Table of Contents

GE / Selector switch _ Element settings & highlights _ GU8244

Table of Contents

Overview

The “Selector switch” element is intended to replace a mechanical selector switch. Typical applications include setting group control or control of multiple logic sub-circuits in user-programmable logic.

For more detailed information on “Selector switch” element, refer to GE, Universal Relay (UR) family of products, Version 8.0x manuals.

To see other supported elements, click here.


Setting Parameters


Modbus memory map for Setting parameters

Products Hex address Register name Range Units Step Format Default
All except B90 6848 Selector 1 Function 0 to 1 1 F102 0 (Disabled)
" 6849 Selector 1 Range 1 to 7 1 F001 7
" 684A Selector 1 Timeout 3 to 60 s 0.1 F001 50
" 684B Selector 1 Step Up 0 to 4294967295 1 F300 0
" 684D Selector 1 Step Mode 0 to 1 1 F083 0 (Time-out)
" 684E Selector 1 Acknowledge 0 to 4294967295 1 F300 0
" 6850 Selector 1 Bit0 0 to 4294967295 1 F300 0
" 6852 Selector 1 Bit1 0 to 4294967295 1 F300 0
" 6854 Selector 1 Bit2 0 to 4294967295 1 F300 0
" 6856 Selector 1 Bit Mode 0 to 1 1 F083 0 (Time-out)
" 6857 Selector 1 Bit Acknowledge 0 to 4294967295 1 F300 0
" 6859 Selector 1 Power Up Mode 0 to 2 1 F084 0 (Restore)
" 685A Selector 1 Target 0 to 2 1 F109 0 (Self-reset)
" 685B Selector 1 Events 0 to 1 1 F102 0 (Disabled)
" 685C Reserved (10 items) 1 F001 0
" 6866 …Repeated for Selector 2          
F102 0 = Disabled, 1 = Enabled
F109 0 = Self-reset, 1 = Latched, 2 = Disabled
F083 0 = Time-out, 1 = Acknowledge
F084 0 = Restore, 1 = Synchronize, 2 = Sync/Restore

Logics & highlights


The three-bit control word

The three-bit control word

Selector 1 events (if enabled)

SELECTOR 1 EVENTS (if enabled)

Time-out mode

Time-out mode

Acknowledge mode

Acknowledge mode

Application example

Application example

Selector switch logic

Selector switch logic