Table of Contents

Siemens / Reverse power protection (ANSI 32R) _ Setting & highlights _ SI5085

Table of Contents

Overview

The “Reverse power protection” monitors the motor operation of generators and thus detects driving-power failure. It prevents endangering the turbine (e.g. the turbine-blade damage due to overheating) by opening the circuit breaker of the system, and protects a turbo-generator set.

For more detailed information on “Reverse power protection” function, refer to SIPROTEC 5 devices, V8.30 & higher manuals.

To see other supported functions, click here.


Structure/Embedding of the Function

Structure/Embedding of the Function

Setting Parameters


General setting parameters

Addr. Parameter C Setting Options Default Setting
General
_:2311:101 General:Angle correction   -10.00 ° to 10.00 ° 0.00 °
_:2311:102 General:Minimum voltage V1   0.300 V to 60.000 V 5.000 V

Setting parameters for stage 1 of Reverse power protection

Addr. Parameter C Setting Options Default Setting
Stage 1
_:991:1 Stage 1:Mode   off
on
test
off
_:991:2 Stage 1:Operate & flt.rec. blocked   no
yes
no
_:991:3 Stage 1:Threshold   -30.00 % to -0.30 % -1.00 %
_:991:4 Stage 1:Dropout ratio   0.40 to 0.99 0.60
_:991:102 Stage 1:Dropout delay   0.00 s to 60.00 s 0.00 s
_:991:6 Stage 1:Operate delay   0.00 s to 60.00 s 10.00 s
_:991:103 Stage 1:Operate delay stop valve   0.00 s to 60.00 s 1.00 s

Logic Diagrams & highlights


Logic Diagram of the Cross-Stage Functionality

Logic Diagram of the Cross-Stage Functionality

Power Calculation and Angle Correction

Power Calculation and Angle Correction

Logic Diagram of the Reverse-Power Protection Stage

Logic Diagram of the Reverse-Power Protection Stage

Consumed active power

Logic Diagram of the Reverse-Power Protection Stage