Siemens / SIPROTEC 7SD5 V4.7 setting parameters & highlights (SI4013)

Table of Contents

Overview

The SIPROTEC 7SD5 relay provides full scheme differential protection and incorporates all functions usually required for the protection of power lines. It is designed for all power and distribution levels and protects lines with two up to six line ends.

For more detailed information on “SIPROTEC 7SD5 V4.7” relays, refer to SIPROTEC 4 devices manuals.

To see other supported devices, click here.


Functional Scope

Addr. Parameter C Setting Options Default Setting Comments
103 Grp Chge OPTION   Disabled
Enabled
Disabled Setting Group Change Option
110 Trip mode   3pole only
1-/3pole
3pole only Trip mode
112 DIFF.PROTECTION   Disabled
Enabled
Enabled Differential protection
115 Phase Distance   Quadrilateral
MHO
Disabled
Quadrilateral Phase Distance
116 Earth Distance   Quadrilateral
MHO
Disabled
Quadrilateral Earth Distance
117 Dis. PICKUP   Z< (quadrilat.)
I> (overcurr.)
U/I
U/I/φ
Disabled
Z< (quadrilat.) Distance protection pickup program
119 Iph>(Z1)   Disabled
Enabled
Disabled Additional Threshold Iph>(Z1)
120 Power Swing   Disabled
Enabled
Disabled Power Swing detection
121 Teleprot. Dist.   PUTT (Z1B)
PUTT (Pickup) POTT
Dir.Comp.Pickup UNBLOCKING BLOCKING
Rev. Interlock Pilot wire comp Disabled
Disabled Teleprotection for Distance prot.
122 DTT Direct Trip   Disabled
Enabled
Disabled DTT Direct Transfer Trip
124 HS/SOTF-O/C   Disabled
Enabled
Disabled Instantaneous HighSpeed/SOTF Overcurrent
125 Weak Infeed   Disabled
Enabled
Logic no. 2
Disabled Weak Infeed (Trip and/or Echo)
126 Back-Up O/C   Disabled
TOC IEC
TOC ANSI
TOC IEC Backup overcurrent
130 Sens. Earth Flt   Disabled
Enabled
Disabled Sensitive Earth Flt.(comp/ isol. starp.)
131 Earth Fault O/C   Disabled T
OC IEC
TOC ANSI
TOC Logarithm.
Definite Time
U0 inverse
Sr inverse
Disabled Earth fault overcurrent
132 Teleprot. E/F   Dir.Comp.Pickup
UNBLOCKING
BLOCKING
Disabled
Disabled Teleprotection for Earth fault over- curr.
133 Auto Reclose   1 AR-cycle
2 AR-cycles
3 AR-cycles
4 AR-cycles
5 AR-cycles
6 AR-cycles
7 AR-cycles
8 AR-cycles
ADT
Disabled
Disabled Auto-Reclose Function
134 AR control mode   Pickup w/ Tact
Pickup w/o Tact
Trip w/ Tact
Trip w/o Tact
Trip w/o Tact Auto-Reclose control mode
135 Synchro-Check   Disabled
Enabled
Disabled Synchronism and Voltage Check
136 FREQUENCY Prot.   Disabled
Enabled
Disabled Over / Underfrequency Protection
137 U/O VOLTAGE   Disabled
Enabled
Enabl. w. comp.
Disabled Under / Overvoltage Protection
138 Fault Locator   Disabled
Enabled
with BCD-output
Disabled Fault Locator
139 BREAKER FAILURE   Disabled
Enabled
enabled w/ 3I0>
Disabled Breaker Failure Protection
140 Trip Cir. Sup.   Disabled
1 trip circuit
2 trip circuits
3 trip circuits
Disabled Trip Circuit Supervision
141 REF PROT.   Disabled
Enabled
Disabled Restricted earth fault protection
142 Therm.Overload   Disabled
Enabled
Disabled Thermal Overload Protection
143 TRANSFORMER   NO
YES
NO Transformer inside protection zone
144 V-TRANSFORMER   Not connected
connected
connected Voltage transformers
145 P. INTERFACE 1   Enabled
Disabled
IEEE C37.94
Enabled Protection Interface 1 (Port D)
146 P. INTERFACE 2   Disabled
Enabled
IEEE C37.94
Disabled Protection Interface 2 (Port E)
147 NUMBER OF RELAY   2 relays
3 relays
4 relays
5 relays
6 relays
2 relays Number of relays
148 GPS-SYNC.   Disabled
Enabled
Disabled GPS synchronization
149 charge I comp.   Disabled
Enabled
Disabled charging current compensation
160 L-sections FL   1 Section
2 Sections
3 Sections
1 Section Line sections for fault locator

General Power System Data (Power System Data 1)

Addr. Parameter C Setting Options Default Setting Comments
201 CT Starpoint   towards Line
towards Busbar
towards Line CT Starpoint
203 Unom PRIMARY   0.4 .. 1200.0 kV 400.0 kV Rated Primary Voltage
204 Unom SECONDARY   80 .. 125 V 100 V Rated Secondary Voltage (Ph-Ph)
205 CT PRIMARY   10 .. 10000 A 1000 A CT Rated Primary Current
206 CT SECONDARY   1A
5A
1A CT Rated Secondary Current
207 SystemStarpoint   Solid Earthed
Peterson-Coil
Isolated
Solid Earthed System Starpoint is
208A 1-1/2 CB   NO
YES
NO 1-1/2 Circuit breaker arrangement
210 U4 transformer   Not connected
Udelta transf.
Usy2 transf.
Ux transformer
Not connected U4 voltage transformer is
211 Uph / Udelta   0.10 .. 9.99 1.73 Matching ratio Phase-VT To Open- Delta-VT
212 Usy2 connection   L1-E
L2-E
L3-E
L1-L2
L2-L3
L3-L1
L1-E VT connection for Usy2
214A φ Usy2-Usy1   0 .. 360 ° 0 ° Angle adjustment Usy2-Usy1
215 Usy1/Usy2 ratio   0.50 .. 2.00 1.00 Matching ratio Usy1 / Usy2
220 I4 transformer   Not connected
In prot. line
In paral. line
IY starpoint
In prot. line I4 current transformer is
221 I4/Iph CT   0.010 .. 5.000 1.000 Matching ratio I4/Iph for CT’s
230 Rated Frequency   50 Hz
60 Hz
50 Hz Rated Frequency
236 Distance Unit   km
Miles
km Distance measurement unit
237 Format Z0/Z1   RE/RL, XE/XL
K0
RE/RL, XE/XL Setting format for zero seq.comp. format
238A EarthFltO/C 1p   stages together
stages separat.
stages together Earth Fault O/C: setting for 1pole AR
239 T-CB close   0.01 .. 0.60 sec 0.06 sec Closing (operating) time of CB
240A TMin TRIP CMD   0.02 .. 30.00 sec 0.10 sec Minimum TRIP Command Duration
241A TMax CLOSE CMD   0.01 .. 30.00 sec 1.00 sec Maximum Close Command Dura- tion
242 T-CBtest-dead   0.00 .. 30.00 sec 0.10 sec Dead Time for CB test-autoreclo- sure
251 K_ALF/K_ALF_N   1.00 .. 10.00 1.00 k_alf/k_alf nominal
253 E% ALF/ALF_N   0.5 .. 50.0 % 5.0 % CT Error in % at k_alf/k_alf nominal
254 E% K_ALF_N   0.5 .. 50.0 % 15.0 % CT Error in % at k_alf nominal

Change Group

Addr. Parameter C Setting Options Default Setting Comments
301 ACTIVE GROUP   Group A
Group B
Group C
Group D
Group A Active Setting Group is
302 CHANGE   Group A
Group B
Group C
Group D
Binary Input
Protocol
Group A Change to Another Setting Group

General Protection Data (Power System Data 2)

Addr. Parameter C Setting Options Default Setting Comments
1103 FullScaleVolt.   0.4 .. 1200.0 kV 400.0 kV Measurement: Full Scale Voltage (100%)
1104 FullScaleCurr.   10 .. 10000 A 1000 A Measurement: Full Scale Current (100%)
1105 Line Angle   10 .. 89 ° 85 ° Line Angle
1106 OPERATION POWER   0.2 .. 5000.0 MVA 692.8 MVA Operational power of protection zone
1107 P,Q sign   not reversed
reversed
not reversed P,Q operational measured values sign
1111 x’ 1A 0.0050 .. 9.5000 Ω/km 0.1500 Ω/km x’ – Line Reactance per length unit
5A 0.0010 .. 1.9000 Ω/km 0.0300 Ω/km
1111 x’ 1A 0.0050 .. 15.0000 Ω/mi 0.2420 Ω/mi x’ – Line Reactance per length unit
5A 0.0010 .. 3.0000 Ω/mi 0.0484 Ω/mi
1112 c’ 1A 0.000 .. 100.000 µF/km 0.010 µF/km c’ – capacit. per unit line len. µF/km
5A 0.000 .. 500.000 µF/km 0.050 µF/km
1112 c’ 1A 0.000 .. 160.000 µF/mi 0.016 µF/mi c’ – capacit. per unit line len. µF/mile
5A 0.000 .. 800.000 µF/mi 0.080 µF/mi
1113 Line Length   0.1 .. 1000.0 km 100.0 km Line Length
1113 Line Length   0.1 .. 650.0 Miles 62.1 Miles Line Length
1114 Tot.Line Length   0.1 .. 1000.0 km 100.0 km Total Line Length
1114 Tot.Line Length   0.1 .. 650.0 Miles 62.1 Miles Total Line Length
1116 RE/RL(Z1)   -0.33 .. 10.00 1.00 Zero seq. comp. factor RE/RL for Z1
1117 XE/XL(Z1)   -0.33 .. 10.00 1.00 Zero seq. comp. factor XE/XL for Z1
1118 RE/RL(> Z1)   -0.33 .. 10.00 1.00 Zero seq. comp.factor RE/ RL(> Z1)
1119 XE/XL(> Z1)   -0.33 .. 10.00 1.00 Zero seq. comp.factor XE/ XL(> Z1)
1120 K0 (Z1)   0.000 .. 4.000 1.000 Zero seq. comp. factor K0 for zone Z1
1121 Angle K0(Z1)   -180.00 .. 180.00 ° 0.00 ° Zero seq. comp. angle for zone Z1
1122 K0 (> Z1)   0.000 .. 4.000 1.000 Zero seq.comp.factor K0,higher zones >Z1
1123 Angle K0(> Z1)   -180.00 .. 180.00 ° 0.00 ° Zero seq. comp. angle, higher zones >Z1
1124 center phase   unknown/sym.
Phase 1
Phase 2
Phase 3
unknown/sym. center phase of feeder
1125 C0/C1   0.01 .. 10.00 0.75 Compensation factor C0/C1
1126 RM/RL ParalLine   0.00 .. 8.00 0.00 Mutual Parallel Line comp. ratio RM/RL
1127 XM/XL ParalLine   0.00 .. 8.00 0.00 Mutual Parallel Line comp. ratio XM/XL
1128 RATIO Par. Comp   50 .. 95 % 85 % Neutral current RATIO Parallel Line Comp
1130A PoleOpenCurrent 1A 0.05 .. 1.00 A 0.10 A Pole Open Current Threshold
5A 0.25 .. 5.00 A 0.50 A
1131A PoleOpenVoltage   2 .. 70 V 30 V Pole Open Voltage Threshold
1132A SI Time all Cl.   0.01 .. 30.00 sec 0.10 sec Seal-in Time after ALL closures
1133A T DELAY SOTF   0.05 .. 30.00 sec 0.25 sec minimal time for line open before SOTF
1134 Line Closure   only with ManCl
I OR U or ManCl
CB OR I or M/C
I or Man.Close
I or Man.Close Recognition of Line Closures with
1135 Reset Trip CMD   CurrentOpenPole
Current AND CB
Pickup Reset
CurrentOpenPole RESET of Trip Command
1136 OpenPoleDetect.   OFF
Current AND CB
w/ measurement
w/ measurement open pole detector
1140A I-CTsat. Thres. 1A 0.2 .. 50.0 A; ∞ 20.0 A CT Saturation Threshold
5A 1.0 .. 250.0 A; ∞ 100.0 A
1150A SI Time Man.Cl   0.01 .. 30.00 sec 0.30 sec Seal-in Time after MANUAL closures
1151 SYN.MAN.CL   with Sync-check
w/o Sync-check
NO
NO Manual CLOSE COMMAND
generation
1152 Man.Clos. Imp.   (Einstellmoglichkeiten anwendungsabhangig) none MANUAL Closure Impulse after CONTROL
1155 3pole coupling   with PICKUP
with TRIP
with TRIP 3 pole coupling
1156A Trip2phFlt   3pole
1pole leading Ø
1pole lagging Ø
3pole Trip type with 2phase faults
1161 VECTOR GROUP U   0 .. 11 0 Vector group numeral for voltage
1162 VECTOR GROUP I   0 .. 11 0 Vector group numeral for current
1163 TRANS STP IS   Solid Earthed
Not Earthed
Solid Earthed Transformer starpoint is
1511 Distance Angle   30 .. 90 ° 85 ° Angle of inclination, distance charact.
6001 S1: Line angle   30 .. 89 ° 85 ° S1: Line angle
6002 S1: x’ 1A 0.0050 .. 9.5000 Ω/km 0.1500 Ω/km S1: feeder reactance per km: x’
5A 0.0010 .. 1.9000 Ω/km 0.0300 Ω/km
6002 S1: x’ 1A 0.0050 .. 15.0000 Ω/mi 0.2420 Ω/mi S1: feeder reactance per mile: x’
5A 0.0010 .. 3.0000 Ω/mi 0.0484 Ω/mi
6003 S1: c’ 1A 0.000 .. 100.000 µF/km 0.010 µF/km S1: feeder capacitance c’ in
µF/km
5A 0.000 .. 500.000 µF/km 0.050 µF/km
6003 S1: c’ 1A 0.000 .. 160.000 µF/mi 0.016 µF/mi S1: feeder capacitance c’ in
µF/mile
5A 0.000 .. 800.000 µF/mi 0.080 µF/mi
6004 S1: Line length   0.1 .. 1000.0 km 100.0 km S1: Line length in kilometer
6004 S1: line length   0.1 .. 650.0 Miles 62.1 Miles S1: Line length in kilometer
6008 S1: center ph.   unknown/sym.
Phase 1
Phase 2
Phase 3
unknown/sym. S1: center phase
6009 S1: XE/XL   -0.33 .. 10.00 1.00 S1: Zero seq. compen- sating factor XE/XL
6010 S1: RE/RL   -0.33 .. 10.00 1.00 S1: Zero seq. compen- sating factor RE/RL
6011 S1: K0   0.000 .. 4.000 1.000 S1: Zero seq. compen- sating factor K0
6012 S1: angle K0   -180.00 .. 180.00 ° 0.00 ° S1: Zero seq. compen- sating angle of K0
6021 S2: Line angle   30 .. 89 ° 85 ° S2: Line angle
6022 S2: x’ 1A 0.0050 .. 9.5000 Ω/km 0.1500 Ω/km S2: feeder reactance per km: x’
5A 0.0010 .. 1.9000 Ω/km 0.0300 Ω/km
6022 S2: x’ 1A 0.0050 .. 15.0000 Ω/mi 0.2420 Ω/mi S2: feeder reactance per mile: x’
5A 0.0010 .. 3.0000 Ω/mi 0.0484 Ω/mi
6023 S2: c’ 1A 0.000 .. 100.000 µF/km 0.010 µF/km S2: feeder capacitance c’ in
µF/km
5A 0.000 .. 500.000 µF/km 0.050 µF/km
6023 S2: c’ 1A 0.000 .. 160.000 µF/mi 0.016 µF/mi S2: feeder capacitance c’ in
µF/mile
5A 0.000 .. 800.000 µF/mi 0.080 µF/mi
6024 S2: Line length   0.1 .. 1000.0 km 100.0 km S2: Line length in kilometer
6024 S2: line length   0.1 .. 650.0 Miles 62.1 Miles S2: line length in miles
6028 S2: center ph.   unknown/sym.
Phase 1
Phase 2
Phase 3
unknown/sym. S2: center phase
6029 S2: XE/XL   -0.33 .. 10.00 1.00 S2: Zero seq. compen- sating factor XE/XL
6030 S2: RE/RL   -0.33 .. 10.00 1.00 S2: Zero seq. compen- sating factor RE/RL
6031 S2: K0   0.000 .. 4.000 1.000 S2: Zero seq. compen- sating factor K0
6032 S2: angle K0   -180.00 .. 180.00 ° 0.00 ° S2: Zero seq. compen- sating angle of K0
6041 S3: Line angle   30 .. 89 ° 85 ° S3: Line angle
6042 S3: x’ 1A 0.0050 .. 9.5000 Ω/km 0.1500 Ω/km S3: feeder reactance per km: x’
5A 0.0010 .. 1.9000 Ω/km 0.0300 Ω/km
6042 S3: x’ 1A 0.0050 .. 15.0000 Ω/mi 0.2420 Ω/mi S3: feeder reactance per mile: x’
5A 0.0010 .. 3.0000 Ω/mi 0.0484 Ω/mi
6043 S3: c’ 1A 0.000 .. 100.000 µF/km 0.010 µF/km S3: feeder capacitance c’ in
µF/km
5A 0.000 .. 500.000 µF/km 0.050 µF/km
6043 S3: c’ 1A 0.000 .. 160.000 µF/mi 0.016 µF/mi S3: feeder capacitance c’ in
µF/mile
5A 0.000 .. 800.000 µF/mi 0.080 µF/mi
6044 S3: Line length   0.1 .. 1000.0 km 100.0 km S3: Line length in kilometer
6044 S3: line length   0.1 .. 650.0 Miles 62.1 Miles S3: line length in miles
6048 S3: center ph.   unknown/sym.
Phase 1
Phase 2
Phase 3
unknown/sym. S3: center phase
6049 S3: XE/XL   -0.33 .. 10.00 1.00 S3: Zero seq. compen- sating factor XE/XL
6050 S3: RE/RL   -0.33 .. 10.00 1.00 S3: Zero seq. compen- sating factor RE/RL
6051 S3: K0   0.000 .. 4.000 1.000 S3: Zero seq. compen- sating factor K0
6052 S3: angle K0   -180.00 .. 180.00 ° 0.00 ° S3: Zero seq. compen- sating angle of K0

Protection Data Interfaces

Addr. Parameter C Setting Options Default Setting Comments
4501 STATE PROT I 1   ON
OFF
ON State of protection interface 1
4502 CONNEC. 1 OVER   F.optic direct
Com c 64 kBit/s
Com c 128kBit/s
Com c 512kBit/s
C37.94 1 slot
C37.94 2 slots
C37.94 4 slots
C37.94 8 slots
F.optic direct Connection 1 over
4505A PROT 1 T-DELAY   0.1 .. 30.0 ms 30.0 ms Prot 1: Maximal permissible delay time
4506A PROT 1 UNSYM.   0.000 .. 3.000 ms 0.100 ms Prot 1: Diff. in send and receive time
4509 T-DATA DISTURB   0.05 .. 2.00 sec 0.10 sec Time delay for data disturbance alarm
4510 T-DATAFAIL   0.0 .. 60.0 sec 6.0 sec Time del for transmission failure alarm
4511 PI1 SYNCMODE   TEL and GPS T
EL or GPS
GPS SYNC OFF
TEL and GPS PI1 Synchronizationmode
4512 Td ResetRemote   0.00 .. 300.00 sec; ∞ 0.00 sec Remote signal RESET DELAY for comm.fail
4513A PROT1 max ERROR   0.5 .. 20.0 % 1.0 % Prot 1: Maximal permissible error rate
4515A PI1 BLOCK UNSYM   YES
NO
YES Prot.1: Block. due to unsym. delay time
4601 STATE PROT I 2   ON
OFF
ON State of protection interface 2
4602 CONNEC. 2 OVER   F.optic direct
Com c 64 kBit/s
Com c 128kBit/s
Com c 512kBit/s
C37.94 1 slot
C37.94 2 slots
C37.94 4 slots
C37.94 8 slots
F.optic direct Connection 2 over
4605A PROT 2 T-DELAY   0.1 .. 30.0 ms 30.0 ms Prot 2: Maximal permissible delay time
4606A PROT 2 UNSYM.   0.000 .. 3.000 ms 0.100 ms Prot 2: Diff. in send and receive time
4611 PI2 SYNCMODE   TEL and GPS
TEL or GPS
GPS SYNC OFF
TEL and GPS PI2 Synchronizationmode
4613A PROT2 max ERROR   0.5 .. 20.0 % 1.0 % Prot 2: Maximal permissible error rate
4615A PI2 BLOCK UNSYM   YES
NO
YES Prot.2: Block. due to unsym. delay time
4801 GPS-SYNC.   ON
OFF
OFF GPS synchronization
4803A TD GPS FAILD   0.5 .. 60.0 sec 2.1 sec Delay time for local GPS-pulse loss

Differential Protection Topology

Addr. Parameter C Setting Options Default Setting Comments
4701 ID OF RELAY 1   1 .. 65534 1 Identification number of relay 1
4702 ID OF RELAY 2   1 .. 65534 2 Identification number of relay 2
4703 ID OF RELAY 3   1 .. 65534 3 Identification number of relay 3
4704 ID OF RELAY 4   1 .. 65534 4 Identification number of relay 4
4705 ID OF RELAY 5   1 .. 65534 5 Identification number of relay 5
4706 ID OF RELAY 6   1 .. 65534 6 Identification number of relay 6
4710 LOCAL RELAY   relay 1
relay 2
relay 3
relay 4
relay 5
relay 6
relay 1 Local relay is

Differential Protection

Addr. Parameter C Setting Options Default Setting Comments
1201 STATE OF DIFF.   OFF
ON
ON State of differential protec- tion
1210 I-DIFF> 1A 0.10 .. 20.00 A 0.30 A I-DIFF>: Pickup value
5A 0.50 .. 100.00 A 1.50 A
1213 I-DIF>SWITCH ON 1A 0.10 .. 20.00 A 0.30 A I-DIFF>: Value under switch on condition
5A 0.50 .. 100.00 A 1.50 A
1217A T-DELAY I-DIFF>   0.00 .. 60.00 sec; ∞ 0.00 sec I-DIFF>: Trip time delay
1218 T3I0 1PHAS   0.00 .. 0.50 sec; ∞ 0.04 sec Delay 1ph-faults (comp/ isol. star-point)
1219A I> RELEASE DIFF 1A 0.10 .. 20.00 A; 0 0.00 A Min. local current to release DIFF-Trip
5A 0.50 .. 100.00 A; 0 0.00 A
1221 Ic-comp.   OFF
ON
OFF Charging current compen- sation
1224 IcSTAB/IcN   1.0 .. 4.0 1.5 Ic Stabilising / Ic Nominal
1233 I-DIFF>> 1A 0.8 .. 100.0 A; ∞ 1.2 A I-DIFF>>: Pickup value
5A 4.0 .. 500.0 A; ∞ 6.0 A
1235 I-DIF>>SWITCHON 1A 0.8 .. 100.0 A; ∞ 1.2 A I-DIFF>>: Value under switch on cond.
5A 4.0 .. 500.0 A; ∞ 6.0 A
2301 INRUSH REST.   OFF
ON
OFF Inrush Restraint
2302 2nd HARMONIC   10 .. 45 % 15 % 2nd. harmonic in % of fundamental
2303 CROSS BLOCK   NO
YES
NO Cross Block
2305 MAX INRUSH PEAK 1A 1.1 .. 25.0 A 15.0 A Maximum inrush-peak value
5A 5.5 .. 125.0 A 75.0 A
2310 CROSSB 2HM   0.00 .. 60.00 sec; ∞ 0.00 sec Time for Crossblock with 2nd harmonic

Breaker Intertrip and Remote Tripping

Addr. Parameter C Setting Options Default Setting Comments
1301 I-TRIP SEND   YES
NO
NO State of transmit. the intertrip command
1302 I-TRIP RECEIVE   Alarm only
Trip
Trip Reaction if intertrip command is receiv.
1303 T-ITRIP BI   0.00 .. 30.00 sec 0.02 sec Delay for intertrip via binary input
1304 T-ITRIP PROL BI   0.00 .. 30.00 sec 0.00 sec Prolongation for intertrip via bin.input

Distance Protection, General Settings

Addr. Parameter C Setting Options Default Setting Comments
1218 T3I0 1PHAS   0.00 .. 0.50 sec; ∞ 0.04 sec Delay 1ph-faults (comp/ isol. star-point)
1501 FCT Distance   ON
OFF
ON Distance protection
1502 Minimum Iph> 1A 0.05 .. 4.00 A 0.10 A Phase Current threshold for dist. meas.
5A 0.25 .. 20.00 A 0.50 A
1503 3I0> Threshold 1A 0.05 .. 4.00 A 0.10 A 3I0 threshold for neutral current pickup
5A 0.25 .. 20.00 A 0.50 A
1504 3U0> Threshold   1 .. 100 V; ∞ 5 V 3U0 threshold zero seq. voltage pickup
1505 3U0> COMP/ISOL.   10 .. 200 V; ∞ ∞ V 3U0> pickup (comp/ isol. star-point)
1507A 3I0>/ Iphmax   0.05 .. 0.30 0.10 3I0>-pickup-stabilisation (3I0> /Iphmax)
1508 SER-COMP.   NO
YES
NO Series compensated line
1509A E/F recognition   3I0> OR 3U0>
3I0> AND 3U0>
3I0> OR 3U0> criterion of earth fault recognition
1510 Start Timers   on Dis. Pickup
on Zone Pickup
on Dis. Pickup Condition for zone timer start
1511 Distance Angle   30 .. 90 ° 85 ° Angle of inclination, distance charact.
1515 Paral.Line Comp   NO
YES
YES Mutual coupling parall.line compensation
1520 PHASE PREF.2phe   L3 (L1) ACYCLIC
L1 (L3) ACYCLIC
L2 (L1) ACYCLIC
L1 (L2) ACYCLIC
L3 (L2) ACYCLIC
L2 (L3) ACYCLIC
L3 (L1) CYCLIC
L1 (L3) CYCLIC
All loops
L3 (L1) ACYCLIC Phase preference for 2ph-e faults
1521A 2Ph-E faults   Block leading Ø
Block lagging Ø
All loops
Ø-Ø loops only
Ø-E loops only
Block leading Ø Loop selection with 2Ph-E faults
1523 Uph-ph unbal.   5 .. 50 % 25 % Max Uph-ph unbal. for 1ph Flt. detection
1532 SOTF zone   PICKUP
Zone Z1B
Z1B undirect.
Zone Z1
Z1 undirect.
Inactive
Inactive Instantaneous trip after SwitchOnToFault
1533 Z1 blkd by diff   YES
NO
YES Zone Z1 blocked by diff. active
1541 R load (Ø-E) 1A 0.100 .. 600.000 Ω; ∞ ∞ Ω R load, minimum Load Impedance (ph-e)
5A 0.020 .. 120.000 Ω; ∞ ∞ Ω
1541 R load 1A 0.100 .. 600.000 Ω; ∞ ∞ Ω R load, minimum Load Impedance
5A 0.020 .. 120.000 Ω; ∞ ∞ Ω
1542 φ load (Ø-E)   20 .. 60 ° 45 ° PHI load, maximum Load Angle (ph-e)
1542 φ load   20 .. 60 ° 45 ° PHI load, maximum Load Angle
1543 R load (Ø-Ø) 1A 0.100 .. 600.000 Ω; ∞ ∞ Ω R load, minimum Load Impedance (ph-ph)
5A 0.020 .. 120.000 Ω; ∞ ∞ Ω
1544 φ load (Ø-Ø)   20 .. 60 ° 45 ° PHI load, maximum Load Angle (ph-ph)
1605 T1-1phase   0.00 .. 30.00 sec; ∞ 0.00 sec T1-1phase, delay for single phase faults
1606 T1-multi-phase   0.00 .. 30.00 sec; ∞ 0.00 sec T1multi-ph, delay for multi phase faults
1615 T2-1phase   0.00 .. 30.00 sec; ∞ 0.30 sec T2-1phase, delay for single phase faults
1616 T2-multi-phase   0.00 .. 30.00 sec; ∞ 0.30 sec T2multi-ph, delay for multi phase faults
1617A Trip 1pole Z2   NO
YES
NO Single pole trip for faults in Z2
1625 T3 DELAY   0.00 .. 30.00 sec; ∞ 0.60 sec T3 delay
1635 T4 DELAY   0.00 .. 30.00 sec; ∞ 0.90 sec T4 delay
1645 T5 DELAY   0.00 .. 30.00 sec; ∞ 0.90 sec T5 delay
1655 T1B-1phase   0.00 .. 30.00 sec; ∞ 0.00 sec T1B-1phase, delay for single ph. faults
1656 T1B-multi-phase   0.00 .. 30.00 sec; ∞ 0.00 sec T1B-multi-ph, delay for multi ph. faults
1657 1st AR -> Z1B   NO
YES
NO Z1B enabled before 1st AR (int. or ext.)
1665 T6 DELAY   0.00 .. 30.00 sec; ∞ 1.50 sec T6 delay
1901 PROGAM U/I   LE:Uphe/LL:Uphp
LE:Uphp/LL:Uphp
LE:Uphe/LL:Uphe
LE:Uphe/LL:I>>
LE:Uphe/LL:Uphp Pickup program U/I
1902 DELAY FORW. PU   0.00 .. 30.00 sec; ∞ 1.20 sec Trip delay for Forward- PICKUP
1903 DEL. NON-DIR PU   0.00 .. 30.00 sec; ∞ 1.20 sec Trip delay for non-direc- tional PICKUP
1910 Iph>> 1A 0.25 .. 10.00 A 1.80 A Iph>> Pickup (overcurrent)
5A 1.25 .. 50.00 A 9.00 A
1911 Iph> 1A 0.10 .. 4.00 A 0.20 A Iph> Pickup (minimum current)
5A 0.50 .. 20.00 A 1.00 A
1912 Uph-e (I>>)   20 .. 70 V 48 V Undervoltage (ph-e) at Iph>>
1913 Uph-e (I>)   20 .. 70 V 48 V Undervoltage (ph-e) at Iph>
1914 Uph-ph (I>>)   40 .. 130 V 80 V Undervoltage (ph-ph) at Iph>>
1915 Uph-ph (I>)   40 .. 130 V 80 V Undervoltage (ph-ph) at Iph>
1916 Iphi> 1A 0.10 .. 8.00 A 0.50 A Iphi> Pickup (minimum current at phi>)
5A 0.50 .. 40.00 A 2.50 A
1917 Uph-e (Iphi>)   20 .. 70 V 48 V Undervoltage (ph-e) at Iphi>
1918 Uph-ph (Iphi>)   40 .. 130 V 80 V Undervoltage (ph-ph) at Iphi>
1919A EFFECT φ   forward&reverse
Forward
forward&reverse Effective direction of phi- pickup
1920 φ>   30 .. 60 ° 50 ° PHI> pickup (lower setpoint)
1921 φ<   90 .. 120 ° 110 ° PHI< pickup (upper setpoint)
1930A 1ph FAULTS   PHASE-EARTH
PHASE-PHASEONLY
PHASE-EARTH 1ph-pickup loop selection (PU w/o earth)

Distance Protection with Quadrilateral Characteristic (optional)

Addr. Parameter C Setting Options Default Setting Comments
1601 Op. mode Z1   Forward
Reverse
Non-Directional
Inactive
Forward Operating mode Z1
1602 R(Z1) Ø-Ø 1A 0.050 .. 600.000 Ω 1.250 Ω R(Z1), Resistance for ph- ph-faults
5A 0.010 .. 120.000 Ω 0.250 Ω
1603 X(Z1) 1A 0.050 .. 600.000 Ω 2.500 Ω X(Z1), Reactance
5A 0.010 .. 120.000 Ω 0.500 Ω
1604 RE(Z1) Ø-E 1A 0.050 .. 600.000 Ω 2.500 Ω RE(Z1), Resistance for ph-e faults
5A 0.010 .. 120.000 Ω 0.500 Ω
1605 T1-1phase   0.00 .. 30.00 sec; ∞ 0.00 sec T1-1phase, delay for single phase faults
1606 T1-multi-phase   0.00 .. 30.00 sec; ∞ 0.00 sec T1multi-ph, delay for multi phase faults
1607 Zone Reduction   0 .. 45 ° 0 ° Zone Reduction Angle (load compensation)
1608 Iph>(Z1) 1A 0.05 .. 20.00 A 0.20 A Minimum current for Z1 only Iph>(Z1)
5A 0.25 .. 100.00 A 1.00 A
1611 Op. mode Z2   Forward
Reverse
Non-Directional
Inactive
Forward Operating mode Z2
1612 R(Z2) Ø-Ø 1A 0.050 .. 600.000 Ω 2.500 Ω R(Z2), Resistance for ph- ph-faults
5A 0.010 .. 120.000 Ω 0.500 Ω
1613 X(Z2) 1A 0.050 .. 600.000 Ω 5.000 Ω X(Z2), Reactance
5A 0.010 .. 120.000 Ω 1.000 Ω
1614 RE(Z2) Ø-E 1A 0.050 .. 600.000 Ω 5.000 Ω RE(Z2), Resistance for ph-e faults
5A 0.010 .. 120.000 Ω 1.000 Ω
1615 T2-1phase   0.00 .. 30.00 sec; ∞ 0.30 sec T2-1phase, delay for single phase faults
1616 T2-multi-phase   0.00 .. 30.00 sec; ∞ 0.30 sec T2multi-ph, delay for multi phase faults
1617A Trip 1pole Z2   NO
YES
NO Single pole trip for faults in Z2
1621 Op. mode Z3   Forward
Reverse
Non-Directional
Inactive
Reverse Operating mode Z3
1622 R(Z3) Ø-Ø 1A 0.050 .. 600.000 Ω 5.000 Ω R(Z3), Resistance for ph- ph-faults
5A 0.010 .. 120.000 Ω 1.000 Ω
1623 X(Z3) 1A 0.050 .. 600.000 Ω 10.000 Ω X(Z3), Reactance
5A 0.010 .. 120.000 Ω 2.000 Ω
1624 RE(Z3) Ø-E 1A 0.050 .. 600.000 Ω 10.000 Ω RE(Z3), Resistance for ph-e faults
5A 0.010 .. 120.000 Ω 2.000 Ω
1625 T3 DELAY   0.00 .. 30.00 sec; ∞ 0.60 sec T3 delay
1631 Op. mode Z4   Forward
Reverse
Non-Directional
Inactive
Non-Directional Operating mode Z4
1632 R(Z4) Ø-Ø 1A 0.050 .. 600.000 Ω 12.000 Ω R(Z4), Resistance for ph- ph-faults
5A 0.010 .. 120.000 Ω 2.400 Ω
1633 X(Z4) 1A 0.050 .. 600.000 Ω 12.000 Ω X(Z4), Reactance
5A 0.010 .. 120.000 Ω 2.400 Ω
1634 RE(Z4) Ø-E 1A 0.050 .. 250.000 Ω 12.000 Ω RE(Z4), Resistance for ph-e faults
5A 0.010 .. 50.000 Ω 2.400 Ω
1635 T4 DELAY   0.00 .. 30.00 sec; ∞ 0.90 sec T4 delay
1641 Op. mode Z5   Forward
Reverse
Non-Directional
Inactive
Inactive Operating mode Z5
1642 R(Z5) Ø-Ø 1A 0.050 .. 600.000 Ω 12.000 Ω R(Z5), Resistance for ph- ph-faults
5A 0.010 .. 120.000 Ω 2.400 Ω
1643 X(Z5)+ 1A 0.050 .. 600.000 Ω 12.000 Ω X(Z5)+, Reactance for Forward direction
5A 0.010 .. 120.000 Ω 2.400 Ω
1644 RE(Z5) Ø-E 1A 0.050 .. 600.000 Ω 12.000 Ω RE(Z5), Resistance for ph-e faults
5A 0.010 .. 120.000 Ω 2.400 Ω
1645 T5 DELAY   0.00 .. 30.00 sec; ∞ 0.90 sec T5 delay
1646 X(Z5)- 1A 0.050 .. 600.000 Ω 4.000 Ω X(Z5)-, Reactance for Reverse direction
5A 0.010 .. 120.000 Ω 0.800 Ω
1651 Op. mode Z1B   Forward
Reverse
Non-Directional
Inactive
Forward Operating mode Z1B (over- rreach zone)
1652 R(Z1B) Ø-Ø 1A 0.050 .. 600.000 Ω 1.500 Ω R(Z1B), Resistance for ph- ph-faults
5A 0.010 .. 120.000 Ω 0.300 Ω
1653 X(Z1B) 1A 0.050 .. 600.000 Ω 3.000 Ω X(Z1B), Reactance
5A 0.010 .. 120.000 Ω 0.600 Ω
1654 RE(Z1B) Ø-E 1A 0.050 .. 600.000 Ω 3.000 Ω RE(Z1B), Resistance for ph- e faults
5A 0.010 .. 120.000 Ω 0.600 Ω
1655 T1B-1phase   0.00 .. 30.00 sec; ∞ 0.00 sec T1B-1phase, delay for single ph. faults
1656 T1B-multi-phase   0.00 .. 30.00 sec; ∞ 0.00 sec T1B-multi-ph, delay for multi ph. faults
1657 1st AR -> Z1B   NO
YES
NO Z1B enabled before 1st AR (int. or ext.)
1661 Op. mode Z6   Forward
Reverse
Non-Directional
Inactive
Inactive Operating mode Z6
1662 R(Z6) Ø-Ø 1A 0.050 .. 600.000 Ω 15.000 Ω R(Z6), Resistance for ph- ph-faults
5A 0.010 .. 120.000 Ω 3.000 Ω
1663 X(Z6)+ 1A 0.050 .. 600.000 Ω 15.000 Ω X(Z6)+, Reactance for Forward direction
5A 0.010 .. 120.000 Ω 3.000 Ω
1664 RE(Z6) Ø-E 1A 0.050 .. 600.000 Ω 15.000 Ω RE(Z6), Resistance for ph-e faults
5A 0.010 .. 120.000 Ω 3.000 Ω
1665 T6 DELAY   0.00 .. 30.00 sec; ∞ 1.50 sec T6 delay
1666 X(Z6)- 1A 0.050 .. 600.000 Ω 4.000 Ω X(Z6)-, Reactance for Reverse direction
5A 0.010 .. 120.000 Ω 0.800 Ω

Distance Protection with MHO Characteristic (optional)

Addr. Parameter C Setting Options Default Setting Comments
1605 T1-1phase   0.00 .. 30.00 sec; ∞ 0.00 sec T1-1phase, delay for single phase faults
1606 T1-multi-phase   0.00 .. 30.00 sec; ∞ 0.00 sec T1multi-ph, delay for multi phase faults
1608 Iph>(Z1) 1A 0.05 .. 20.00 A 0.20 A Minimum current for Z1 only Iph>(Z1)
5A 0.25 .. 100.00 A 1.00 A
1615 T2-1phase   0.00 .. 30.00 sec; ∞ 0.30 sec T2-1phase, delay for single phase faults
1616 T2-multi-phase   0.00 .. 30.00 sec; ∞ 0.30 sec T2multi-ph, delay for multi phase faults
1617A Trip 1pole Z2   NO
YES
NO Single pole trip for faults in Z2
1625 T3 DELAY   0.00 .. 30.00 sec; ∞ 0.60 sec T3 delay
1635 T4 DELAY   0.00 .. 30.00 sec; ∞ 0.90 sec T4 delay
1645 T5 DELAY   0.00 .. 30.00 sec; ∞ 0.90 sec T5 delay
1655 T1B-1phase   0.00 .. 30.00 sec; ∞ 0.00 sec T1B-1phase, delay for single ph. faults
1656 T1B-multi-phase   0.00 .. 30.00 sec; ∞ 0.00 sec T1B-multi-ph, delay for multi ph. faults
1657 1st AR -> Z1B   NO
YES
NO Z1B enabled before 1st AR (int. or ext.)
1665 T6 DELAY   0.00 .. 30.00 sec; ∞ 1.50 sec T6 delay
1701 Op. mode Z1   Forward
Reverse
Inactive
Forward Operating mode Z1
1702 ZR(Z1) 1A 0.050 .. 200.000 Ω 2.500 Ω ZR(Z1), Impedance Reach
5A 0.010 .. 40.000 Ω 0.500 Ω
1711 Op. mode Z2   Forward
Reverse
Inactive
Forward Operating mode Z2
1712 ZR(Z2) 1A 0.050 .. 200.000 Ω 5.000 Ω ZR(Z2), Impedance Reach
5A 0.010 .. 40.000 Ω 1.000 Ω
1721 Op. mode Z3   Forward
Reverse
Inactive
Reverse Operating mode Z3
1722 ZR(Z3) 1A 0.050 .. 200.000 Ω 5.000 Ω ZR(Z3), Impedance Reach
5A 0.010 .. 40.000 Ω 1.000 Ω
1731 Op. mode Z4   Forward
Reverse
Inactive
Forward Operating mode Z4
1732 ZR(Z4) 1A 0.050 .. 200.000 Ω 10.000 Ω ZR(Z4), Impedance Reach
5A 0.010 .. 40.000 Ω 2.000 Ω
1741 Op. mode Z5   Forward
Reverse
Inactive
Inactive Operating mode Z5
1742 ZR(Z5) 1A 0.050 .. 200.000 Ω 10.000 Ω ZR(Z5), Impedance Reach
5A 0.010 .. 40.000 Ω 2.000 Ω
1751 Op. mode Z1B   Forward
Reverse
Inactive
Forward Operating mode Z1B (extended zone)
1752 ZR(Z1B) 1A 0.050 .. 200.000 Ω 3.000 Ω ZR(Z1B), Impedance Reach
5A 0.010 .. 40.000 Ω 0.600 Ω
1761 Op. mode Z6   Forward
Reverse
Inactive
Inactive Operating mode Z6
1762 ZR(Z6) 1A 0.050 .. 200.000 Ω 15.000 Ω ZR(Z6), Impedance Reach
5A 0.010 .. 40.000 Ω 3.000 Ω
1771A Mem.Polariz.PhE   0.0 .. 100.0 % 15.0 % Voltage Memory polariza- tion (phase-e)
1772A CrossPolarizPhE   0.0 .. 100.0 % 15.0 % Cross polarization (phase- e)
1773A Mem.Polariz.P-P   0.0 .. 100.0 % 15.0 % Voltage Memory polariza- tion (ph-ph)
1774A CrossPolarizP-P   0.0 .. 100.0 % 15.0 % Cross polarization (phase- phase)

Power Swing Detection (optional)

Addr. Parameter C Setting Options Default Setting Comments
2002 P/S Op. mode   All zones block
Z1/Z1B block
>= Z2 block Z1,Z1B,Z2 block
All zones block Power Swing Operating mode
2006 PowerSwing trip   NO
YES
NO Power swing trip

Teleprotection for Distance Protection (optional)

Addr. Parameter C Setting Options Default Setting Comments
2101 FCT Telep. Dis.   ON
OFF
ON Teleprotection for Distance protec- tion
2102 Type of Line   Two Terminals
Three terminals
Two Terminals Type of Line
2103A Send Prolong.   0.00 .. 30.00 sec 0.05 sec Time for send signal prolongation
2107A Delay for alarm   0.00 .. 30.00 sec 10.00 sec Time Delay for Alarm
2108 Release Delay   0.000 .. 30.000 sec 0.000 sec Time Delay for release after pickup
2109A TrBlk Wait Time   0.00 .. 30.00 sec; ∞ 0.04 sec Transient Block.: Duration external flt.
2110A TrBlk BlockTime   0.00 .. 30.00 sec 0.05 sec Transient Block.: Blk.T. after ext. flt.
2112A DIS TRANSBLK EF   YES
NO
YES DIS transient block by EF
2113 Mem.rec.sig.   YES
NO
NO Memorize receive signal

Earth Fault Protection in Earthed Systems (optional)

Addr. Parameter C Setting Options Default Setting Comments
3101 FCT EarthFltO/C   ON
OFF
ON Earth Fault overcurrent function
3102 BLOCK for Dist.   every PICKUP
1phase PICKUP
multiph. PICKUP
NO
every PICKUP Block E/F for Distance protection
3103 BLOCK 1pDeadTim   YES
NO
YES Block E/F for 1pole Dead time
3104A Iph-STAB. Slope   0 .. 30 % 10 % Stabilisation Slope with Iphase
3105 3IoMin Teleprot 1A 0.01 .. 1.00 A 0.50 A 3Io-Min threshold for Tele- prot. schemes
5A 0.05 .. 5.00 A 2.50 A
3105 3IoMin Teleprot 1A 0.003 .. 1.000 A 0.500 A 3Io-Min threshold for Tele- prot. schemes
5A 0.015 .. 5.000 A 2.500 A
3109 Trip 1pole E/F   YES
NO
YES Single pole trip with earth flt.prot.
3110 Op. mode 3I0>>>   Forward
Reverse
Non-Directional
Inactive
Inactive Operating mode
3111 3I0>>> 1A 0.05 .. 25.00 A 4.00 A 3I0>>> Pickup
5A 0.25 .. 125.00 A 20.00 A
3112 T 3I0>>>   0.00 .. 30.00 sec; ∞ 0.30 sec T 3I0>>> Time delay
3113 3I0>>> Telep/BI   YES
NO
NO Instantaneous trip via Tele- prot./BI
3114 3I0>>>SOTF-Trip   YES
NO
NO Instantaneous trip after SwitchOnToFault
3115 3I0>>>InrushBlk   YES
NO
NO Inrush Blocking
3116 BLK /1p 3I0>>>   YES
No (non-dir.)
YES Block 3I0>>> during 1pole dead time
3117 Trip 1p 3I0>>>   YES
NO
YES Single pole trip with 3I0>>>
3120 Op. mode 3I0>>   Forward
Reverse
Non-Directional
Inactive
Inactive Operating mode
3121 3I0>> 1A 0.05 .. 25.00 A 2.00 A 3I0>> Pickup
5A 0.25 .. 125.00 A 10.00 A
3122 T 3I0>>   0.00 .. 30.00 sec; ∞ 0.60 sec T 3I0>> Time Delay
3123 3I0>> Telep/BI   YES
NO
NO Instantaneous trip via Tele- prot./BI
3124 3I0>> SOTF-Trip   YES
NO
NO Instantaneous trip after SwitchOnToFault
3125 3I0>> InrushBlk   YES
NO
NO Inrush Blocking
3126 BLK /1p 3I0>>   YES
No (non-dir.)
YES Block 3I0>> during 1pole dead time
3127 Trip 1p 3I0>>   YES
NO
YES Single pole trip with 3I0>>
3130 Op. mode 3I0>   Forward
Reverse
Non-Directional
Inactive
Inactive Operating mode
3131 3I0> 1A 0.05 .. 25.00 A 1.00 A 3I0> Pickup
5A 0.25 .. 125.00 A 5.00 A
3132 T 3I0>   0.00 .. 30.00 sec; ∞ 0.90 sec T 3I0> Time Delay
3133 3I0> Telep/BI   YES
NO
NO Instantaneous trip via Tele- prot./BI
3134 3I0> SOTF-Trip   YES
NO
NO Instantaneous trip after SwitchOnToFault
3135 3I0> InrushBlk   YES
NO
NO Inrush Blocking
3136 BLK /1p 3I0>   YES
No (non-dir.)
YES Block 3I0> during 1pole dead time
3137 Trip 1p 3I0>   YES
NO
YES Single pole trip with 3I0>
3140 Op. mode 3I0p   Forward
Reverse
Non-Directional
Inactive
Inactive Operating mode
3141 3I0p PICKUP 1A 0.05 .. 25.00 A 1.00 A 3I0p Pickup
5A 0.25 .. 125.00 A 5.00 A
3142 3I0p MinT-DELAY   0.00 .. 30.00 sec 1.20 sec 3I0p Minimum Time Delay
3143 3I0p Time Dial   0.05 .. 3.00 sec; ∞ 0.50 sec 3I0p Time Dial
3144 3I0p Time Dial   0.50 .. 15.00 ; ∞ 5.00 3I0p Time Dial
3145 3I0p Time Dial   0.05 .. 15.00 sec; ∞ 1.35 sec 3I0p Time Dial
3146 3I0p MaxT-DELAY   0.00 .. 30.00 sec 5.80 sec 3I0p Maximum Time Delay
3147 Add.T-DELAY   0.00 .. 30.00 sec; ∞ 1.20 sec Additional Time Delay
3148 3I0p Telep/BI   YES
NO
NO Instantaneous trip via Tele- prot./BI
3149 3I0p SOTF-Trip   YES
NO
NO Instantaneous trip after SwitchOnToFault
3150 3I0p InrushBlk   YES
NO
NO Inrush Blocking
3151 IEC Curve   Normal Inverse
Very Inverse
Extremely Inv.
LongTimeInverse
Normal Inverse IEC Curve
3152 ANSI Curve   Inverse
Short Inverse
Long Inverse
Moderately Inv.
Very Inverse
Extremely Inv.
Definite Inv.
Inverse ANSI Curve
3153 LOG Curve   Log. inverse Log. inverse LOGARITHMIC Curve
3154 3I0p Startpoint   1.0 .. 4.0 1.1 Start point of inverse char- acteristic
3155 k   0.00 .. 3.00 sec 0.50 sec k-factor for Sr-character- istic
3156 S ref 1A 1 .. 100 VA 10 VA S ref for Sr-characteristic
5A 5 .. 500 VA 50 VA
3157 BLK /1p 3I0p   YES
No (non-dir.)
YES Block 3I0p during 1pole dead time
3158 Trip 1p 3I0p   YES
NO
YES Single pole trip with 3I0p
3160 POLARIZATION   U0 + IY or U2
U0 + IY
with IY only
with U2 and I2
zero seq. power
U0 + IY or U2 Polarization
3162A Dir. ALPHA   0 .. 360 ° 338 ° ALPHA, lower angle for forward direction
3163A Dir. BETA   0 .. 360 ° 122 ° BETA, upper angle for forward direction
3164 3U0>   0.5 .. 10.0 V 0.5 V Min. zero seq.voltage 3U0 for polarizing
3165 IY> 1A 0.05 .. 1.00 A 0.05 A Min. earth current IY for polarizing
5A 0.25 .. 5.00 A 0.25 A
3166 3U2>   0.5 .. 10.0 V 0.5 V Min. neg. seq. polarizing voltage 3U2
3167 3I2> 1A 0.05 .. 1.00 A 0.05 A Min. neg. seq. polarizing current 3I2
5A 0.25 .. 5.00 A 0.25 A
3168 PHI comp   0 .. 360 ° 255 ° Compensation angle PHI comp. for Sr
3169 S forward 1A 0.1 .. 10.0 VA 0.3 VA Forward direction power threshold
5A 0.5 .. 50.0 VA 1.5 VA
3170 2nd InrushRest   10 .. 45 % 15 % 2nd harmonic ratio for inrush restraint
3171 Imax InrushRest 1A 0.50 .. 25.00 A 7.50 A Max.Current, overriding inrush restraint
5A 2.50 .. 125.00 A 37.50 A
3172 SOTF Op. Mode   PICKUP
PICKUP+DIRECT.
PICKUP+DIRECT. Instantaneous mode after SwitchOnToFault
3173 SOTF Time DELAY   0.00 .. 30.00 sec 0.00 sec Trip time delay after SOTF
3174 BLK for DisZone   in zone Z1
in zone Z1/Z1B
in each zone
in each zone Block E/F for Distance Protection Pickup
3175 EF BLK Dif.PU   YES
NO
YES Block E/F for Differential Prot. Pickup
3182 3U0>(U0 inv)   1.0 .. 10.0 V 5.0 V 3U0> setpoint
3183 U0inv. minimum   0.1 .. 5.0 V 0.2 V Minimum voltage U0min for T->oo
3184 T forw. (U0inv)   0.00 .. 32.00 sec 0.90 sec T-forward Time delay (U0inv)
3185 T rev. (U0inv)   0.00 .. 32.00 sec 1.20 sec T-reverse Time delay (U0inv)
3186A 3U0< forward   0.1 .. 10.0 V; 0 0.0 V 3U0 min for forward direc- tion
3187A XserCap 1A 0.000 .. 600.000 Ω 0.000 Ω Reactance X of series capacitor
5A 0.000 .. 120.000 Ω 0.000 Ω

Teleprotection for Earth Fault Protection (optional)

Addr. Parameter C Setting Options Default Setting Comments
3201 FCT Telep. E/F   ON
OFF
ON Teleprotection for Earth Fault O/C
3202 Line Config.   Two Terminals
Three terminals
Two Terminals Line Configuration
3203A Send Prolong.   0.00 .. 30.00 sec 0.05 sec Time for send signal prolongation
3207A Delay for alarm   0.00 .. 30.00 sec 10.00 sec Unblocking: Time Delay for Alarm
3208 Release Delay   0.000 .. 30.000 sec 0.000 sec Time Delay for release after pickup
3209A TrBlk Wait Time   0.00 .. 30.00 sec; ∞ 0.04 sec Transient Block.: Duration external flt.
3210A TrBlk BlockTime   0.00 .. 30.00 sec 0.05 sec Transient Block.: Blk.T. after ext. flt.
3212A EF TRANSBLK DIS   YES
NO
YES EF transient block by DIS

Restricted Earth Fault Protection (optional)

Addr. Parameter C Setting Options Default Setting Comments
4101 REF PROT.   OFF
ON
OFF Restricted Earth Fault Protection
4111 I-REF> 1A 0.05 .. 2.00 A 0.15 A Pick up value I REF>
5A 0.25 .. 10.00 A 0.75 A
4112A T I-REF>   0.00 .. 60.00 sec; ∞ 0.00 sec T I-REF> Time Delay
4113A SLOPE   0.00 .. 0.95 0.00 Slope of Charac. I-REF> = f(I-SUM)

Measures for Weak and Zero Infeed

Addr. Parameter C Setting Options Default Setting Comments
2501 FCT Weak Infeed   OFF
ECHO only
ECHO and TRIP
Echo &Trip(I=0)
ECHO only Weak Infeed function
2502A Trip/Echo DELAY   0.00 .. 30.00 sec 0.04 sec Trip / Echo Delay after carrier receipt
2503A Trip EXTENSION   0.00 .. 30.00 sec 0.05 sec Trip Extension / Echo Impulse time
2504A Echo BLOCK Time   0.00 .. 30.00 sec 0.05 sec Echo Block Time
2505 UNDERVOLTAGE   2 .. 70 V 25 V Undervoltage (ph-e)
2509 Echo:1channel   NO
YES
NO Echo logic: Dis and EF on common channel
2510 Uphe< Factor   0.10 .. 1.00 0.70 Factor for undervoltage Uphe<
2511 Time const. τ   1 .. 60 sec 5 sec Time constant Tau
2512A Rec. Ext.   0.00 .. 30.00 sec 0.65 sec Reception extension
2513A T 3I0> Ext.   0.00 .. 30.00 sec 0.60 sec 3I0> exceeded extension
2514 3I0> Threshold 1A 0.05 .. 1.00 A 0.50 A 3I0 threshold for neutral current pickup
5A 0.25 .. 5.00 A 2.50 A
2515 TM   0.00 .. 30.00 sec 0.40 sec WI delay single pole
2516 TT   0.00 .. 30.00 sec 1.00 sec WI delay multi pole
2517 1pol. Trip   ON
OFF
ON Single pole WI trip allowed
2518 1pol. with 3I0   ON
OFF
ON Single pole WI trip with 3I0
2519 3pol. Trip   ON
OFF
ON Three pole WI trip allowed
2520 T 3I0> alarm   0.00 .. 30.00 sec 10.00 sec 3I0> exceeded delay for alarm
2530 WI non delayed   ON
OFF
ON WI non delayed
2531 WI delayed   ON
by receive fail
OFF
by receive fail WI delayed

Direct Local Trip

Addr. Parameter C Setting Options Default Setting Comments
2201 FCT Direct Trip   ON
OFF
OFF Direct Transfer Trip (DTT)
2202 Trip Time DELAY   0.00 .. 30.00 sec; ∞ 0.01 sec Trip Time Delay

Instantaneous High-Current Switch-onto-Fault Protection (SOTF)

Addr. Parameter C Setting Options Default Setting Comments
2401 FCT HS/SOTF-O/C   ON
OFF
ON Inst. High Speed/SOTF-O/C is
2404 I>>> 1A 0.10 .. 15.00 A; ∞ 1.50 A I>>> Pickup
5A 0.50 .. 75.00 A; ∞ 7.50 A
2405A I>>>> 1A 1.00 .. 25.00 A; ∞ ∞ A I>>>> Pickup
5A 5.00 .. 125.00 A; ∞ ∞ A
2406 CBaux for I>>>   local only
local and rem.
local and rem. CB-aux check for activation of I>>>

Sensitive Earth Flt.(comp/isol. starp.)

Addr. Parameter C Setting Options Default Setting Comments
3001 Sens. Earth Flt   Alarm Only
ON: with Trip
OFF
Alarm Only Sensitive Earth Flt.(comp/ isol. starp.)
3002 3U0>   1 .. 150 V 50 V 3U0> pickup
3003 Uph-e min   10 .. 100 V 40 V Uph-e min of faulted phase
3004 Uph-e max   10 .. 100 V 75 V Uph-e max of healthy phases
3005 3I0>   0.003 .. 1.000 A 0.050 A 3I0> Release directional element
3006 T Sens.E/F   0.00 .. 320.00 sec 1.00 sec Time delay for sens. E/F detection
3007 T 3U0>   0.00 .. 320.00 sec 0.00 sec Time delay for sens. E/F trip
3008A TRIP Direction   Forward
Reverse
Non-Directional
Forward Direction for sens. E/F trip
3010 CT Err. I1   0.003 .. 1.600 A 0.050 A Current I1 for CT Angle Error
3011 CT Err. F1   0.0 .. 5.0 ° 0.0 ° CT Angle Error at I1
3012 CT Err. I2   0.003 .. 1.600 A 1.000 A Current I2 for CT Angle Error
3013 CT Err. F2   0.0 .. 5.0 ° 0.0 ° CT Angle Error at I2

Backup Time Overcurrent Protection

Addr. Parameter C Setting Options Default Setting Comments
2601 Operating Mode   ON
Only Emer. prot
OFF
ON Operating mode
2602 SOTF Time DELAY   0.00 .. 30.00 sec 0.00 sec Trip time delay after SOTF
2610 Iph>> 1A 0.05 .. 50.00 A; ∞ 2.00 A Iph>> Pickup
5A 0.25 .. 250.00 A; ∞ 10.00 A
2611 T Iph>>   0.00 .. 30.00 sec; ∞ 0.30 sec T Iph>> Time delay
2612 3I0>> PICKUP 1A 0.05 .. 25.00 A; ∞ 0.50 A 3I0>> Pickup
5A 0.25 .. 125.00 A; ∞ 2.50 A
2613 T 3I0>>   0.00 .. 30.00 sec; ∞ 2.00 sec T 3I0>> Time delay
2614 I>> InstTrip BI   NO
YES
YES Instantaneous trip via BI
2615 I>> SOTF   NO
YES
NO Instantaneous trip after SwitchOnToFault
2620 Iph> 1A 0.05 .. 50.00 A; ∞ 1.50 A Iph> Pickup
5A 0.25 .. 250.00 A; ∞ 7.50 A
2621 T Iph>   0.00 .. 30.00 sec; ∞ 0.50 sec T Iph> Time delay
2622 3I0> 1A 0.05 .. 25.00 A; ∞ 0.20 A 3I0> Pickup
5A 0.25 .. 125.00 A; ∞ 1.00 A
2623 T 3I0>   0.00 .. 30.00 sec; ∞ 2.00 sec T 3I0> Time delay
2624 I> Telep/BI   NO
YES
NO Instantaneous trip via Tele- prot./BI
2625 I> SOTF   NO
YES
NO Instantaneous trip after SwitchOnToFault
2630 Iph> STUB 1A 0.05 .. 50.00 A; ∞ 1.50 A Iph> STUB Pickup
5A 0.25 .. 250.00 A; ∞ 7.50 A
2631 T Iph STUB   0.00 .. 30.00 sec; ∞ 0.30 sec T Iph STUB Time delay
2632 3I0> STUB 1A 0.05 .. 25.00 A; ∞ 0.20 A 3I0> STUB Pickup
5A 0.25 .. 125.00 A; ∞ 1.00 A
2633 T 3I0 STUB   0.00 .. 30.00 sec; ∞ 2.00 sec T 3I0 STUB Time delay
2634 I-STUB Telep/BI   NO
YES
NO Instantaneous trip via Tele- prot./BI
2635 I-STUB SOTF   NO
YES
NO Instantaneous trip after SwitchOnToFault
2640 Ip> 1A 0.10 .. 4.00 A; ∞ ∞ A Ip> Pickup
5A 0.50 .. 20.00 A; ∞ ∞ A
2642 T Ip Time Dial   0.05 .. 3.00 sec; ∞ 0.50 sec T Ip Time Dial
2643 Time Dial TD Ip   0.50 .. 15.00 ; ∞ 5.00 Time Dial TD Ip
2646 T Ip Add   0.00 .. 30.00 sec 0.00 sec T Ip Additional Time Delay
2650 3I0p PICKUP 1A 0.05 .. 4.00 A; ∞ ∞ A 3I0p Pickup
5A 0.25 .. 20.00 A; ∞ ∞ A
2652 T 3I0p TimeDial   0.05 .. 3.00 sec; ∞ 0.50 sec T 3I0p Time Dial
2653 TimeDial TD3I0p   0.50 .. 15.00 ; ∞ 5.00 Time Dial TD 3I0p
2656 T 3I0p Add   0.00 .. 30.00 sec 0.00 sec T 3I0p Additional Time Delay
2660 IEC Curve   Normal Inverse
Very Inverse
Extremely Inv.
LongTimeInverse
Normal Inverse IEC Curve
2661 ANSI Curve   Inverse
Short Inverse
Long Inverse
Moderately Inv.
Very Inverse
Extremely Inv.
Definite Inv.
Inverse ANSI Curve
2670 I(3I0)p Tele/BI   NO
YES
NO Instantaneous trip via Tele- prot./BI
2671 I(3I0)p SOTF   NO
YES
NO Instantaneous trip after SwitchOnToFault

Automatic Reclosure Function (optional)

Addr. Parameter C Setting Options Default Setting Comments
3401 AUTO RECLOSE   OFF
ON
ON Auto-Reclose Function
3402 CB? 1.TRIP   YES
NO
NO CB ready interrogation at 1st trip
3403 T-RECLAIM   0.50 .. 300.00 sec 3.00 sec Reclaim time after successful AR cycle
3403 T-RECLAIM   0.50 .. 300.00 sec; 0 3.00 sec Reclaim time after successful AR cycle
3404 T-BLOCK MC   0.50 .. 300.00 sec; 0 1.00 sec AR blocking duration after manual close
3406 EV. FLT. RECOG.   with PICKUP
with TRIP
with TRIP Evolving fault recognition
3407 EV. FLT. MODE   Stops AutoRecl
starts 3p AR
starts 3p AR Evolving fault (during the dead time)
3408 T-Start MONITOR   0.01 .. 300.00 sec 0.50 sec AR start-signal monitoring time
3409 CB TIME OUT   0.01 .. 300.00 sec 3.00 sec Circuit Breaker (CB) Supervision Time
3410 T RemoteClose   0.00 .. 300.00 sec; ∞ 0.20 sec Send delay for remote close command
3411A T-DEAD EXT.   0.50 .. 300.00 sec; ∞ ∞ sec Maximum dead time extension
3420 AR WITH DIFF   YES
NO
YES AR with differential protection ?
3421 AR w/ SOTF-O/C   YES
NO
YES AR with switch-onto-fault overcur- rent ?
3422 AR w/ DIST.   YES
NO
YES AR with distance protection ?
3423 AR WITH I.TRIP   YES
NO
YES AR with intertrip ?
3424 AR w/ DTT   YES
NO
YES AR with direct transfer trip ?
3425 AR w/ BackUpO/C   YES
NO
YES AR with back-up overcurrent ?
3426 AR w/ W/I   YES
NO
YES AR with weak infeed tripping ?
3427 AR w/ EF-O/C   YES
NO
YES AR with earth fault overcurrent prot. ?
3430 AR TRIP 3pole   YES
NO
YES 3pole TRIP by AR
3431 DLC / RDT   WITHOUT
DLC
WITHOUT Dead Line Check / Reduced Dead Time
3433 T-ACTION ADT   0.01 .. 300.00 sec; ∞ 0.20 sec Action time
3434 T-MAX ADT   0.50 .. 3000.00 sec 5.00 sec Maximum dead time
3435 ADT 1p allowed   YES NO NO 1pole TRIP allowed
3436 ADT CB? CLOSE   YES NO NO CB ready interrogation before reclosing
3437 ADT SynRequest   YES NO NO Request for synchro-check after 3pole AR
3438 T U-stable   0.10 .. 30.00 sec 0.10 sec Supervision time for dead/live voltage
3440 U-live>   30 .. 90 V 48 V Voltage threshold for live line or bus
3441 U-dead<   2 .. 70 V 30 V Voltage threshold for dead line or bus
3450 1.AR: START   YES
NO
YES Start of AR allowed in this cycle
3451 1.AR: T-ACTION   0.01 .. 300.00 sec; ∞ 0.20 sec Action time
3453 1.AR Tdead 1Flt   0.01 .. 1800.00 sec; ∞ 1.20 sec Dead time after 1phase faults
3454 1.AR Tdead 2Flt   0.01 .. 1800.00 sec; ∞ 1.20 sec Dead time after 2phase faults
3455 1.AR Tdead 3Flt   0.01 .. 1800.00 sec; ∞ 0.50 sec Dead time after 3phase faults
3456 1.AR Tdead1Trip   0.01 .. 1800.00 sec; ∞ 1.20 sec Dead time after 1pole trip
3457 1.AR Tdead3Trip   0.01 .. 1800.00 sec; ∞ 0.50 sec Dead time after 3pole trip
3458 1.AR: Tdead EV.   0.01 .. 1800.00 sec 1.20 sec Dead time after evolving fault
3459 1.AR: CB? CLOSE   YES
NO
NO CB ready interrogation before reclosing
3460 1.AR SynRequest   YES
NO
NO Request for synchro-check after 3pole AR
3461 2.AR: START   YES
NO
NO AR start allowed in this cycle
3462 2.AR: T-ACTION   0.01 .. 300.00 sec; ∞ 0.20 sec Action time
3464 2.AR Tdead 1Flt   0.01 .. 1800.00 sec; ∞ 1.20 sec Dead time after 1phase faults
3465 2.AR Tdead 2Flt   0.01 .. 1800.00 sec; ∞ 1.20 sec Dead time after 2phase faults
3466 2.AR Tdead 3Flt   0.01 .. 1800.00 sec; ∞ 0.50 sec Dead time after 3phase faults
3467 2.AR Tdead1Trip   0.01 .. 1800.00 sec; ∞ ∞ sec Dead time after 1pole trip
3468 2.AR Tdead3Trip   0.01 .. 1800.00 sec; ∞ 0.50 sec Dead time after 3pole trip
3469 2.AR: Tdead EV.   0.01 .. 1800.00 sec 1.20 sec Dead time after evolving fault
3470 2.AR: CB? CLOSE   YES
NO
NO CB ready interrogation before reclosing
3471 2.AR SynRequest   YES
NO
NO Request for synchro-check after 3pole AR
3472 3.AR: START   YES
NO
NO AR start allowed in this cycle
3473 3.AR: T-ACTION   0.01 .. 300.00 sec; ∞ 0.20 sec Action time
3475 3.AR Tdead 1Flt   0.01 .. 1800.00 sec; ∞ 1.20 sec Dead time after 1phase faults
3476 3.AR Tdead 2Flt   0.01 .. 1800.00 sec; ∞ 1.20 sec Dead time after 2phase faults
3477 3.AR Tdead 3Flt   0.01 .. 1800.00 sec; ∞ 0.50 sec Dead time after 3phase faults
3478 3.AR Tdead1Trip   0.01 .. 1800.00 sec; ∞ ∞ sec Dead time after 1pole trip
3479 3.AR Tdead3Trip   0.01 .. 1800.00 sec; ∞ 0.50 sec Dead time after 3pole trip
3480 3.AR: Tdead EV.   0.01 .. 1800.00 sec 1.20 sec Dead time after evolving fault
3481 3.AR: CB? CLOSE   YES
NO
NO CB ready interrogation before reclosing
3482 3.AR SynRequest   YES
NO
NO Request for synchro-check after 3pole AR
3483 4.AR: START   YES
NO
NO AR start allowed in this cycle
3484 4.AR: T-ACTION   0.01 .. 300.00 sec; ∞ 0.20 sec Action time
3486 4.AR Tdead 1Flt   0.01 .. 1800.00 sec; ∞ 1.20 sec Dead time after 1phase faults
3487 4.AR Tdead 2Flt   0.01 .. 1800.00 sec; ∞ 1.20 sec Dead time after 2phase faults
3488 4.AR Tdead 3Flt   0.01 .. 1800.00 sec; ∞ 0.50 sec Dead time after 3phase faults
3489 4.AR Tdead1Trip   0.01 .. 1800.00 sec; ∞ ∞ sec Dead time after 1pole trip
3490 4.AR Tdead3Trip   0.01 .. 1800.00 sec; ∞ 0.50 sec Dead time after 3pole trip
3491 4.AR: Tdead EV.   0.01 .. 1800.00 sec 1.20 sec Dead time after evolving fault
3492 4.AR: CB? CLOSE   YES
NO
NO CB ready interrogation before reclosing
3493 4.AR SynRequest   YES
NO
NO Request for synchro-check after 3pole AR

Synchronism and Voltage Check (optional)

Addr. Parameter C Setting Options Default Setting Comments
3501 FCT Synchronism   ON
OFF
ON:w/o CloseCmd
ON Synchronism and Voltage Check function
3502 Dead Volt. Thr.   1 .. 100 V 5 V Voltage threshold dead line / bus
3503 Live Volt. Thr.   20 .. 125 V 90 V Voltage threshold live line / bus
3504 Umax   20 .. 140 V 110 V Maximum permissible voltage
3507 T-SYN. DURATION   0.01 .. 600.00 sec; ∞ 1.00 sec Maximum duration of synchronism-check
3508 T SYNC-STAB   0.00 .. 30.00 sec 0.00 sec Synchronous condition stability timer
3509 SyncCB   (Einstellmoglichkeiten anwendungsabhangig) none Synchronizable circuit breaker
3510 Op.mode with AR   with T-CB close
w/o T-CB close
w/o T-CB close Operating mode with AR
3511 AR maxVolt.Diff   1.0 .. 60.0 V 2.0 V Maximum voltage difference
3512 AR maxFreq.Diff   0.03 .. 2.00 Hz 0.10 Hz Maximum frequency difference
3513 AR maxAngleDiff   2 .. 80 ° 10 ° Maximum angle difference
3515A AR SYNC-CHECK   YES
NO
YES AR at Usy2>, Usy1>, and Synchr.
3516 AR Usy1<Usy2>   YES
NO
NO AR at Usy1< and Usy2>
3517 AR Usy1>Usy2<   YES
NO
NO AR at Usy1> and Usy2<
3518 AR Usy1<Usy2<   YES
NO
NO AR at Usy1< and Usy2<
3519 AR OVERRIDE   YES
NO
NO Override of any check before AR
3530 Op.mode with MC   with T-CB close
w/o T-CB close
w/o T-CB close Operating mode with Man.Cl
3531 MC maxVolt.Diff   1.0 .. 60.0 V 2.0 V Maximum voltage difference
3532 MC maxFreq.Diff   0.03 .. 2.00 Hz 0.10 Hz Maximum frequency difference
3533 MC maxAngleDiff   2 .. 80 ° 10 ° Maximum angle difference
3535A MC SYNCHR   YES
NO
YES Manual Close at Usy2>, Usy1>, and Synchr
3536 MC Usy1< Usy2>   YES
NO
NO Manual Close at Usy1< and Usy2>
3537 MC Usy1> Usy2<   YES
NO
NO Manual Close at Usy1> and Usy2<
3538 MC Usy1< Usy2<   YES
NO
NO Manual Close at Usy1< and Usy2<
3539 MC OVERRIDE   YES
NO
NO Override of any check before Man.Cl

Undervoltage and Overvoltage Protection (optional)

Addr. Parameter C Setting Options Default Setting Comments
3701 Uph-e>(>)   OFF
Alarm Only
ON
U>Alarm U>>Trip
OFF Operating mode Uph-e overvoltage prot.
3702 Uph-e>   1.0 .. 170.0 V; ∞ 85.0 V Uph-e> Pickup
3703 T Uph-e>   0.00 .. 100.00 sec; ∞ 2.00 sec T Uph-e> Time Delay
3704 Uph-e>>   1.0 .. 170.0 V; ∞ 100.0 V Uph-e>> Pickup
3705 T Uph-e>>   0.00 .. 100.00 sec; ∞ 1.00 sec T Uph-e>> Time Delay
3709A Uph-e>(>) RESET   0.30 .. 0.99 0.98 Uph-e>(>) Reset ratio
3711 Uph-ph>(>)   OFF
Alarm Only
ON
U>Alarm U>>Trip
OFF Operating mode Uph-ph overvoltage prot.
3712 Uph-ph>   2.0 .. 220.0 V; ∞ 150.0 V Uph-ph> Pickup
3713 T Uph-ph>   0.00 .. 100.00 sec; ∞ 2.00 sec T Uph-ph> Time Delay
3714 Uph-ph>>   2.0 .. 220.0 V; ∞ 175.0 V Uph-ph>> Pickup
3715 T Uph-ph>>   0.00 .. 100.00 sec; ∞ 1.00 sec T Uph-ph>> Time Delay
3719A Uphph>(>) RESET   0.30 .. 0.99 0.98 Uph-ph>(>) Reset ratio
3721 3U0>(>) (or Ux)   OFF
Alarm Only
ON
U>Alarm U>>Trip
OFF Operating mode 3U0 (or Ux) overvoltage prot.
3722 3U0>   1.0 .. 220.0 V; ∞ 30.0 V 3U0> Pickup (or Ux>)
3723 T 3U0>   0.00 .. 100.00 sec; ∞ 2.00 sec T 3U0> Time Delay (or T Ux>)
3724 3U0>>   1.0 .. 220.0 V; ∞ 50.0 V 3U0>> Pickup (or Ux>>)
3725 T 3U0>>   0.00 .. 100.00 sec; ∞ 1.00 sec T 3U0>> Time Delay (or T Ux>>)
3728A 3U0>(>) Stabil.   ON
OFF
ON 3U0>(>): Stabilization 3U0-Meas- urement
3729A 3U0>(>) RESET   0.30 .. 0.99 0.95 3U0>(>) Reset ratio (or Ux)
3731 U1>(>)   OFF
Alarm Only ON
U>Alarm U>>Trip
OFF Operating mode U1 overvoltage prot.
3732 U1>   2.0 .. 220.0 V; ∞ 150.0 V U1> Pickup
3733 T U1>   0.00 .. 100.00 sec; ∞ 2.00 sec T U1> Time Delay
3734 U1>>   2.0 .. 220.0 V; ∞ 175.0 V U1>> Pickup
3735 T U1>>   0.00 .. 100.00 sec; ∞ 1.00 sec T U1>> Time Delay
3736 U1> Compound   ON
OFF
OFF U1> with Compounding
3737 U1>> Compound   ON
OFF
OFF U1>> with Compounding
3739A U1>(>) RESET   0.30 .. 0.99 0.98 U1>(>) Reset ratio
3741 U2>(>)   OFF
Alarm Only
ON
U>Alarm U>>Trip
OFF Operating mode U2 overvoltage prot.
3742 U2>   2.0 .. 220.0 V; ∞ 30.0 V U2> Pickup
3743 T U2>   0.00 .. 100.00 sec; ∞ 2.00 sec T U2> Time Delay
3744 U2>>   2.0 .. 220.0 V; ∞ 50.0 V U2>> Pickup
3745 T U2>>   0.00 .. 100.00 sec; ∞ 1.00 sec T U2>> Time Delay
3749A U2>(>) RESET   0.30 .. 0.99 0.98 U2>(>) Reset ratio
3751 Uph-e<(<)   OFF
Alarm Only
ON
U<Alarm U<<Trip
OFF Operating mode Uph-e under- voltage prot.
3752 Uph-e<   1.0 .. 100.0 V; 0 30.0 V Uph-e< Pickup
3753 T Uph-e<   0.00 .. 100.00 sec; ∞ 2.00 sec T Uph-e< Time Delay
3754 Uph-e<<   1.0 .. 100.0 V; 0 10.0 V Uph-e<< Pickup
3755 T Uph-e<<   0.00 .. 100.00 sec; ∞ 1.00 sec T Uph-e<< Time Delay
3758 CURR.SUP. Uphe<   ON
OFF
ON Current supervision (Uph-e)
3759A Uph-e<(<) RESET   1.01 .. 1.20 1.05 Uph-e<(<) Reset ratio
3761 Uph-ph<(<)   OFF
Alarm Only
ON
U<Alarm U<<Trip
OFF Operating mode Uph-ph undervoltage prot.
3762 Uph-ph<   1.0 .. 175.0 V; 0 50.0 V Uph-ph< Pickup
3763 T Uph-ph<   0.00 .. 100.00 sec; ∞ 2.00 sec T Uph-ph< Time Delay
3764 Uph-ph<<   1.0 .. 175.0 V; 0 17.0 V Uph-ph<< Pickup
3765 T Uphph<<   0.00 .. 100.00 sec; ∞ 1.00 sec T Uph-ph<< Time Delay
3768 CURR.SUP.Uphph<   ON
OFF
ON Current supervision (Uph-ph)
3769A Uphph<(<) RESET   1.01 .. 1.20 1.05 Uph-ph<(<) Reset ratio
3771 U1<(<)   OFF
Alarm Only
ON
U<Alarm U<<Trip
OFF Operating mode U1 undervoltage prot.
3772 U1<   1.0 .. 100.0 V; 0 30.0 V U1< Pickup
3773 T U1<   0.00 .. 100.00 sec; ∞ 2.00 sec T U1< Time Delay
3774 U1<<   1.0 .. 100.0 V; 0 10.0 V U1<< Pickup
3775 T U1<<   0.00 .. 100.00 sec; ∞ 1.00 sec T U1<< Time Delay
3778 CURR.SUP.U1<   ON
OFF
ON Current supervision (U1)
3779A U1<(<) RESET   1.01 .. 1.20 1.05 U1<(<) Reset ratio

Frequency Protection (optional)

Addr. Parameter C Setting Options Default Setting Comments
3601 O/U FREQ. f1   ON: Alarm only
ON: with Trip
OFF
ON: Alarm only Over/Under Frequency Protection stage f1
3602 f1 PICKUP   45.50 .. 54.50 Hz 49.50 Hz f1 Pickup
3603 f1 PICKUP   55.50 .. 64.50 Hz 59.50 Hz f1 Pickup
3604 T f1   0.00 .. 600.00 sec 60.00 sec T f1 Time Delay
3611 O/U FREQ. f2   ON: Alarm only
ON: with Trip
OFF
ON: Alarm only Over/Under Frequency Protection stage f2
3612 f2 PICKUP   45.50 .. 54.50 Hz 49.00 Hz f2 Pickup
3613 f2 PICKUP   55.50 .. 64.50 Hz 57.00 Hz f2 Pickup
3614 T f2   0.00 .. 600.00 sec 30.00 sec T f2 Time Delay
3621 O/U FREQ. f3   ON: Alarm only
ON: with Trip
OFF
ON: Alarm only Over/Under Frequency Protection stage f3
3622 f3 PICKUP   45.50 .. 54.50 Hz 47.50 Hz f3 Pickup
3623 f3 PICKUP   55.50 .. 64.50 Hz 59.50 Hz f3 Pickup
3624 T f3   0.00 .. 600.00 sec 3.00 sec T f3 Time Delay
3631 O/U FREQ. f4   ON: Alarm only
ON: with Trip
OFF
ON: Alarm only Over/Under Frequency Protection stage f4
3632 f4 PICKUP   45.50 .. 54.50 Hz 51.00 Hz f4 Pickup
3633 f4 PICKUP   55.50 .. 64.50 Hz 62.00 Hz f4 Pickup
3634 T f4   0.00 .. 600.00 sec 30.00 sec T f4 Time Delay

Fault Locator

Addr. Parameter C Setting Options Default Setting Comments
3802 START   Pickup
TRIP
Pickup Start fault locator with
3805 Paral.Line Comp   NO
YES
YES Mutual coupling parall.line compensation
3806 Load Compensat.   NO
YES
NO Load Compensation
3807 two ended   ON
OFF
ON two ended fault location
3811 Tmax OUTPUT BCD   0.10 .. 180.00 sec 0.30 sec Maximum output time via BCD

Circuit Breaker Failure Protection

Addr. Parameter C Setting Options Default Setting Comments
3901 FCT BreakerFail   ON
OFF
ON Breaker Failure Protection
3902 I> BF 1A 0.05 .. 20.00 A 0.10 A Pick-up threshold I>
5A 0.25 .. 100.00 A 0.50 A
3903 1p-RETRIP (T1)   NO
YES
YES 1pole retrip with stage T1 (local trip)
3904 T1-1pole   0.00 .. 30.00 sec; ∞ 0.00 sec T1, Delay after 1pole start (local trip)
3905 T1-3pole   0.00 .. 30.00 sec; ∞ 0.00 sec T1, Delay after 3pole start (local trip)
3906 T2   0.00 .. 30.00 sec; ∞ 0.15 sec T2, Delay of 2nd stage (busbar trip)
3907 T3-BkrDefective   0.00 .. 30.00 sec; ∞ 0.00 sec T3, Delay for start with defective bkr.
3908 Trip BkrDefect.   NO
with T1-trip
with T2-trip
w/ T1/T2-trip
NO Trip output selection with defective bkr
3909 Chk BRK CONTACT   NO
YES
YES Check Breaker contacts
3912 3I0> BF 1A 0.05 .. 20.00 A 0.10 A Pick-up threshold 3I0>
5A 0.25 .. 100.00 A 0.50 A
3913 T2StartCriteria   With exp. of T1
Parallel withT1
Parallel withT1 T2 Start Criteria
3921 End Flt. stage   ON
OFF
OFF End fault protection
3922 T-EndFault   0.00 .. 30.00 sec; ∞ 2.00 sec Trip delay of end fault protection
3931 PoleDiscrepancy   ON
OFF
OFF Pole Discrepancy supervi- sion
3932 T-PoleDiscrep.   0.00 .. 30.00 sec; ∞ 2.00 sec Trip delay with pole discrepancy

Thermal Overload Protection

Addr. Parameter C Setting Options Default Setting Comments
4201 Ther. OVERLOAD   OFF
ON
Alarm Only
OFF Thermal overload protec- tion
4202 K-FACTOR   0.10 .. 4.00 1.10 K-Factor
4203 TIME CONSTANT   1.0 .. 999.9 min 100.0 min Time Constant
4204 Θ ALARM   50 .. 100 % 90 % Thermal Alarm Stage
4205 I ALARM 1A 0.10 .. 4.00 A 1.00 A Current Overload Alarm Setpoint
5A 0.50 .. 20.00 A 5.00 A
4206 CALC. METHOD   Θ max Average Θ
Θ from Imax
Θ max Method of Acquiring Temperature

Measurement Supervision

Addr. Parameter C Setting Options Default Setting Comments
2901 MEASURE. SUPERV   ON
OFF
ON Measurement Supervision
2902A BALANCE U-LIMIT   10 .. 100 V 50 V Voltage Threshold for Balance Monitoring
2903A BAL. FACTOR U   0.58 .. 0.95 0.75 Balance Factor for Voltage Monitor
2904A BALANCE I LIMIT 1A 0.10 .. 1.00 A 0.50 A Current Balance Monitor
5A 0.50 .. 5.00 A 2.50 A  
2905A BAL. FACTOR I   0.10 .. 0.95 0.50 Balance Factor for Current Monitor
2906A ΣI THRESHOLD 1A 0.10 .. 2.00 A 0.25 A Summated Current Moni- toring Threshold
5A 0.50 .. 10.00 A 1.25 A  
2907A ΣI FACTOR   0.00 .. 0.95 0.50 Summated Current Moni- toring Factor
2908A T BAL. U LIMIT   5 .. 100 sec 5 sec T Balance Factor for Voltage Monitor
2909A T BAL. I LIMIT   5 .. 100 sec 5 sec T Current Balance Monitor
2910 FUSE FAIL MON.   ON
OFF
ON Fuse Failure Monitor
2911A FFM U>(min)   10 .. 100 V 30 V Minimum Voltage Threshold U>
2912A FFM I< (max) 1A 0.05 .. 1.00 A 0.10 A Maximum Current Threshold I<
5A 0.25 .. 5.00 A 0.50 A  
2913A FFM U<max (3ph)   2 .. 100 V 15 V Maximum Voltage Threshold U< (3phase)
2914A FFM Idelta (3p) 1A 0.05 .. 1.00 A 0.10 A Delta Current Threshold (3phase)
5A 0.25 .. 5.00 A 0.50 A  
2915 V-Supervision   w/ CURR.SUP
w/ I> & CBaux
OFF
w/ CURR.SUP Voltage Failure Supervision
2916A T V-Supervision   0.00 .. 30.00 sec 3.00 sec Delay Voltage Failure Supervision
2921 T mcb   0 .. 30 ms 0 ms VT mcb operating time
2931 BROKEN WIRE   ON
OFF
Alarm only
OFF Fast broken current-wire supervision
2933 FAST Σ i SUPERV   ON
OFF
ON State of fast current summation supervis
2935A ΔI min 1A 0.05 .. 1.00 A 0.10 A Min. current diff. for wire break det.
5A 0.25 .. 5.00 A 0.50 A  
2941 φA   0 .. 359 ° 200 ° Limit setting PhiA
2942 φB   0 .. 359 ° 340 ° Limit setting PhiB
2943 I1> 1A 0.05 .. 2.00 A 0.05 A Minimum value I1>
5A 0.25 .. 10.00 A 0.25 A  
2944 U1>   2 .. 70 V 20 V Minimum value U1>

Trip Circuit Supervision

Addr. Parameter C Setting Options Default Setting Comments
4001 FCT TripSuperv.   ON
OFF
OFF TRIP Circuit Supervision is
4002 No. of BI   1 .. 2 2 Number of Binary Inputs per trip circuit
4003 Alarm Delay   1 .. 30 sec 2 sec Delay Time for alarm

Device

Addr. Parameter C Setting Options Default Setting Comments
610 FltDisp.LED/LCD   Target on PU
Target on TRIP
Target on PU Fault Display on LED / LCD
615 Spont. FltDisp.   NO
YES
NO Spontaneous display of flt.annun- ciations
625A T MIN LED HOLD   0 .. 60 min; ∞ 0 min Minimum hold time of latched LEDs
640 Start image DD   image 1
image 2
image 3
image 4
image 5
image 6
image 1 Start image Default Display

Oscillographic Fault Records

Addr. Parameter C Setting Options Default Setting Comments
402A WAVEFORMTRIGGER   Save w. Pickup
Save w. TRIP
Start w. TRIP
Save w. Pickup Waveform Capture
403A WAVEFORM DATA   Fault event
Pow.Sys.Flt.
Fault event Scope of Waveform Data
410 MAX. LENGTH   0.30 .. 5.00 sec 2.00 sec Max. length of a Waveform Capture Record
411 PRE. TRIG. TIME   0.05 .. 0.50 sec 0.25 sec Captured Waveform Prior to Trigger
412 POST REC. TIME   0.05 .. 0.50 sec 0.10 sec Captured Waveform after Event
415 BinIn CAPT.TIME   0.10 .. 5.00 sec; ∞ 0.50 sec Capture Time via Binary Input

Demand Measurement Setup

Addr. Parameter C Setting Options Default Setting Comments
2801 DMD Interval   15 Min., 1 Sub
15 Min., 3 Subs
15 Min.,15 Subs
30 Min., 1 Sub
60 Min., 1 Sub
60 Min., 1 Sub Demand Calculation Intervals
2802 DMD Sync.Time   On The Hour
15 After Hour
30 After Hour
45 After Hour
On The Hour Demand Synchronization Time

Min/Max Measurement Setup

Addr. Parameter C Setting Options Default Setting Comments
2811 MinMax cycRESET   NO
YES
YES Automatic Cyclic Reset Function
2812 MiMa RESET TIME   0 .. 1439 min 0 min MinMax Reset Timer
2813 MiMa RESETCYCLE   1 .. 365 Days 7 Days MinMax Reset Cycle Period
2814 MinMaxRES.START   1 .. 365 Days 1 Days MinMax Start Reset Cycle in