Overview
The function “Rotor ground fault protection (1-3 Hz)” monitors the rotor circuit of electrical synchronous machines (generator, motor) for a ground fault, and the rotor circuit of asynchronous machines for a ground fault if the rotor circuit is accessible via a slip ring. It detects faults by coupling a low-frequency square-wave voltage into the rotor circuit and monitoring the rotor ground current.
For more detailed information on “Rotor ground fault protection (1-3 Hz)” function, refer to SIPROTEC 5 devices, V8.30 & higher manuals.
To see other supported functions, click here.
Structure/Embedding of the Function
Setting Parameters
General setting parameters
Addr. | Parameter | C | Setting Options | Default Setting |
General | ||||
_:2311:103 | General:Threshold Qc < | 0.00 mAs to 1.00 mAs | 0.02 mAs | |
_:2311:104 | General:Brush supervi- sion | off on |
off | |
_:2311:106 | General:Dropout delay | 0.00 s to 60.00 s | 1.00 s | |
_:2311:101 | General:V-control | Setting options depend on configuration | ||
_:2311:102 | General:V-measurement | Setting options depend on configuration | ||
Setting parameters for R< Stage
Addr. | Parameter | C | Setting Options | Default Setting |
RGF 1-3Hz R< 1 | ||||
_:17341:1 | RGF 1-3Hz R< 1:Mode | off on test |
off | |
_:17341:2 | RGF 1-3Hz R< 1:Operate & flt.rec. blocked | no yes |
yes | |
_:17341:3 | RGF 1-3Hz R< 1:Threshold R < |
1.0 kΩ to 80.0 kΩ | 40.0 kΩ | |
_:17341:6 | RGF 1-3Hz R< 1:Operate delay | 0.00 s to 60.00 s | 10.00 s | |
RGF 1-3Hz R< 2 | ||||
_:17342:1 | RGF 1-3Hz R< 2:Mode | off on test |
off | |
_:17342:2 | RGF 1-3Hz R< 2:Operate & flt.rec. blocked | no yes |
no | |
_:17342:3 | RGF 1-3Hz R< 2:Threshold R < |
1.0 kΩ to 80.0 kΩ | 5.0 kΩ | |
_:17342:6 | RGF 1-3Hz R< 2:Operate delay | 0.00 s to 60.00 s | 1.00 s | |
Setting parameters for Test stage
Addr. | Parameter | C | Setting Options | Default Setting |
RGF 1-3Hz tst# | ||||
_:1 | RGF 1-3Hz tst#:Mode | off on test |
off | |
_:101 | RGF 1-3Hz tst#:Test resistor | 1.0 kΩ to 10.0 kΩ | 3.3 kΩ | |