Overview
The “Setting groups” menu controls the activation and deactivation of up to six groups of settings in the GROUPED ELEMENTS settings menu. On a setting group change, protection elements are blocked temporarily to allow the relay to re-initialize with the new settings. The duration of the block depends on relay configuration and can last up to four cycles.
For more detailed information on “Setting groups”, refer to GE, Universal Relay (UR) family of products, Version 8.0x manuals.
To see other supported elements, click here.
Setting Parameters
Modbus memory map for Setting parameters
Products | Hex address | Register name | Range | Units | Step | Format | Default |
All except C30 | 3D60 | Setting Group for Modbus Comms (0 means group 1) | 0 to 5 | — | 1 | F001 | 0 |
" | 3D61 | Setting Groups Block | 0 to 4294967295 | — | 1 | F300 | 0 |
" | 3D63 | FlexLogic Operands to Activate Groups 2 through 6 (5 items) | 0 to 4294967295 | — | 1 | F300 | 0 |
" | 3D6D | Setting Group Function | 0 to 1 | — | 1 | F102 | 0 (Disabled) |
" | 3D6E | Setting Group Events | 0 to 1 | — | 1 | F102 | 0 (Disabled) |
" | 3D6F | Setting Groups Control Mode | 0 to 1 | — | 1 | F283 | 0 (Local) |
All except C30 | 3D70 | Setting Group 1 Name | — | — | — | F203 | (none) |
" | 3D78 | Setting Group 2 Name | — | — | — | F203 | (none) |
" | 3D80 | Setting Group 3 Name | — | — | — | F203 | (none) |
" | 3D88 | Setting Group 4 Name | — | — | — | F203 | (none) |
" | 3D90 | Setting Group 5 Name | — | — | — | F203 | (none) |
" | 3D98 | Setting Group 6 Name | — | — | — | F203 | (none) |
F102 | 0 = Disabled, 1 = Enabled | ||||||
F283 | 0 = Local, 1 = IEC61850 Client | ||||||