134 AR control mode   Pickup w/ Tact
Pickup w/o Tact
Trip w/ Tact
Trip w/o Tact
Trip w/o Tact Auto-Reclose control mode
136 FREQUENCY Prot.   Disabled
Enabled
Disabled Over / Underfrequency Protection
137 U/O VOLTAGE   Disabled
Enabled
Enabl. w. comp.
Disabled Under / Overvoltage Protection
139 BREAKER FAILURE   Disabled
Enabled
enabled w/ 3I0>
Disabled Breaker Failure Protection
140 Trip Cir. Sup.   Disabled
1 trip circuit
2 trip circuits
3 trip circuits
Disabled Trip Circuit Supervision
141 REF PROT.   Disabled
Enabled
Disabled Restricted earth fault protection
142 Therm.Overload   Disabled
Enabled
Disabled Thermal Overload Protection
143 TRANSFORMER   NO
YES
NO Transformer inside protection zone
144 V-TRANSFORMER   Not connected
connected
connected Voltage transformers
148 GPS-SYNC.   Disabled
Enabled
Disabled GPS synchronization

General Power System Data (Power System Data 1)

Addr. Parameter C Setting Options Default Setting Comments
201 CT Starpoint   towards Line
towards Busbar
towards Line CT Starpoint
203 Unom PRIMARY   0.4 .. 1200.0 kV 400.0 kV Rated Primary Voltage
204 Unom SECONDARY   80 .. 125 V 100 V Rated Secondary Voltage (Ph-Ph)
205 CT PRIMARY   10 .. 10000 A 1000 A CT Rated Primary Current
206 CT SECONDARY   1A
5A
1A CT Rated Secondary Current
207 SystemStarpoint   Solid Earthed
Peterson-Coil
Isolated
Solid Earthed System Starpoint is
208A 1-1/2 CB   NO
YES
NO 1-1/2 Circuit breaker arrangement
210 U4 transformer   Not connected
Udelta transf.
Ux transformer
Not connected U4 voltage transformer is
211 Uph / Udelta   0.10 .. 9.99 1.73 Matching ratio Phase-VT To Open- Delta-VT
220 I4 transformer   Not connected
In prot. line
IY starpoint
In prot. line I4 current transformer is
221 I4/Iph CT   0.010 .. 5.000 1.000 Matching ratio I4/Iph for CT’s
230 Rated Frequency   50 Hz
60 Hz
50 Hz Rated Frequency
236 Distance Unit   km
Miles
km Distance measurement unit
240A TMin TRIP CMD   0.02 .. 30.00 sec 0.10 sec Minimum TRIP Command Duration
241A TMax CLOSE CMD   0.01 .. 30.00 sec 1.00 sec Maximum Close Command Dura- tion
242 T-CBtest-dead   0.00 .. 30.00 sec 0.10 sec Dead Time for CB test-autoreclo- sure
251 K_ALF/K_ALF_N   1.00 .. 10.00 1.00 k_alf/k_alf nominal
253 E% ALF/ALF_N   0.5 .. 50.0 % 5.0 % CT Error in % at k_alf/k_alf nominal
254 E% K_ALF_N   0.5 .. 50.0 % 15.0 % CT Error in % at k_alf nominal

Change Group

Addr. Parameter C Setting Options Default Setting Comments
301 ACTIVE GROUP   Group A
Group B
Group C
Group D
Group A Active Setting Group is
302 CHANGE   Group A
Group B
Group C
Group D
Binary Input
Protocol
Group A Change to Another Setting Group

General Protection Data (Power System Data 2)

Addr. Parameter C Setting Options Default Setting Comments
1103 FullScaleVolt.   0.4 .. 1200.0 kV 400.0 kV Measurement: Full Scale Voltage (100%)
1104 FullScaleCurr.   10 .. 10000 A 1000 A Measurement: Full Scale Current (100%)
1105 Line Angle   10 .. 89 ° 85 ° Line Angle
1106 OPERATION POWER   0.2 .. 5000.0 MVA 692.8 MVA Operational power of protection zone
1107 P,Q sign   not reversed
reversed
not reversed P,Q operational measured values sign
1111 x’ 1A 0.0050 .. 9.5000 Ω/km 0.1500 Ω/km x’ – Line Reactance per length unit
5A 0.0010 .. 1.9000 Ω/km 0.0300 Ω/km
1111 x’ 1A 0.0050 .. 15.0000 Ω/mi 0.2420 Ω/mi x’ – Line Reactance per length unit
5A 0.0010 .. 3.0000 Ω/mi 0.0484 Ω/mi
1112 c’ 1A 0.000 .. 100.000 µF/km 0.010 µF/km c’ – capacit. per unit line len. µF/km
5A 0.000 .. 500.000 µF/km 0.050 µF/km
1112 c’ 1A 0.000 .. 160.000 µF/mi 0.016 µF/mi c’ – capacit. per unit line len. µF/mile
5A 0.000 .. 800.000 µF/mi 0.080 µF/mi
1113 Line Length   0.1 .. 1000.0 km 100.0 km Line Length
1113 Line Length   0.1 .. 650.0 Miles 62.1 Miles Line Length
1130A PoleOpenCurrent 1A 0.05 .. 1.00 A 0.10 A Pole Open Current Threshold
5A 0.25 .. 5.00 A 0.50 A
1131A PoleOpenVoltage   2 .. 70 V 30 V Pole Open Voltage Threshold
1132A SI Time all Cl.   0.01 .. 30.00 sec 0.10 sec Seal-in Time after ALL closures
1133A T DELAY SOTF   0.05 .. 30.00 sec 0.25 sec minimal time for line open before SOTF
1134 Line Closure   only with ManCl
I OR U or ManCl
CB OR I or M/C
I or Man.Close
I or Man.Close Recognition of Line Closures with
1135 Reset Trip CMD   CurrentOpenPole
Current AND CB
Pickup Reset
CurrentOpenPole RESET of Trip Command
1136 OpenPoleDetect.   OFF
Current AND CB
w/ measurement
w/ measurement open pole detector
1150A SI Time Man.Cl   0.01 .. 30.00 sec 0.30 sec Seal-in Time after MANUAL closures
1151 SYN.MAN.CL   w/o Sync-check
NO
NO Manual CLOSE COMMAND
generation
1152 Man.Clos. Imp.   (Einstellmoglichkeiten anwendungsabhangig) none MANUAL Closure Impulse after CONTROL
1155 3pole coupling   with PICKUP
with TRIP
with TRIP 3 pole coupling
1156A Trip2phFlt   3pole
1pole leading Ø
1pole lagging Ø
3pole Trip type with 2phase faults
1161 VECTOR GROUP U   0 .. 11 0 Vector group numeral for voltage
1162 VECTOR GROUP I   0 .. 11 0 Vector group numeral for current
1163 TRANS STP IS   Solid Earthed
Not Earthed
Solid Earthed Transformer starpoint is

Protection Data Interfaces

Addr. Parameter C Setting Options Default Setting Comments
4501 STATE PROT I 1   ON
OFF
ON State of protection interface 1
4502 CONNEC. 1 OVER   F.optic direct
Com c 64 kBit/s
Com c 128kBit/s
Com c 512kBit/s
C37.94 1 slot
C37.94 2 slots
C37.94 4 slots
C37.94 8 slots
F.optic direct Connection 1 over
4505A PROT 1 T-DELAY   0.1 .. 30.0 ms 30.0 ms Prot 1: Maximal permissible delay time
4506A PROT 1 UNSYM.   0.000 .. 3.000 ms 0.100 ms Prot 1: Diff. in send and receive time
4509 T-DATA DISTURB   0.05 .. 2.00 sec 0.10 sec Time delay for data disturbance alarm
4510 T-DATAFAIL   0.0 .. 60.0 sec 6.0 sec Time del for transmission failure alarm
4511 PI1 SYNCMODE   TEL and GPS
TEL or GPS
GPS SYNC OFF
TEL and GPS PI1 Synchronizationmode
4512 Td ResetRemote   0.00 .. 300.00 sec; ∞ 0.00 sec Remote signal RESET DELAY for comm.fail
4513A PROT1 max ERROR   0.5 .. 20.0 % 1.0 % Prot 1: Maximal permissible error rate
4515A PI1 BLOCK UNSYM   YES
NO
YES Prot.1: Block. due to unsym. delay time
4801 GPS-SYNC.   ON
OFF
OFF GPS synchronization
4803A TD GPS FAILD   0.5 .. 60.0 sec 2.1 sec Delay time for local GPS-pulse loss

Differential Protection Topology

Addr. Parameter C Setting Options Default Setting Comments
4701 ID OF RELAY 1   1 .. 65534 1 Identification number of relay 1
4702 ID OF RELAY 2   1 .. 65534 2 Identification number of relay 2
4710 LOCAL RELAY   relay 1
relay 2
relay 1 Local relay is

Differential Protection

Addr. Parameter C Setting Options Default Setting Comments
1201 STATE OF DIFF.   ON
OFF
ON State of differential protec- tion
1210 I-DIFF> 1A 0.10 .. 20.00 A 0.30 A I-DIFF>: Pickup value
5A 0.50 .. 100.00 A 1.50 A
1213 I-DIF>SWITCH ON 1A 0.10 .. 20.00 A 0.30 A I-DIFF>: Value under switch on condition
5A 0.50 .. 100.00 A 1.50 A
1217A T-DELAY I-DIFF>   0.00 .. 60.00 sec; ∞ 0.00 sec I-DIFF>: Trip time delay
1218 T3I0 1PHAS   0.00 .. 0.50 sec; ∞ 0.04 sec Delay 1ph-faults (comp/ isol. star-point)
1219A I> RELEASE DIFF 1A 0.10 .. 20.00 A; 0 0.00 A Min. local current to release DIFF-Trip
5A 0.50 .. 100.00 A; 0 0.00 A
1233 I-DIFF>> 1A 0.8 .. 100.0 A; ∞ 1.2 A I-DIFF>>: Pickup value
5A 4.0 .. 500.0 A; ∞ 6.0 A
1235 I-DIF>>SWITCHON 1A 0.8 .. 100.0 A; ∞ 1.2 A I-DIFF>>: Value under switch on cond.
5A 4.0 .. 500.0 A; ∞ 6.0 A
2301 INRUSH REST.   ON
OFF
OFF Inrush Restraint
2302 2nd HARMONIC   10 .. 45 % 15 % 2nd. harmonic in % of fundamental
2303 CROSS BLOCK   YES
NO
NO Cross Block
2305 MAX INRUSH PEAK 1A 1.1 .. 25.0 A 15.0 A Maximum inrush-peak value
5A 5.5 .. 125.0 A 75.0 A
2310 CROSSB 2HM   0.00 .. 60.00 sec; ∞ 0.00 sec Time for Crossblock with 2nd harmonic

Breaker Intertrip and Remote Tripping

Addr. Parameter C Setting Options Default Setting Comments
1301 I-TRIP SEND   YES
NO
NO State of transmit. the intertrip command
1302 I-TRIP RECEIVE   Alarm only
Trip
Trip Reaction if intertrip command is receiv.
1303 T-ITRIP BI   0.00 .. 30.00 sec 0.02 sec Delay for intertrip via binary input
1304 T-ITRIP PROL BI   0.00 .. 30.00 sec 0.00 sec Prolongation for intertrip via bin.input

Restricted Earth Fault Protection (optional)

Addr. Parameter C Setting Options Default Setting Comments
4101 REF PROT.   ON
OFF
OFF Restricted Earth Fault Protection
4111 I-REF> 1A 0.05 .. 2.00 A 0.15 A Pick up value I REF>
5A 0.25 .. 10.00 A 0.75 A
4112A T I-REF>   0.00 .. 60.00 sec; ∞ 0.00 sec T I-REF> Time Delay
4113A SLOPE   0.00 .. 0.95 0.00 Slope of Charac. I-REF> = f(I-SUM)

Direct Local Trip

Addr. Parameter C Setting Options Default Setting Comments
2201 FCT Direct Trip   ON
OFF
OFF Direct Transfer Trip (DTT)
2202 Trip Time DELAY   0.00 .. 30.00 sec; ∞ 0.01 sec Trip Time Delay

Instantaneous High-Current Switch-onto-Fault Protection (SOTF)

Addr. Parameter C Setting Options Default Setting Comments
2401 FCT HS/SOTF-O/C   ON
OFF
ON Inst. High Speed/SOTF-O/C is
2404 I>>> 1A 0.10 .. 15.00 A; ∞ 1.50 A I>>> Pickup
5A 0.50 .. 75.00 A; ∞ 7.50 A
2405A I>>>> 1A 1.00 .. 25.00 A; ∞ ∞ A I>>>> Pickup
5A 5.00 .. 125.00 A; ∞ ∞ A
2406 CBaux for I>>>   local only
local and rem.
local and rem. CB-aux check for activation of I>>>

Backup Time Overcurrent Protection

Addr. Parameter C Setting Options Default Setting Comments
2601 Operating Mode   ON
Only Emer. prot
OFF
ON Operating mode
2602 SOTF Time DELAY   0.00 .. 30.00 sec 0.00 sec Trip time delay after SOTF
2603A Direct. 3I0   U0/I0 or U2/I0
with U0/I0
with U2/I2
U0/I0 or U2/I0 Measurement of direction for 3I0
2610 Iph>> 1A 0.05 .. 50.00 A; ∞ 2.00 A Iph>> Pickup
5A 0.25 .. 250.00 A; ∞ 10.00 A
2611 T Iph>>   0.00 .. 30.00 sec; ∞ 0.30 sec T Iph>> Time delay
2612 3I0>> PICKUP 1A 0.05 .. 25.00 A; ∞ 0.50 A 3I0>> Pickup
5A 0.25 .. 125.00 A; ∞ 2.50 A
2613 T 3I0>>   0.00 .. 30.00 sec; ∞ 2.00 sec T 3I0>> Time delay
2614 I>> InstTrip BI   NO
YES
YES Instantaneous trip via BI
2615 I>> SOTF   NO
YES
NO Instantaneous trip after SwitchOnToFault
2620 Iph> 1A 0.05 .. 50.00 A; ∞ 1.50 A Iph> Pickup
5A 0.25 .. 250.00 A; ∞ 7.50 A
2621 T Iph>   0.00 .. 30.00 sec; ∞ 0.50 sec T Iph> Time delay
2622 3I0> 1A 0.05 .. 25.00 A; ∞ 0.20 A 3I0> Pickup
5A 0.25 .. 125.00 A; ∞ 1.00 A
2623 T 3I0>   0.00 .. 30.00 sec; ∞ 2.00 sec T 3I0> Time delay
2624 I> Telep/BI   NO
YES
NO Instantaneous trip via Tele- prot./BI
2625 I> SOTF   NO
YES
NO Instantaneous trip after SwitchOnToFault
2630 Iph> STUB 1A 0.05 .. 50.00 A; ∞ 1.50 A Iph> STUB Pickup
5A 0.25 .. 250.00 A; ∞ 7.50 A
2631 T Iph STUB   0.00 .. 30.00 sec; ∞ 0.30 sec T Iph STUB Time delay
2632 3I0> STUB 1A 0.05 .. 25.00 A; ∞ 0.20 A 3I0> STUB Pickup
5A 0.25 .. 125.00 A; ∞ 1.00 A
2633 T 3I0 STUB   0.00 .. 30.00 sec; ∞ 2.00 sec T 3I0 STUB Time delay
2634 I-STUB Telep/BI   NO
YES
NO Instantaneous trip via Tele- prot./BI
2635 I-STUB SOTF   NO
YES
NO Instantaneous trip after SwitchOnToFault
2640 Ip> 1A 0.10 .. 4.00 A; ∞ ∞ A Ip> Pickup
5A 0.50 .. 20.00 A; ∞ ∞ A
2642 T Ip Time Dial   0.05 .. 3.00 sec; ∞ 0.50 sec T Ip Time Dial
2643 Time Dial TD Ip   0.50 .. 15.00 ; ∞ 5.00 Time Dial TD Ip
2646 T Ip Add   0.00 .. 30.00 sec 0.00 sec T Ip Additional Time Delay
2650 3I0p PICKUP 1A 0.05 .. 4.00 A; ∞ ∞ A 3I0p Pickup
5A 0.25 .. 20.00 A; ∞ ∞ A
2652 T 3I0p TimeDial   0.05 .. 3.00 sec; ∞ 0.50 sec T 3I0p Time Dial
2653 TimeDial TD3I0p   0.50 .. 15.00 ; ∞ 5.00 Time Dial TD 3I0p
2656 T 3I0p Add   0.00 .. 30.00 sec 0.00 sec T 3I0p Additional Time Delay
2660 IEC Curve   Normal Inverse
Very Inverse
Extremely Inv.
LongTimeInverse
Normal Inverse IEC Curve
2661 ANSI Curve   Inverse
Short Inverse
Long Inverse
Moderately Inv.
Very Inverse
Extremely Inv.
Definite Inv.
Inverse ANSI Curve
2670 I(3I0)p Tele/BI   NO
YES
NO Instantaneous trip via Tele- prot./BI
2671 I(3I0)p SOTF   NO
YES
NO Instantaneous trip after SwitchOnToFault
2680 Direction Iph>   Non-Directional
Forward
Reverse
Non-Directional Direction of stage Iph> Dir.
2681 Iph> Dir. 1A 0.05 .. 50.00 A; ∞ 1.50 A Iph> directional Pickup
5A 0.25 .. 250.00 A; ∞ 7.50 A
2682 T Iph> Dir.   0.00 .. 30.00 sec; ∞ 0.50 sec T Iph> Dir. Time delay
2683 Direction 3I0>   Non-Directional
Forward
Reverse
Non-Directional Direction of stage 3I0> Dir.
2684 3I0> Dir. 1A 0.05 .. 25.00 A; ∞ 0.20 A 3I0> directional Pickup
5A 0.25 .. 125.00 A; ∞ 1.00 A
2685 T 3I0> Dir.   0.00 .. 30.00 sec; ∞ 2.00 sec T 3I0> Dir. Time delay
2686 I>Dir.Telep/BI   NO
YES
NO Instantaneous trip via Tele- prot./BI
2687 I> Dir. SOTF   NO
YES
NO Instantaneous trip after SwitchOnToFault
2688 Direction IP   Forward
Reverse
Forward Direction of stage Ip> Dir.
2689 Ip> Dir. 1A 0.10 .. 4.00 A; ∞ ∞ A Ip> directional Pickup
5A 0.50 .. 20.00 A; ∞ ∞ A
2690 T Ip Dir.   0.05 .. 3.00 sec; ∞ 0.50 sec T Ip Dir.: Inv.-Time delay for IEC-Char.
2691 D Ip Dir.   0.50 .. 15.00 ; ∞ 5.00 D 3I0p Dir.:Inv.-Time delay for ANSI-Ch.
2692 T Ip Add Dir.   0.00 .. 30.00 sec 0.00 sec T 3I0p Dir.: additional time delay
2693 Direction 3I0P   Forward
Reverse
Forward Direction of stage 3I0p
2694 3I0p Dir. 1A 0.05 .. 4.00 A; ∞ ∞ A 3I0p directional Pickup
5A 0.25 .. 20.00 A; ∞ ∞ A
2695 T 3I0p Dir.   0.05 .. 3.00 sec; ∞ 0.50 sec T 3I0p Dir.:Inv.-Time delay for IEC-Char
2696 D 3I0p Dir.   0.50 .. 15.00 ; ∞ 5.00 D 3I0p Dir.:Inv.-Time delay for ANSI-Ch.
2697 T 3I0p Add Dir.   0.00 .. 30.00 sec 0.00 sec T 3I0p Dir.: additional time delay
2698 IPDir.Telep/BI   NO
YES
NO Instantaneous trip via Tele- prot./BI
2699 IP Dir. SOTF   NO
YES
NO Instantaneous trip after SwitchOnToFault

Automatic Reclosure Function (optional)

Addr. Parameter C Setting Options Default Setting Comments
3401 AUTO RECLOSE   OFF
ON
ON Auto-Reclose Function
3402 CB? 1.TRIP   YES
NO
NO CB ready interrogation at 1st trip
3403 T-RECLAIM   0.50 .. 300.00 sec 3.00 sec Reclaim time after successful AR cycle
3403 T-RECLAIM   0.50 .. 300.00 sec; 0 3.00 sec Reclaim time after successful AR cycle
3404 T-BLOCK MC   0.50 .. 300.00 sec; 0 1.00 sec AR blocking duration after manual close
3406 EV. FLT. RECOG.   with PICKUP
with TRIP
with TRIP Evolving fault recognition
3407 EV. FLT. MODE   Stops AutoRecl
starts 3p AR
starts 3p AR Evolving fault (during the dead time)
3408 T-Start MONITOR   0.01 .. 300.00 sec 0.50 sec AR start-signal monitoring time
3409 CB TIME OUT   0.01 .. 300.00 sec 3.00 sec Circuit Breaker (CB) Supervision Time
3410 T RemoteClose   0.00 .. 300.00 sec; ∞ 0.20 sec Send delay for remote close command
3411A T-DEAD EXT.   0.50 .. 300.00 sec; ∞ ∞ sec Maximum dead time extension
3420 AR WITH DIFF   YES
NO
YES AR with differential protection ?
3421 AR w/ SOTF-O/C   YES
NO
YES AR with switch-onto-fault overcur- rent ?
3423 AR WITH I.TRIP   YES
NO
YES AR with intertrip ?
3424 AR w/ DTT   YES
NO
YES AR with direct transfer trip ?
3425 AR w/ BackUpO/C   YES
NO
YES AR with back-up overcurrent ?
3430 AR TRIP 3pole   YES
NO
YES 3pole TRIP by AR
3431 DLC / RDT   WITHOUT
DLC
WITHOUT Dead Line Check / Reduced Dead Time
3433 T-ACTION ADT   0.01 .. 300.00 sec; ∞ 0.20 sec Action time
3434 T-MAX ADT   0.50 .. 3000.00 sec 5.00 sec Maximum dead time
3435 ADT 1p allowed   YES
NO
NO 1pole TRIP allowed
3436 ADT CB? CLOSE   YES
NO
NO CB ready interrogation before reclosing
3437 ADT SynRequest   YES
NO
NO Request for synchro-check after 3pole AR
3438 T U-stable   0.10 .. 30.00 sec 0.10 sec Supervision time for dead/live voltage
3440 U-live>   30 .. 90 V 48 V Voltage threshold for live line or bus
3441 U-dead<   2 .. 70 V 30 V Voltage threshold for dead line or bus
3450 1.AR: START   YES
NO
YES Start of AR allowed in this cycle
3451 1.AR: T-ACTION   0.01 .. 300.00 sec; ∞ 0.20 sec Action time
3453 1.AR Tdead 1Flt   0.01 .. 1800.00 sec; ∞ 1.20 sec Dead time after 1phase faults
3454 1.AR Tdead 2Flt   0.01 .. 1800.00 sec; ∞ 1.20 sec Dead time after 2phase faults
3455 1.AR Tdead 3Flt   0.01 .. 1800.00 sec; ∞ 0.50 sec Dead time after 3phase faults
3456 1.AR Tdead1Trip   0.01 .. 1800.00 sec; ∞ 1.20 sec Dead time after 1pole trip
3457 1.AR Tdead3Trip   0.01 .. 1800.00 sec; ∞ 0.50 sec Dead time after 3pole trip
3458 1.AR: Tdead EV.   0.01 .. 1800.00 sec 1.20 sec Dead time after evolving fault
3459 1.AR: CB? CLOSE   YES
NO
NO CB ready interrogation before reclosing
3460 1.AR SynRequest   YES
NO
NO Request for synchro-check after 3pole AR
3461 2.AR: START   YES
NO
NO AR start allowed in this cycle
3462 2.AR: T-ACTION   0.01 .. 300.00 sec; ∞ 0.20 sec Action time
3464 2.AR Tdead 1Flt   0.01 .. 1800.00 sec; ∞ 1.20 sec Dead time after 1phase faults
3465 2.AR Tdead 2Flt   0.01 .. 1800.00 sec; ∞ 1.20 sec Dead time after 2phase faults
3466 2.AR Tdead 3Flt   0.01 .. 1800.00 sec; ∞ 0.50 sec Dead time after 3phase faults
3467 2.AR Tdead1Trip   0.01 .. 1800.00 sec; ∞ ∞ sec Dead time after 1pole trip
3468 2.AR Tdead3Trip   0.01 .. 1800.00 sec; ∞ 0.50 sec Dead time after 3pole trip
3469 2.AR: Tdead EV.   0.01 .. 1800.00 sec 1.20 sec Dead time after evolving fault
3470 2.AR: CB? CLOSE   YES
NO
NO CB ready interrogation before reclosing
3471 2.AR SynRequest   YES
NO
NO Request for synchro-check after 3pole AR
3472 3.AR: START   YES
NO
NO AR start allowed in this cycle
3473 3.AR: T-ACTION   0.01 .. 300.00 sec; ∞ 0.20 sec Action time
3475 3.AR Tdead 1Flt   0.01 .. 1800.00 sec; ∞ 1.20 sec Dead time after 1phase faults
3476 3.AR Tdead 2Flt   0.01 .. 1800.00 sec; ∞ 1.20 sec Dead time after 2phase faults
3477 3.AR Tdead 3Flt   0.01 .. 1800.00 sec; ∞ 0.50 sec Dead time after 3phase faults
3478 3.AR Tdead1Trip   0.01 .. 1800.00 sec; ∞ ∞ sec Dead time after 1pole trip
3479 3.AR Tdead3Trip   0.01 .. 1800.00 sec; ∞ 0.50 sec Dead time after 3pole trip
3480 3.AR: Tdead EV.   0.01 .. 1800.00 sec 1.20 sec Dead time after evolving fault
3481 3.AR: CB? CLOSE   YES
NO
NO CB ready interrogation before reclosing
3482 3.AR SynRequest   YES
NO
NO Request for synchro-check after 3pole AR
3483 4.AR: START   YES
NO
NO AR start allowed in this cycle
3484 4.AR: T-ACTION   0.01 .. 300.00 sec; ∞ 0.20 sec Action time
3486 4.AR Tdead 1Flt   0.01 .. 1800.00 sec; ∞ 1.20 sec Dead time after 1phase faults
3487 4.AR Tdead 2Flt   0.01 .. 1800.00 sec; ∞ 1.20 sec Dead time after 2phase faults
3488 4.AR Tdead 3Flt   0.01 .. 1800.00 sec; ∞ 0.50 sec Dead time after 3phase faults
3489 4.AR Tdead1Trip   0.01 .. 1800.00 sec; ∞ ∞ sec Dead time after 1pole trip
3490 4.AR Tdead3Trip   0.01 .. 1800.00 sec; ∞ 0.50 sec Dead time after 3pole trip
3491 4.AR: Tdead EV.   0.01 .. 1800.00 sec 1.20 sec Dead time after evolving fault
3492 4.AR: CB? CLOSE   YES
NO
NO CB ready interrogation before reclosing
3493 4.AR SynRequest   YES
NO
NO Request for synchro-check after 3pole AR

Undervoltage and Overvoltage Protection (optional)

Addr. Parameter C Setting Options Default Setting Comments
3701 Uph-e>(>)   OFF
Alarm Only
ON
U>Alarm U>>Trip
OFF Operating mode Uph-e overvoltage prot.
3702 Uph-e>   1.0 .. 170.0 V; ∞ 85.0 V Uph-e> Pickup
3703 T Uph-e>   0.00 .. 100.00 sec; ∞ 2.00 sec T Uph-e> Time Delay
3704 Uph-e>>   1.0 .. 170.0 V; ∞ 100.0 V Uph-e>> Pickup
3705 T Uph-e>>   0.00 .. 100.00 sec; ∞ 1.00 sec T Uph-e>> Time Delay
3709A Uph-e>(>) RESET   0.30 .. 0.99 0.98 Uph-e>(>) Reset ratio
3711 Uph-ph>(>)   OFF
Alarm Only
ON
U>Alarm U>>Trip
OFF Operating mode Uph-ph overvoltage prot.
3712 Uph-ph>   2.0 .. 220.0 V; ∞ 150.0 V Uph-ph> Pickup
3713 T Uph-ph>   0.00 .. 100.00 sec; ∞ 2.00 sec T Uph-ph> Time Delay
3714 Uph-ph>>   2.0 .. 220.0 V; ∞ 175.0 V Uph-ph>> Pickup
3715 T Uph-ph>>   0.00 .. 100.00 sec; ∞ 1.00 sec T Uph-ph>> Time Delay
3719A Uphph>(>) RESET   0.30 .. 0.99 0.98 Uph-ph>(>) Reset ratio
3721 3U0>(>) (or Ux)   OFF
Alarm Only
ON
U>Alarm U>>Trip
OFF Operating mode 3U0 (or Ux) overvoltage
3722 3U0>   1.0 .. 220.0 V; ∞ 30.0 V 3U0> Pickup (or Ux>)
3723 T 3U0>   0.00 .. 100.00 sec; ∞ 2.00 sec T 3U0> Time Delay (or T Ux>)
3724 3U0>>   1.0 .. 220.0 V; ∞ 50.0 V 3U0>> Pickup (or Ux>>)
3725 T 3U0>>   0.00 .. 100.00 sec; ∞ 1.00 sec T 3U0>> Time Delay (or T Ux>>)
3728A 3U0>(>) Stabil.   ON
OFF
ON 3U0>(>): Stabilization 3U0-Meas- urement
3729A 3U0>(>) RESET   0.30 .. 0.99 0.95 3U0>(>) Reset ratio (or Ux)
3731 U1>(>)   OFF
Alarm Only
ON
U>Alarm U>>Trip
OFF Operating mode U1 overvoltage prot.
3732 U1>   2.0 .. 220.0 V; ∞ 150.0 V U1> Pickup
3733 T U1>   0.00 .. 100.00 sec; ∞ 2.00 sec T U1> Time Delay
3734 U1>>   2.0 .. 220.0 V; ∞ 175.0 V U1>> Pickup
3735 T U1>>   0.00 .. 100.00 sec; ∞ 1.00 sec T U1>> Time Delay
3736 U1> Compound   ON
OFF
OFF U1> with Compounding
3737 U1>> Compound   ON
OFF
OFF U1>> with Compounding
3739A U1>(>) RESET   0.30 .. 0.99 0.98 U1>(>) Reset ratio
3741 U2>(>)   OFF
Alarm Only
ON
U>Alarm U>>Trip
OFF Operating mode U2 overvoltage prot.
3742 U2>   2.0 .. 220.0 V; ∞ 30.0 V U2> Pickup
3743 T U2>   0.00 .. 100.00 sec; ∞ 2.00 sec T U2> Time Delay
3744 U2>>   2.0 .. 220.0 V; ∞ 50.0 V U2>> Pickup
3745 T U2>>   0.00 .. 100.00 sec; ∞ 1.00 sec T U2>> Time Delay
3749A U2>(>) RESET   0.30 .. 0.99 0.98 U2>(>) Reset ratio
3751 Uph-e<(<)   OFF
Alarm Only
ON
U>Alarm U>>Trip
OFF Operating mode Uph-e under- voltage prot.
3752 Uph-e<   1.0 .. 100.0 V; 0 30.0 V Uph-e< Pickup
3753 T Uph-e<   0.00 .. 100.00 sec; ∞ 2.00 sec T Uph-e< Time Delay
3754 Uph-e<<   1.0 .. 100.0 V; 0 10.0 V Uph-e<< Pickup
3755 T Uph-e<<   0.00 .. 100.00 sec; ∞ 1.00 sec T Uph-e<< Time Delay
3758 CURR.SUP. Uphe<   ON
OFF
ON Current supervision (Uph-e)
3759A Uph-e<(<) RESET   1.01 .. 1.20 1.05 Uph-e<(<) Reset ratio
3761 Uph-ph<(<)   OFF
Alarm Only
ON
U>Alarm U>>Trip
OFF Operating mode Uph-ph under- voltage prot.
3762 Uph-ph<   1.0 .. 175.0 V; 0 50.0 V Uph-ph< Pickup
3763 T Uph-ph<   0.00 .. 100.00 sec; ∞ 2.00 sec T Uph-ph< Time Delay
3764 Uph-ph<<   1.0 .. 175.0 V; 0 17.0 V Uph-ph<< Pickup
3765 T Uphph<<   0.00 .. 100.00 sec; ∞ 1.00 sec T Uph-ph<< Time Delay
3768 CURR.SUP.Uphph<   ON
OFF
ON Current supervision (Uph-ph)
3769A Uphph<(<) RESET   1.01 .. 1.20 1.05 Uph-ph<(<) Reset ratio
3771 U1<(<)   OFF
Alarm Only
ON
U>Alarm U>>Trip
OFF Operating mode U1 undervoltage prot.
3772 U1<   1.0 .. 100.0 V; 0 30.0 V U1< Pickup
3773 T U1<   0.00 .. 100.00 sec; ∞ 2.00 sec T U1< Time Delay
3774 U1<<   1.0 .. 100.0 V; 0 10.0 V U1<< Pickup
3775 T U1<<   0.00 .. 100.00 sec; ∞ 1.00 sec T U1<< Time Delay
3778 CURR.SUP.U1<   ON
OFF
ON Current supervision (U1)
3779A U1<(<) RESET   1.01 .. 1.20 1.05 U1<(<) Reset ratio

Frequency Protection (optional)

Addr. Parameter C Setting Options Default Setting Comments
3601 O/U FREQ. f1   ON: Alarm only
ON: with Trip
OFF
ON: Alarm only Over/Under Frequency Protection stage f1
3602 f1 PICKUP   45.50 .. 54.50 Hz 49.50 Hz f1 Pickup
3603 f1 PICKUP   55.50 .. 64.50 Hz 59.50 Hz f1 Pickup
3604 T f1   0.00 .. 600.00 sec 60.00 sec T f1 Time Delay
3611 O/U FREQ. f2   ON: Alarm only
ON: with Trip
OFF
ON: Alarm only Over/Under Frequency Protection stage f2
3612 f2 PICKUP   45.50 .. 54.50 Hz 49.00 Hz f2 Pickup
3613 f2 PICKUP   55.50 .. 64.50 Hz 57.00 Hz f2 Pickup
3614 T f2   0.00 .. 600.00 sec 30.00 sec T f2 Time Delay
3621 O/U FREQ. f3   ON: Alarm only
ON: with Trip
OFF
ON: Alarm only Over/Under Frequency Protection stage f3
3622 f3 PICKUP   45.50 .. 54.50 Hz 47.50 Hz f3 Pickup
3623 f3 PICKUP   55.50 .. 64.50 Hz 59.50 Hz f3 Pickup
3624 T f3   0.00 .. 600.00 sec 3.00 sec T f3 Time Delay
3631 O/U FREQ. f4   ON: Alarm only
ON: with Trip
OFF
ON: Alarm only Over/Under Frequency Protection stage f4
3632 f4 PICKUP   45.50 .. 54.50 Hz 51.00 Hz f4 Pickup
3633 f4 PICKUP   55.50 .. 64.50 Hz 62.00 Hz f4 Pickup
3634 T f4   0.00 .. 600.00 sec 30.00 sec T f4 Time Delay

Circuit Breaker Failure Protection

Addr. Parameter C Setting Options Default Setting Comments
3901 FCT BreakerFail   ON
OFF
ON Breaker Failure Protection
3902 I> BF 1A 0.05 .. 20.00 A 0.10 A Pick-up threshold I>
5A 0.25 .. 100.00 A 0.50 A
3903 1p-RETRIP (T1)   NO
YES
YES 1pole retrip with stage T1 (local trip)
3904 T1-1pole   0.00 .. 30.00 sec; ∞ 0.00 sec T1, Delay after 1pole start (local trip)
3905 T1-3pole   0.00 .. 30.00 sec; ∞ 0.00 sec T1, Delay after 3pole start (local trip)
3906 T2   0.00 .. 30.00 sec; ∞ 0.15 sec T2, Delay of 2nd stage (busbar trip)
3907 T3-BkrDefective   0.00 .. 30.00 sec; ∞ 0.00 sec T3, Delay for start with defective bkr.
3908 Trip BkrDefect.   NO
with T1-trip
with T2-trip
w/ T1/T2-trip
NO Trip output selection with defective bkr
3909 Chk BRK CONTACT   NO
YES
YES Check Breaker contacts
3912 3I0> BF 1A 0.05 .. 20.00 A 0.10 A Pick-up threshold 3I0>
5A 0.25 .. 100.00 A 0.50 A
3913 T2StartCriteria   With exp. of T1
Parallel withT1
Parallel withT1 T2 Start Criteria
3921 End Flt. stage   ON
OFF
OFF End fault protection
3922 T-EndFault   0.00 .. 30.00 sec; ∞ 2.00 sec Trip delay of end fault protection
3931 PoleDiscrepancy   ON
OFF
OFF Pole Discrepancy supervi- sion
3932 T-PoleDiscrep.   0.00 .. 30.00 sec; ∞ 2.00 sec Trip delay with pole discrepancy

Thermal Overload Protection

Addr. Parameter C Setting Options Default Setting Comments
4201 Ther. OVERLOAD   OFF
ON
Alarm Only
OFF Thermal overload protec- tion
4202 K-FACTOR   0.10 .. 4.00 1.10 K-Factor
4203 TIME CONSTANT   1.0 .. 999.9 min 100.0 min Time Constant
4204 Θ ALARM   50 .. 100 % 90 % Thermal Alarm Stage
4205 I ALARM 1A 0.10 .. 4.00 A 1.00 A Current Overload Alarm Setpoint
5A 0.50 .. 20.00 A 5.00 A
4206 CALC. METHOD   Θ max
Average Θ
Θ from Imax
Θ max Method of Acquiring Temperature

Measurement Supervision

Addr. Parameter C Setting Options Default Setting Comments
2901 MEASURE. SUPERV   ON
OFF
ON Measurement Supervision
2902A BALANCE U-LIMIT   10 .. 100 V 50 V Voltage Threshold for Balance Monitoring
2903A BAL. FACTOR U   0.58 .. 0.95 0.75 Balance Factor for Voltage Monitor
2904A BALANCE I LIMIT 1A 0.10 .. 1.00 A 0.50 A Current Balance Monitor
5A 0.50 .. 5.00 A 2.50 A
2905A BAL. FACTOR I   0.10 .. 0.95 0.50 Balance Factor for Current Monitor
2906A ΣI THRESHOLD 1A 0.10 .. 2.00 A 0.25 A Summated Current Moni- toring Threshold
5A 0.50 .. 10.00 A 1.25 A
2907A ΣI FACTOR   0.00 .. 0.95 0.50 Summated Current Moni- toring Factor
2908A T BAL. U LIMIT   5 .. 100 sec 5 sec T Balance Factor for Voltage Monitor
2909A T BAL. I LIMIT   5 .. 100 sec 5 sec T Current Balance Monitor
2910 FUSE FAIL MON.   ON
OFF
ON Fuse Failure Monitor
2911A FFM U>(min)   10 .. 100 V 30 V Minimum Voltage Threshold U>
2912A FFM I< (max) 1A 0.05 .. 1.00 A 0.10 A Maximum Current Threshold I<
5A 0.25 .. 5.00 A 0.50 A
2913A FFM U<max (3ph)   2 .. 100 V 15 V Maximum Voltage Threshold U< (3phase)
2914A FFM Idelta (3p) 1A 0.05 .. 1.00 A 0.10 A Delta Current Threshold (3phase)
5A 0.25 .. 5.00 A 0.50 A
2915 V-Supervision   w/ CURR.SUP
w/ I> & CBaux
OFF
w/ CURR.SUP Voltage Failure Supervision
2916A T V-Supervision   0.00 .. 30.00 sec 3.00 sec Delay Voltage Failure Supervision
2921 T mcb   0 .. 30 ms 0 ms VT mcb operating time
2931 BROKEN WIRE   ON
OFF
Alarm only
OFF Fast broken current-wire supervision
2933 FAST Σ i SUPERV   ON
OFF
ON State of fast current summation supervis
2935A ΔI min 1A 0.05 .. 1.00 A 0.10 A Min. current diff. for wire break det.
5A 0.25 .. 5.00 A 0.50 A
2941 φA   0 .. 359 ° 200 ° Limit setting PhiA
2942 φB   0 .. 359 ° 340 ° Limit setting PhiB
2943 I1> 1A 0.05 .. 2.00 A 0.05 A Minimum value I1>
5A 0.25 .. 10.00 A 0.25 A
2944 U1>   2 .. 70 V 20 V Minimum value U1>

Trip Circuit Supervision

Addr. Parameter C Setting Options Default Setting Comments
4001 FCT TripSuperv.   ON
OFF
OFF TRIP Circuit Supervision is
4002 No. of BI   1 .. 2 2 Number of Binary Inputs per trip circuit
4003 Alarm Delay   1 .. 30 sec 2 sec Delay Time for alarm

Device

Addr. Parameter C Setting Options Default Setting Comments
610 FltDisp.LED/LCD   Target on PU
Target on TRIP
Target on PU Fault Display on LED / LCD
625A T MIN LED HOLD   0 .. 60 min; ∞ 0 min Minimum hold time of latched LEDs
640 Start image DD   image 1
image 2
image 3
image 4
image 5
image 6
image 1 Start image Default Display

Oscillographic Fault Records

Addr. Parameter C Setting Options Default Setting Comments
402A WAVEFORMTRIGGER   Save w. Pickup
Save w. TRIP
Start w. TRIP
Save w. Pickup Waveform Capture
403A WAVEFORM DATA   Fault event
Pow.Sys.Flt.
Fault event Scope of Waveform Data
410 MAX. LENGTH   0.30 .. 5.00 sec 2.00 sec Max. length of a Waveform Capture Record
411 PRE. TRIG. TIME   0.05 .. 0.50 sec 0.25 sec Captured Waveform Prior to Trigger
412 POST REC. TIME   0.05 .. 0.50 sec 0.10 sec Captured Waveform after Event
415 BinIn CAPT.TIME   0.10 .. 5.00 sec; ∞ 0.50 sec Capture Time via Binary Input