Overview

The “Setting groups” menu controls the activation and deactivation of up to six groups of settings in the GROUPED ELEMENTS settings menu. On a setting group change, protection elements are blocked temporarily to allow the relay to re-initialize with the new settings. The duration of the block depends on relay configuration and can last up to four cycles.

For more detailed information on “Setting groups”, refer to GE, Universal Relay (UR) family of products, Version 8.0x manuals.

To see other supported elements, click here.


Setting Parameters


Modbus memory map for Setting parameters

Products Hex address Register name Range Units Step Format Default
All except C30 3D60 Setting Group for Modbus Comms (0 means group 1) 0 to 5 1 F001 0
" 3D61 Setting Groups Block 0 to 4294967295 1 F300 0
" 3D63 FlexLogic Operands to Activate Groups 2 through 6 (5 items) 0 to 4294967295 1 F300 0
" 3D6D Setting Group Function 0 to 1 1 F102 0 (Disabled)
" 3D6E Setting Group Events 0 to 1 1 F102 0 (Disabled)
" 3D6F Setting Groups Control Mode 0 to 1 1 F283 0 (Local)
All except C30 3D70 Setting Group 1 Name F203 (none)
" 3D78 Setting Group 2 Name F203 (none)
" 3D80 Setting Group 3 Name F203 (none)
" 3D88 Setting Group 4 Name F203 (none)
" 3D90 Setting Group 5 Name F203 (none)
" 3D98 Setting Group 6 Name F203 (none)
F102 0 = Disabled, 1 = Enabled
F283 0 = Local, 1 = IEC61850 Client

Logics & highlights


Logic diagram for Control Mode setting

Logic diagram for Control Mode setting

Example of FlexLogic control of a setting group

Example of FlexLogic control of a setting group