ABB / Shunt capacitor cascading failure protection (SCCFPVOC) _ Setting & highlights _ AB2135

Table of Contents

Overview

Cascading failures are series faults in shunt capacitor banks involving more than one capacitor unit (or even more than one rack). They are characterized by the presence of an unbalanced shunt capacitor bank (SCB) current. However, as the connected power system is much stronger than the SCB rating, any unbalance voltage due to cascading faults inside the capacitor bank is typically not present in the system. The “Shunt capacitor cascading failure protection” function provides protection against cascading faults and has two modes to detect the unbalances.

For more detailed information on “Shunt capacitor cascading failure protection” function, refer to ABB, Relion 670 Series manuals.

To see other supported functions, click here.


Function Identification

Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Shunt capacitor cascading failure protection SCCFPVOC 2 (I > /U <) 51 V

Signals & Setting Parameters


Function block of cascading failure protection

Function block of cascading failure protection

SCCFPVOC Input signals

SCCFPVOC Input signals
Name Type Default Description
I3P GROUP SIGNAL Group signal for current input
U3P GROUP SIGNAL Group signal for voltage input
BLOCK BOOLEAN 0 Block of function
BLKST1 BOOLEAN 0 Block of step 1
BLKST2 BOOLEAN 0 Block of step 2

SCCFPVOC Output signals

SCCFPVOC Output signals
Name Type Description
TRIP BOOLEAN General trip signal
TR1 BOOLEAN Trip signal from step 1
TR2 BOOLEAN Trip signal from step 2
START BOOLEAN General start signal
ST1 BOOLEAN Start signal from step 1
ST2 BOOLEAN Start signal from step 2
IMEAS REAL Measured current magnitude
UMEAS REAL Measured voltage magnitude

SCCFPVOC (51V) Non group settings (basic)

SCCFPVOC (51V) Non group settings (basic)
Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 – 12 1 1 Selection of one of the Global Base Value groups

SCCFPVOC (51V) Group settings (basic)

SCCFPVOC (51V) Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Disabled
Enabled
Disabled Operation Disabled/Enabled
CurrentInput NegSeq
3*ZeroSeq
3*ZeroSeq Select current signal which will be measured inside function. Note: Needs to have same value as VoltageInput
VoltageInput -NegSeq
-3*ZeroSeq
-3*ZeroSeq Select voltage signal which will be measured inside function. Note: Needs to have same value as CurrentInput
l_2nd/l_fund 10.0 – 50.0 % 1.0 40.0 Ratio of second to fundamental current harmonic in %
Operation1 Disabled
Enabled
Disabled Operation step 1 Disable/Enable
IPickup 121 – 400 %IB 1 125 Pickup current level for step 1 in % of IBase
tDef1 0.00 – 60.00 s 0.01 0.50 Definite time delay of step 1
VDepFact1 0.0330 – 0.7075 0.0001 0.0640 Voltage dependent factor for step 1. Note: it is recommended to be set as [1-(117/I>)], to follow the capacitor impedance
HarmRestr1 Disabled
Enabled
Disabled Enable block of step 1 by 2nd harmonic restrain to be used for 3I0 current only
Operation2 Disabled
Enabled
Disabled Operation step 2 Disable/Enable
pickup2 125 – 400 %IB 1 130 Pickup current level for step 2 in % of IBase
tDef2 0.00 – 60.00 s 0.01 0.50 Definite time delay of step 2
VDepFact2 0.0640 – 0.7075 0.0001 0.1000 Voltage dependent factor for step 2. Note: it is recommended to be set as [1-(117/I>>)], to follow the capacitor impedance
HarmRestr2 Disabled
Enabled
Disabled Enable block of step 2 by 2nd harmonic restrain to be used for 3I0 current only

SCCFPVOC Monitored data

SCCFPVOC Monitored data
Name Type Values (Range) Unit Description
IMEAS REAL A Measured current magnitude
UMEAS REAL kV Measured voltage magnitude

Logics & highlights


Cascading failure within SCB

Cascading failure within SCB

General voltage restrained characteristic for SCB cascading protection (Stage 1 and stage 2)

General voltage restrained characteristic for SCB cascading protection (Stage 1 and stage 2)

General voltage restrained characteristic for SCB cascading failure protection (Stage 1 and Stage 2)

General voltage restrained characteristic for SCB cascading failure protection (Stage 1 and Stage 2)

Block condition for additional zero sequence 2nd harmonic restrained feature

Block condition for additional zero sequence 2nd harmonic restrained feature

Logic Diagram of cascading failure protection

Logic Diagram of cascading failure protection