Siemens / Shaft current protection (ANSI 51GN) _ Setting & highlights _ SI5099

Table of Contents

Overview

The “Shaft current protection” function detects shaft currents of a generator via special shaft-current transformer. It prevents the damage of the bearings due to a current flow to ground, and allows a flexible evolution of the shaft current with different measuring principles.

For more detailed information on “Shaft current protection” function, refer to SIPROTEC 5 devices, V8.30 & higher manuals.

To see other supported functions, click here.


Structure/Embedding of the Function

Structure/Embedding of the Function

Setting Parameters


Setting parameters for Shaft current protection

Addr. Parameter C Setting Options Default Setting
Stage 1
_:17251:1 Stage 1:Mode   off
on
test
off
_:17251:2 Stage 1:Operate & flt.rec. blocked   no
yes
no
_:17251:3 Stage 1:Threshold   0.30 mA to 1600.00 mA 5.00 mA
_:17251:4 Stage 1:Dropout ratio   0.80 to 0.95 0.90
_:17251:6 Stage 1:Operate delay   0.00 s to 60.00 s 3.00 s
_:17251:7 Stage 1:Dropout delay   0.00 s to 60.00 s 0.00 s
_:17251:8 Stage 1:Method of measurement   fundamental comp.
3rd harmonic
1st and 3rd harmonic
fundamental comp.

Logic Diagrams & highlights


Connection of the Shaft-Current Transformer (Possible Current Flow in the Event of a Fault)

Connection of the Shaft-Current Transformer (Possible Current Flow in the Event of a Fault)

Terminals of the Shaft-Current Transformer

Terminals of the Shaft-Current Transformer

Filter options

Filter options

Logic Diagram of the General Functionality

Logic Diagram of the General Functionality

Logic Diagram of the Stage Shaft-Current Protection

Logic Diagram of the Stage Shaft-Current Protection