Overview
The “Rotor ground fault protection (Rgnd<, fn)” function monitors the rotor circuit of electrical synchronous machines (generator, motor) for a ground fault, and the rotor circuit of asynchronous machines for a ground fault if the rotor circuit is accessible via a slip ring. It detects faults by injecting a rated-frequency voltage into a rotor circuit and monitoring the rotor ground current.
For more detailed information on “Rotor ground fault protection (Rgnd<, fn)” function, refer to SIPROTEC 5 devices, V8.30 & higher manuals.
To see other supported functions, click here.
Structure/Embedding of the Function
Setting Parameters
Setting parameters for Rotor ground fault protection (Rgnd<, fn)
Addr. | Parameter | C | Setting Options | Default Setting |
General | ||||
_:2311:109 | General:Supervision | off on |
on | |
_:2311:106 | General:I< supervision | 1.0 mA to 50.0 mA | 2.0 mA | |
_:2311:101 | General:Correction angle | -1500 ° to 1500 ° | 0 ° | |
_:2311:103 | General:X-coupling | -100 Ω to 800 Ω | 398 Ω | |
_:2311:104 | General:R-coupling | 0 Ω to 999 Ω | 50 Ω | |
_:2311:108 | General:V-RGF external source | no yes |
no | |
RGF resistance 1 | ||||
_:15961:1 | RGF resistance 1:Mode | off on test |
off | |
_:15961:2 | RGF resistance 1:Operate & flt.rec. blocked | no yes |
yes | |
_:15961:3 | RGF resistance 1:Threshold | 1.0 kΩ to 30.0 kΩ | 10.0 kΩ | |
_:15961:6 | RGF resistance 1:Operate delay | 0.00 s to 60.00 s | 10.00 s | |
_:15961:7 | RGF resistance 1:Dropout delay | 0.00 s to 60.00 s | 0.00 s | |
RGF resistance 2 | ||||
_:15962:1 | RGF resistance 2:Mode | off on test |
off | |
_:15962:2 | RGF resistance 2:Operate & flt.rec. blocked | no yes |
no | |
_:15962:3 | RGF resistance 2:Threshold | 1.0 kΩ to 30.0 kΩ | 2.0 kΩ | |
_:15962:6 | RGF resistance 2:Operate delay | 0.00 s to 60.00 s | 0.50 s | |
_:15962:7 | RGF resistance 2:Dropout delay | 0.00 s to 60.00 s | 0.00 s | |