Table of Contents

Siemens / Sensitive ground fault detection _ Setting & highlights _ SI5033

Table of Contents

Overview

The “Directional sensitive ground fault detection” function (ANSI 67Ns) serves for directional detection of permanent ground faults in isolated or resonant-grounded systems, directional detection of fast extinguishing transient ground faults in isolated or resonant-grounded systems, determination of the faulty phase, and detection of high-impedance ground faults in effectively (solidly) or low-impedance (semi-solidly) grounded systems.

The “Non-directional sensitive ground fault detection” function (ANSI 51Ns) serves for ground-fault detection in isolated or resonant-grounded systems, and for detection of high-impedance ground faults in effectively (solidly) or low-impedance (semi-solidly) grounded systems.

For more detailed information on “Sensitive ground fault Detection” functions, refer to SIPROTEC 5 devices, V8.30 & higher manuals.

To see other supported functions, click here.


Structure/Embedding of the Directional Function in Protection Function Groups

Structure/Embedding of the Directional Function in Protection Function Groups

Structure/Embedding of the Non-Directional Function in Protection Function Groups

Structure/Embedding of the Non-Directional Function in Protection Function Groups

Setting Parameters


General setting parameters (Directional sensitive ground-fault detection)

Addr. Parameter C Setting Options Default Setting
General
_:2311:121 General:Network topology   ring/meshed
radial
ring/meshed
_:2311:101 General:Decay time V0   0.03 s to 0.20 s 0.10 s
_:2311:102 General:Dropout delay   0.00 s to 60.00 s 1.00 s
_:2311:103 General:Core balance CT- current 1 1 A @ 100 Irated 0.030 A to 35.000 A 0.050 A
5 A @ 100 Irated 0.15 A to 175.00 A 0.25 A
1 A @ 50 Irated 0.030 A to 35.000 A 0.050 A
5 A @ 50 Irated 0.15 A to 175.00 A 0.25 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 0.050 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 0.250 A
_:2311:104 General:Core balance CT- current 2 1 A @ 100 Irated 0.030 A to 35.000 A 1.000 A
5 A @ 100 Irated 0.15 A to 175.00 A 5.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.000 A
5 A @ 50 Irated 0.15 A to 175.00 A 5.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.000 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 5.000 A
_:2311:105 General:CT angle error at I1   0.0° to 5.0° 0.0°
_:2311:106 General:CT angle error at I2   0.0° to 5.0° 0.0°
_:2311:119 General:Block. group indications   no
yes
no

General setting parameters (Non-directional sensitive ground-fault detection)

Addr. Parameter C Setting Options Default Setting
General
_:2311:102 General:Dropout delay   0.00 s to 60.00 s 1.00 s
_:2311:119 General:Block. group indications   no
yes
no

Setting parameters for Directional 3I0 Stage with Cos φ or Sin φ Measurement

Addr. Parameter C Setting Options Default Setting
3I0> cos/sinφ1
_:12601:1 3I0> cos/sinφ1:Mode   off
on
test
off
_:12601:2 3I0> cos/sinφ1:Operate & flt.rec. blocked   no
yes
no
_:12601:10 3I0> cos/sinφ1:Blk. by meas.-volt. failure   no
yes
yes
_:12601:111 3I0> cos/sinφ1:Blk.by interm.gnd.flt.   no
yes
no
_:12601:27 3I0> cos/sinφ1:Blk. w. inrush curr. detect.   no
yes
no
_:12601:110 3I0> cos/sinφ1:Blk. after fault extinction   no
yes
yes
_:12601:108 3I0> cos/sinφ1:Direc- tional mode   forward
reverse
forward
_:12601:109 3I0> cos/sinφ1:Dir. measuring method   cos φ
sin φ
cos φ
_:12601:107 3I0> cos/sinφ1:φ correc- tion   -45° to 45°
_:12601:102 3I0> cos/ sinφ1:Min.polar.3I0> for dir.det. 1 A @ 100 Irated 0.030 A to 35.000 A 0.030 A
5 A @ 100 Irated 0.15 A to 175.00 A 0.15 A
1 A @ 50 Irated 0.030 A to 35.000 A 0.030 A
5 A @ 50 Irated 0.15 A to 175.00 A 0.15 A
1 A @ 1.6 Irated 0.001 A to 35.000 A 0.030 A
5 A @ 1.6 Irated 0.005 A to 35.000 A 0.150 A
_:12601:105 3I0> cos/sinφ1:α1 reduc- tion dir. area   1° to 15°
_:12601:106 3I0> cos/sinφ1:α2 reduc- tion dir. area   1° to 15°
_:12601:101 3I0> cos/sinφ1:3I0> threshold value 1 A @ 100 Irated 0.030 A to 35.000 A 0.050 A
5 A @ 100 Irated 0.15 A to 175.00 A 0.25 A
1 A @ 50 Irated 0.030 A to 35.000 A 0.050 A
5 A @ 50 Irated 0.15 A to 175.00 A 0.25 A
1 A @ 1.6 Irated 0.001 A to 35.000 A 0.050 A
5 A @ 1.6 Irated 0.005 A to 35.000 A 0.250 A
_:12601:103 3I0> cos/sinφ1:V0> threshold value   0.300 V to 200.000 V 30.000 V
_:12601:104 3I0> cos/sinφ1:Dir. determination delay   0.00 s to 60.00 s 0.10 s
_:12601:6 3I0> cos/sinφ1:Operate delay   0.00 s to 60.00 s 2.00 s

Setting parameters for Directional Transient Ground-Fault Stage

Addr. Parameter C Setting Options Default Setting
Trans.Gnd.flt1
_:13021:1 Trans.Gnd.flt1:Mode   off
on
test
off
_:13021:2 Trans.Gnd.flt1:Operate & flt.rec. blocked   no
yes
no
_:13021:10 Trans.Gnd.flt1:Blk. by meas.-volt. failure   no
yes
yes
_:13021:107 Trans.Gnd.flt1:Blk. after fault extinction   no
yes
yes
_:13021:108 Trans.Gnd.flt1:Operate functionality   no
yes
no
_:13021:106 Trans.Gnd.flt1:Direc- tional mode   forward
reverse
forward
_:13021:103 Trans.Gnd.flt1:V0> threshold value   0.300 V to 200.000 V 15.000 V
_:13021:105 Trans.Gnd.flt1:Maximum operational V0   0.300 V to 200.000 V 3.000 V
_:13021:109 Trans.Gnd.flt1:3I0> threshold for pickup 1 A @ 100 Irated 0.000 A to 35.000 A 0.000 A
5 A @ 100 Irated 0.00 A to 175.00 A 0.00 A
1 A @ 50 Irated 0.000 A to 35.000 A 0.000 A
5 A @ 50 Irated 0.00 A to 175.00 A 0.00 A
1 A @ 1.6 Irated 0.000 A to 1.600 A 0.000 A
5 A @ 1.6 Irated 0.000 A to 8.000 A 0.000 A
_:13021:104 Trans.Gnd.flt1:3I0> threshold for operate 1 A @ 100 Irated 0.000 A to 35.000 A 0.030 A
5 A @ 100 Irated 0.00 A to 175.00 A 0.15 A
1 A @ 50 Irated 0.000 A to 35.000 A 0.030 A
5 A @ 50 Irated 0.00 A to 175.00 A 0.15 A
1 A @ 1.6 Irated 0.000 A to 1.600 A 0.030 A
5 A @ 1.6 Irated 0.000 A to 8.000 A 0.150 A
_:13021:6 Trans.Gnd.flt1:Operate delay   0.00 s to 60.00 s 0.50 s
_:13021:7 Trans.Gnd.flt1:Dropout delay   0.00 s to 60.00 s 0.00 s

Setting parameters for Directional 3I0 Stage with φ(V0,3I0) Measurement

Addr. Parameter C Setting Options Default Setting
3I0> φ(VI) #
_:1 3I0> φ(VI) #:Mode   off
on
test
off
_:2 3I0> φ(VI) #:Operate & flt.rec. blocked   no
yes
no
_:10 3I0> φ(VI) #:Blk. by
meas.-volt. failure
  no
yes
yes
_:111 3I0> φ(VI) #:Blk.by
interm.gnd.flt.
  no
yes
no
_:27 3I0> φ(VI) #:Blk. w.
inrush curr. detect.
  no
yes
no
_:106 3I0> φ(VI) #:Directional mode   non-directional
forward
reverse
forward
_:104 3I0> φ(VI) #:Rotation angle of ref. volt.   -180° to 180° -45°
_:103 3I0> φ(VI) #:Forward section +/-   0° to 180° 88°
_:102 3I0> φ(VI) #:Min. V0>
for dir. determ.
  0.300 V to 200.000 V 2.000 V
_:101 3I0> φ(VI) #:3I0>
threshold value
1 A @ 100 Irated 0.030 A to 35.000 A 0.050 A
5 A @ 100 Irated 0.15 A to 175.00 A 0.25 A
1 A @ 50 Irated 0.030 A to 35.000 A 0.050 A
5 A @ 50 Irated 0.15 A to 175.00 A 0.25 A
1 A @ 1.6 Irated 0.001 A to 35.000 A 0.050 A
5 A @ 1.6 Irated 0.005 A to 35.000 A 0.250 A
_:105 3I0> φ(VI) #:Dir. deter- mination delay   0.00 s to 60.00 s 0.10 s
_:6 3I0> φ(VI) #:Operate delay   0.00 s to 100.00 s 0.50 s

Setting parameters for Directional Y0 Stage with G0 or B0 Measurement

Addr. Parameter C Setting Options Default Setting
Y0> G0/B0 #
_:1 Y0> G0/B0 #:Mode   off
on
test
off
_:2 Y0> G0/B0 #:Operate & flt.rec. blocked   no
yes
no
_:10 Y0> G0/B0 #:Blk. by meas.-volt. failure   no
yes
yes
_:111 Y0> G0/B0 #:Blk.by interm.gnd.flt.   no
yes
no
_:27 Y0> G0/B0 #:Blk. w.
inrush curr. detect.
  no
yes
no
_:110 Y0> G0/B0 #:Blk. after fault extinction   no
yes
yes
_:108 Y0> G0/B0 #:Directional mode   forward
reverse
forward
_:109 Y0> G0/B0 #:Dir. meas- uring method   G0
B0
G0
_:107 Y0> G0/B0 #:φ correc- tion   -45° to 45°
_:102 Y0> G0/B0 #:Polarized G0/B0 threshold   0.10 mS to 100.00 mS 2.00 mS
_:105 Y0> G0/B0 #:α1 reduc- tion dir. area   1° to 15°
_:106 Y0> G0/B0 #:α2 reduc- tion dir. area   1° to 15°
_:101 Y0> G0/B0 #:3I0>
release thresh. value
1 A @ 100 Irated 0.030 A to 35.000 A 0.030 A
5 A @ 100 Irated 0.15 A to 175.00 A 0.15 A
1 A @ 50 Irated 0.030 A to 35.000 A 0.030 A
5 A @ 50 Irated 0.15 A to 175.00 A 0.15 A
1 A @ 1.6 Irated 0.001 A to 35.000 A 0.030 A
5 A @ 1.6 Irated 0.005 A to 35.000 A 0.150 A
_:103 Y0> G0/B0 #:V0>
threshold value
  0.300 V to 200.000 V 30.000 V
_:104 Y0> G0/B0 #:Dir. deter- mination delay   0.00 s to 60.00 s 0.10 s
_:6 Y0> G0/B0 #:Operate delay   0.00 s to 60.00 s 2.00 s

Setting parameters for Directional Stage with Phasor Measurement of a Harmonic

Addr. Parameter C Setting Options Default Setting
V0>dir.harm.#
_:1 V0>dir.harm.#:Mode   off
on
test
off
_:2 V0>dir.harm.#:Operate & flt.rec. blocked   no
yes
no
_:10 V0>dir.harm.#:Blk. by meas.-volt. failure   no
yes
yes
_:111 V0>dir.harm.#:Blk.by interm.gnd.flt.   no
yes
no
_:106 V0>dir.harm.#:Direc- tional mode   non-directional
forward
reverse
forward
_:103 V0>dir.harm.#:Forward section +/-   0° to 90° 80°
_:102 V0>dir.harm.#:V0> threshold value   0.300 V to 200.000 V 20.000 V
_:201 V0>dir.harm.#:Harmonic selection   3rd harmonic
5th harmonic
7th harmonic
5th harmonic
_:203 V0>dir.harm.#:Min. 3I0> harmonic 1 A @ 100 Irated 0.030 A to 35.000 A 0.030 A
5 A @ 100 Irated 0.15 A to 175.00 A 0.15 A
1 A @ 50 Irated 0.030 A to 35.000 A 0.030 A
5 A @ 50 Irated 0.15 A to 175.00 A 0.15 A
1 A @ 1.6 Irated 0.001 A to 35.000 A 0.030 A
5 A @ 1.6 Irated 0.005 A to 35.000 A 0.150 A
_:204 V0>dir.harm.#:3I0 harm. dropout ratio   0.10 to 0.95 0.60
_:110 V0>dir.harm.#:Dir.-result extension   0.00 s to 60.00 s 5.00 s
_:105 V0>dir.harm.#:Dir. determination delay   0.00 s to 60.00 s 0.00 s
_:6 V0>dir.harm.#:Operate delay   0.00 s to 60.00 s 1.00 s

Setting parameters for Non-Directional V0 Stage with Zero-Sequence Voltage/Residual Voltage

Addr. Parameter C Setting Options Default Setting
V0> 1
_:12391:1 V0> 1:Mode   off
on
test
off
_:12391:2 V0> 1:Operate & flt.rec. blocked   no
yes
no
_:12391:10 V0> 1:Blk. by meas.-volt. failure   no
yes
yes
_:12391:109 V0> 1:Detection of faulty phase   no
yes
no
_:12391:8 V0> 1:Method of meas- urement   fundamental comp.
fund. comp. long filter
RMS value
fundamental comp.
_:12391:3 V0> 1:Threshold   0.300 V to 200.000 V 30.000 V
_:12391:4 V0> 1:Dropout ratio   0.90 to 0.99 0.95
_:12391:107 V0> 1:Pickup delay   0.00 s to 60.00 s 0.00 s
_:12391:6 V0> 1:Operate delay   0.00 s to 100.00 s 3.00 s
_:12391:101 V0> 1:V> healthy ph-to- gnd volt.   0.300 V to 200.000 V 70.000 V
_:12391:104 V0> 1:V< faulty ph-to- gnd volt.   0.300 V to 200.000 V 30.000 V

Setting parameters for Non-Directional 3I0 Stage

Addr. Parameter C Setting Options Default Setting
3I0> #
_:1 3I0> #:Mode   off
on
test
off
_:2 3I0> #:Operate & flt.rec. blocked   no
yes
no
_:27 3I0> #:Blk. w. inrush curr. detect.   no
yes
no
_:103 3I0> #:Blk. w. 2nd harm. gnd. det.   no
yes
no
_:8 3I0> #:Method of meas- urement   fundamental comp.
RMS value
fundamental comp.
_:3 3I0> #:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 0.050 A
5 A @ 100 Irated 0.15 A to 175.00 A 0.25 A
1 A @ 50 Irated 0.030 A to 35.000 A 0.050 A
5 A @ 50 Irated 0.15 A to 175.00 A 0.25 A
1 A @ 1.6 Irated 0.001 A to 35.000 A 0.050 A
5 A @ 1.6 Irated 0.005 A to 35.000 A 0.250 A
_:102 3I0> #:Pickup delay   0.00 s to 60.00 s 0.00 s
_:6 3I0> #:Operate delay   0.00 s to 100.00 s 0.30 s

Setting parameters for Non-Directional Y0 Stage

Addr. Parameter C Setting Options Default Setting
Y0> #
_:1 Y0> #:Mode   off
on
test
off
_:2 Y0> #:Operate & flt.rec. blocked   no
yes
no
_:10 Y0> #:Blk. by meas.-volt. failure   no
yes
yes
_:27 Y0> #:Blk. w. inrush curr. detect.   no
yes
no
_:101 Y0> #:V0> threshold value   0.300 V to 200.000 V 5.000 V
_:102 Y0> #:Threshold Y0>   0.10 mS to 100.00 mS 2.00 mS
_:103 Y0> #:Pickup delay   0.00 s to 60.00 s 0.00 s
_:6 Y0> #:Operate delay   0.00 s to 60.00 s 0.30 s

Setting parameters for Non-Directional 3I0 Harmonic Stage

Addr. Parameter C Setting Options Default Setting
3I0> harmonic#
_:1 3I0> harmonic#:Mode   off
on
test
off
_:2 3I0> harmonic#:Operate & flt.rec. blocked   no
yes
no
_:201 3I0>
harmonic#:Harmonic selection
  3rd harmonic
5th harmonic
7th harmonic
5th harmonic
_:202 3I0> harmonic#:3I0 harm. threshold 1 A @ 100 Irated 0.030 A to 35.000 A 0.030 A
5 A @ 100 Irated 0.15 A to 175.00 A 0.15 A
1 A @ 50 Irated 0.030 A to 35.000 A 0.030 A
5 A @ 50 Irated 0.15 A to 175.00 A 0.15 A
1 A @ 1.6 Irated 0.001 A to 35.000 A 0.030 A
5 A @ 1.6 Irated 0.005 A to 35.000 A 0.150 A
_:203 3I0> harmonic#:3I0 harm. dropout ratio   0.10 to 0.95 0.60
_:204 3I0> harmonic#:Stabili- zation counter   1 to 10 4
_:110 3I0> harmonic#:Pickup extension time   0.00 s to 60.00 s 0.00 s
_:6 3I0> harmonic#:Operate delay   0.00 s to 60.00 s 1.00 s

Setting parameters for Pulse-Pattern Detection Stage

Addr. Parameter C Setting Options Default Setting
Pulse detect.#
_:1 Pulse detect.#:Mode   off
on
test
off
_:2 Pulse detect.#:Operate & flt.rec. blocked   no
yes
no
_:102 Pulse detect.#:V0> threshold value   0.300 V to 200.000 V 30.000 V
_:101 Pulse detect.#:3I0> threshold value 1 A @ 100 Irated 0.030 A to 35.000 A 0.200 A
5 A @ 100 Irated 0.15 A to 175.00 A 1.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 0.200 A
5 A @ 50 Irated 0.15 A to 175.00 A 1.00 A
1 A @ 1.6 Irated 0.001 A to 35.000 A 0.200 A
5 A @ 1.6 Irated 0.005 A to 35.000 A 1.000 A
_:103 Pulse detect.#:3I0 delta pulse off-on   2 % to 50 % 10 %
_:104 Pulse detect.#:Pulse-on duration   0.20 s to 10.00 s 1.00 s
_:105 Pulse detect.#:Pulse-off duration   0.20 s to 10.00 s 1.50 s
_:109 Pulse detect.#:Max.tolera.puls e-on or off   0.02 s to 2.00 s 0.15 s
_:107 Pulse detect.#:No. of pulses for operate   2 to 100 3
_:108 Pulse detect.#:Moni- toring time(in pulses)   2 to 100 5

Setting parameters for Intermittent Ground-Fault Blocking Stage

Addr. Parameter C Setting Options Default Setting
Blk.interm.GF
_:20161:1 Blk.interm.GF:Mode   off
on
test
off
_:20161:3 Blk.interm.GF:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.000 A
5 A @ 100 Irated 0.15 A to 175.00 A 5.00 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.000 A
5 A @ 50 Irated 0.15 A to 175.00 A 5.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.000 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 5.000 A
_:20161:104 Blk.interm.GF:No.of pulses for interm.GF   2 to 50 3
_:20161:107 Blk.interm.GF:Reset time   1.00 s to 600.00 s 5.00 s

Logic Diagrams & highlights


Logic Diagram of the Cross-Stage Functionality of the Directional Function

Logic Diagram of the Cross-Stage Functionality of the Directional Function

Logic Diagram of the Cross-Stage Functionality of the Non-Directional Function

Logic Diagram of the Cross-Stage Functionality of the Non-Directional Function

Sign Definition for the Measured Value

Sign Definition for the Measured Value

Correction of the Transmission Characteristic Curve of a Core Balance Current Transformer

Correction of the Transmission Characteristic Curve of a Core Balance Current Transformer

Logic Diagram of the Group-Indication Blocking of the Directional and Non-Directional Functions

Logic Diagram of the Group-Indication Blocking of the Directional and Non-Directional Functions

Logic Diagram of the Stage Control

Logic Diagram of the Stage Control

Logic Diagram of the Directional 3I0 Stage with Cos φ or Sin φ Measurement

Logic Diagram of the Directional 3I0 Stage with Cos φ or Sin φ Measurement

Direction-Characteristic Curve with Cos φ Measurement

Direction-Characteristic Curve with Cos φ Measurement

Turning the Direction-Characteristic Curves with Cos φ Measurement with Angle Correction

Turning the Direction-Characteristic Curves with Cos φ Measurement with Angle Correction

Direction-Characteristic Curve with Sin φ Measurement

Direction-Characteristic Curve with Sin φ Measurement

Logic Diagram of the Stage Control

Logic Diagram of the Stage Control

Logic Diagram of the Directional Transient Ground-Fault Stage

Logic Diagram of the Directional Transient Ground-Fault Stage

Trip Logic Diagram

Trip Logic Diagram

Logic Diagram of the Stage Control

Logic Diagram of the Stage Control

Logic Diagram of the Directional 3I0 Stage with φ (V0,3I0) Measurement

Logic Diagram of the Directional 3I0 Stage with φ (V0,3I0) Measurement

Directional Characteristic in Forward Mode

Directional Characteristic in Forward Mode

Logic Diagram of the Stage Control

Logic Diagram of the Stage Control

Logic Diagram of the Directional Y0 Stage with G0 or B0 Measurement

Logic Diagram of the Directional Y0 Stage with G0 or B0 Measurement

Direction-Characteristic Curve for the G0 Measurement

Direction-Characteristic Curve for the G0 Measurement

Turning the Direction-Characteristic Curves with G0 Measurement with Angle Correction

Turning the Direction-Characteristic Curves with G0 Measurement with Angle Correction

Direction-Characteristic Curve for the B0 Measurement

Direction-Characteristic Curve for the B0 Measurement

Logic Diagram of the Directional Stage with Phasor Measurement of a Harmonic

Logic Diagram of the Directional Stage with Phasor Measurement of a Harmonic

Logic Diagram of the Start Conditions and of the Direction Determination

Logic Diagram of the Start Conditions and of the Direction Determination

Direction Characteristic

Direction Characteristic

Logic Diagram of the Non-Directional V0 Stage with Zero-Sequence Voltage/Residual Voltage

Logic Diagram of the Non-Directional V0 Stage with Zero-Sequence Voltage/Residual Voltage

Logic Diagram of the Non-Directional 3I0 Stage

Logic Diagram of the Non-Directional 3I0 Stage

Logic Diagram of the Non-Directional Y0 Stage

Logic Diagram of the Non-Directional Y0 Stage

Logic Diagram of the Non-Directional 3I0 Harmonic Stage

Logic Diagram of the Non-Directional 3I0 Harmonic Stage

Network that Uses the Pulse-Pattern Detection

Network that Uses the Pulse-Pattern Detection

Current Pulse Pattern in the Overcompensated System

Current Pulse Pattern in the Overcompensated System

Logic Diagram of the Pulse-Pattern Detection Stage

Logic Diagram of the Pulse-Pattern Detection Stage

Pickup and Operate Time

Pickup and Operate Time

Logic Diagram of the Intermittent Ground-Fault Blocking Stage

Logic Diagram of the Intermittent Ground-Fault Blocking Stage